Loading...
15-310-009TURNING VAIN FOR SMACNA STANDARDS. M1 TYP. 90-DEGREE VANED NOT TO SCALE ELBOW DETAIL 4" TOILET EXHAUST ,,n DUCT (SHEETMETAL) VIBRATION HANGER SPRING TYPE W /NEOPRENE L ISOLATOR 3/8" THREADED RODS 0 V WHITE CEILING GRILLE NOTES 1.- PROVIDE BACKDRAFT DAMPER W/ BIRDSCREEN 2.- FLASH & SEAL WALL AND ROOF CAP 3.- PROVIDE INTERNAL ISOLATION AND SOUND INSULATION 4.- SUPPORT FAN FROM STRUCTURE M2 TYP. CABINET EXHAUST FAN DETAIL NOT TO SCALE CAULK TO PROVIDE`%/ WATERTIGHT SEAL . WALL CAP WITH BUILT -IN SPRING LOADED DAMPER AND RUBBERIZED GASKET DUCT CLAMP WALL WALL e ♦ i . ♦ e M3 WALL CAP DETAIL NOT TO SCALE I VENT LINE WITH PERFORATED CAP. 3" ABOVE TOP OF PRIMARY DRAIN PAN TEE C.O. PLUG (SCREWED) j UNION II CONNEC' FJ" TSP +1" A. SLOPE DRAIN LINE TO TSP +1" CONDENSATE RECEPTOR (MIN. (3' MIN.) 1/8" PER FOOT) B. DRAIN LINE SHALL BE COPPER TYPE "L" AND INSULATED. C. TSP = FAN TOTAL STATIC PRESSURE. DETAIL CONDENSATE P-TRAP NOT • SCALE B_ C MECHANICAL DRAWING INDEX DRAWING DESCRIPTION 1 M0.1 MECHANICAL GENERAL NOTES, SYMBOLS AND DETAILS - {- ------------ _ ............ ....... _.... ......... .------ .........._...... ..._._.. _..........- ._._.._........ -.. - ._......... - 2 Ml-1 MECHANICAL CEILING PLAN, SCHEDULES AND NOTES STRAP HANGERS -17- HANGER STRAPS 60" UNLESS FOOT OF STRAP IS PLACED UNDER A BOTTOM REINFORCEMENT. I' INIMUM -SCREWS MAY BE OMITTED IF HANGER LOOPS LOAD RATED �ASTENERS 24" DLAL MAX. Ll 50" DUI. MAX. BAND OF SAME SIZE AS HANGER STRAP. HANGERS MUST NOT DEFORM DUCT SHAPE GER RODS, WIRES OR STRAPS BJWk . , " - - `9i } -s x P n s SIZE BOLTS = FOR LOAD RA 11 Y r Y.s UTS ANGLE c ol ALTERNATE LOCATION (VERIFY UPPER °$ TRAPEZE LOAD CAPACITY.) ? a REINFORCEMENTS MAY BE USED FOR ATTACHMENT IF IT QUALIFIES FOR BOTH DUTIES. ' -. `= <; ROD SIZE BOLT(S) I; ONE HALF ROUND MAY BE FOR LOAD CREWS USED IF DUCT SHAPE IS SCREWS MAY BE MAINTEINED. OMITTED IF HANGER LOOPS RECTANGULAR DUCT HANGERS TABLE 4 -1 MINIMUM SIZE EFER TO SMACNA STANDARDS FOR LOAD LIMITS. I r LOWER HANGER ATTACHMENTS .P .m STRAP HANGERS f�flANGER SSTRAPS 60" MAX J MAXIMUM MECHANICAL SYMBOLS AND GENERAL MECHANICAL NOTES PAIR AT PAIR AT ABBREVIATIONS LEGEND 1. ALL MECHANICAL SYSTEMS ARE TO BE INSTALLED IN ACCORDANCE WITH ALL ACCU AIR COOLED CONDENSING --.D SATE DRAIN PIPING OF 9ZE NOTED APPLICABLE SECTIONS OF THE NFPA STANDARDS, ANSI STANDARDS, FLORIDA BUILDING CODE A.F.F. UNIT ABOVE FINISHED FLOOR 2010, THE LOCAL BUILDING CODE, NOISE & HEIGHT ORDINANCES, PLANS AND AHU AIR HANDLING UNIT BHP BRAKE HORSEPOWER l.l-DUCT M�TM SMOKE DETECTOR SPECIFICATIONS. C.L.; CENTERLINE 2. ALL MATERIALS SHALL BE NEW, AND ALL WORKMANSHIP AND MATERIALS SHALL BE IN CONTR. CONTRACTOR x SUPPLY AR DIFFUSER STRICT ACCORDANCE WITH APPLICABLE LOCAL CODES, PRODUCT APPROVAL, RULES AND DN. DOWN ROD ORDINANCES. ANY DAMAGED EQUIPMENT SHALL BE REPLACED OR RESTORED TO ORIGINAL EAT ENTERING AIR TEMPERATURE UACONTRACTOR RETURN OR EXHAUST C;liILLE CONDITION. F_ ELECTRICAL t-F VOLUME DAMPER (VD) 3. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, ACCESS PANELS, ESP EXH. EXHAUST ' EXTERNAL STATIC PRESSURE 0 THERMOSTATd4a!• A.F. CONTROL SYSTEMS, DEVICES, PERMITS AND SERVICES NECESSARY FOR FURNISHING AND FC FLEXIBLE CONNECTION O REMOTE TEIMPEtATURE SENSOR INSTALLING A COMPLETE, OPERABLE, MECHANICAL. SYSTEM. FD FIRE DAMPER 1 "x18 GA. 4. ALL LOUVERS, GRILLES, PIPING, ETC. SHALL BE PAINTED 70 MATCH SURROUNDING F.D.F. FIRE DEPARTMENT FlN.FL. CONNECTION FINISHED FLOOR I-ELI COLOR AND TEXTURES AS REQUIRED BY ARCHITECT. VERIFY COLOR AND TEXTURE WITH FLA FULL LOAD AMPERES RA �� �� � DROP (��� ���) ARCHITECT. PAINT ALL EXPOSED MECHANICAL EQUIPMENT WITH BENJAMIN MOORE EPDXY F.P.F. FIRE PROTECTION ENAMEL 182. H.C. CONTRACTOR HVAC IFM INDOOR FAN MOTOR ® DISCHARGE OR APPLY AIR DUCT 5. ALL CUTTING, PATCHING, STRUCTURAL STEEL, WEATHER PROOFING, PAINTING, AND WALL LAT LEAVING AIR TEMPERATURE OPENINGS SHALL BE BY THE GENERAL CONTRACTOR. MBH ONE THOUSAND (1000) BTUH N.I.C. NOT IN CONTRACT RETURN OR EXHAUST AIR DUCT 6. ALL OPENINGS IN BUILDING STRUCTURE FOR DUCTWORK, PIPING, ETC.. TO BE 1/2" N.T.S. NOT TO SCALE ® OUTSIDE AIR SUPPLY DUCT LARGER ON ALL SIDES THAN THE OUTSIDE DIMENSIONS. FILL VOIDS WITH FIRE RETARDANT ( } O• I OUTSIDE AIR OAI OUTSIDE AIR INTAKE 1 "x22 GA. SILICONE FOAM (I.E. CHASE -FOAM CTC PR -855 BY CHASE TECHNOLOGY CORP.). OBD OPPOSED BLADE DAMPER TURNING VANES - NUMBER OF PANES 20x12 SMALL BE BASED ON ACTUAL DUCT SIZE 7. BUILDING HVAC CALCULATIONS ARE BASED ON THE FOLLOWING: P.C. PLUMBING CONTRACTOR R.A. RETURN AIR AND NOT ON SCHEMATIC SYMBOLS ON DWG. DUCT SIZE DESIGNATION: SIZE IS R.A.G. RETURN AIR GRILLE FREE AREA REQUIRED. CONTRACTOR A. OUTDOOR DESIGN TEWI A►TURE )' 91T DB AND 79'F W8 RTU ROOF TOP UNIT SHALL MACE ALLOWANCE FOR DUCT B. OUTDOOR DESM TEMPEPAIM S.A. SUPPLY AIR LINER THICKNESS WHERE SPEdFIED. C. INDOOR DESK;I<i TT.IIIPERATURE (SUMMERt 7ff DB S.P. STATIC RESSURE SENS. SENSIBLE a KEYED NOTES ON ORAINNC D. INDOOR DESIGN TE>WMTURE (LIMIER): 77F DB SF SUPPLY FAN cai DRAWING REVISIONS 8. PROVIDE FLEXIBLE DUCT CONNECTORS, RATED AS REQUIRED, TO ALL FANS, A/C UNITS, TF TRANSFER FAN T.G.C. TENANT'S GENERAL z EXHAUST FAN OR MECHANICAL. EQUIPMENT. TYP. CONTRACTOR TYPICAL 9. PROVIDE MAINTENANCE AND OPERATION MANUAL ON ALL MECHANICAL EQUIPMENT OR we WATER HEATER p DUCTrMDRK SUPPLY AIR (DIRECTION OF THROW) SYSTEMS. PROVIDE 5 SETS OF SUBMITTALS ON ALL HVAC EQUIPMENT. SUBMITTALS SHALL W.M.G. WATER MOTOR GONG ] RETURN / INTAKE AIR HAVE A SUMMARY SHEET SHOWING ALL SCHEDULED INFORMATION. 1/2* 1 "x18 GA. 10. HVAC CONTRACTOR WILL WARRANTY ALL MECHANICAL SYSTEMS, DUCTWORK, (ER) EXISTING RELOCATED A X B0 X. AIR DE VK� TYPE X / CFM THERMOSTATS, AND ALL OTHER EQUIPMENT, PARTS AND LABOR UNDER THESE DRAWINGS (E) EXSTM If AKIN NECK SIME AND SPECIFICATIONS FOR A PERIOD OF ONE (1) YEAR AFTER C.O. OF BUILDING. ANY CFM CUBIC FEET PER WNUTE -� MOTOI= DNwIPM REPAIRS REQUIRING SYSTEM SHUT DOWN WILL BE DONE DURING NON - OPERATIONAL NOTE THIS LEGEND IS FOR REFERENCE ONLY. NOT ALL SYMBOLS AND ABBREVIATIONS WILL BE PERIODS. HVAG CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES PRIOR TO BIDDING AND PURCHASING ANY EQUIPMENT. USED. NOT ALL SYMBOLS AND ABBREVIATIONS USED ARE INCLUDED IN LEGEND. IF QUES11ONS 1/2' ARISE DUE TO THE USE OF ANY SYMBOL OR ABBREVIATION THE CONTRACTOR SHALL CONTACT THE 11. AIR QUALITY SHOULD BE TESTED BEFORE OCCUPANCY AND SHOULD BE INSTRUMENTED PROJECT ENGINEER IMMEDIATELY FOR DEFINITION(S) AND /OR CLARIFICATION(S). COORDINATION NOTES AND MONITORED THEREAFTER, OR AT LEAST AT REGULAR INTERVALS 12. SHOP DRAWINGS: CONTRACTORS SHALL SUBMIT FOR APPROVAL, WITHIN 30 DAYS AFTER SIGNING CONTRACT, A MINIMUM OF FIVE COPIES OF FULLY DESCRIPTIVE LITERATURE, ul INCLUDING BUT NOT LIMITED TO: FANS, AIR OUTLETS, A.C. UNITS. NO WORK SHALL DRAWN BY PROCEED WITHOUT APPROVAL OF THESE SUBMITALS. 1. A/C CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE HIS WORK FOR SIZE, MECHANICAL GENERAL LOCATION, CLEARANCE, ACCESS AND ELECTRICAL CHARACTERISTICS WITH ALL OTHER TRADES AND TO PROVIDE SHOP DRAWINGS TO THE ENGINEER FOR REVIEW BEFORE 2 = 193' UP MECHANICAL EQUIPMENT NOTES: INSTALLATION OF DUCTWORK OR EQUIPMENT. SHOP DRAWING WILL INCLUDE BEAM OR STRUCTURE ELEVATION & REQUIRED EQUIPMENT ACCESS AREAS. 2. ROOF, AND CEILING OPENINGS INDICATED ON CONTRACTOR DRAWINGS ARE 1. ALL MECHANICAL EQUIPMENT SHALL BE ARI & U.L. LISTED, WHERE APPLICABLE, AND NOMINAL DIMENSIONS ONLY AND ALL DUCT, PIPE OR EQUIPMENT PENETRATIONS SHALL RATED FOR THE REQUIRED SERVICE, PRESSURES, TEMPERATURES, AND SHALL BE PROVIDED BE SLEEVED AND FIRE RATED AS REQUIRED, ADJUST OPENINGS WITH ALL NECESSARY TRANSFORMERS, SEALS, VALVES, CONNECTIONS, ETC. TO FUNCTION PROPERLY, 3. COORDINATE LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS IN THE FIELD WITH LIGHTS, SPRINKLERS AND ARCHITECTURAL ELEMENTS. 2. PROVIDE SMOKE DETECTORS WITH ACCESS DOORS IN ALL SUPPLY AIR DUCTS FOR FANS AND RTU'S OF 2000 CFM OR ABOVE. ALL SMOKE DETECTORS SHALL BE BY ONE 4. COORDINATE LOCATION OF A/C UNITS, THERMOSTATS, FANS AND DUCTWORK WITH MANUFACTURER; COORDINATE VOLTAGE ETC. WITH ELECTRICAL CONTRACTOR AND FIRE ALARM BUILDING STRUCTURE AND OTHER TRADES SO THAT NO INTERFERENCES OCCUR. SYSTEM BEFORE ORDERING. UPON DETECTION, SMOKE DETECTORS SHALL SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT. 5. IN GENERAL, DUCT OFFSETS HAVE NOT BEEN SHOWN. A/C CONTRACTOR TO COORDINATE THESE AS REQUIRED. 3. PROVIDE TYPE "B" FIRE DAMPERS IN ALL DUCTS OR OPENINGS PENETRATING FIRE 6. MECHANICAL PLANS, IN GENERAL, ARE DIAGRAMMATIC IN NATURE AND ARE TO BE RATED WALLS, PARTITIONS, FLOORS OR ROOF SLABS AND AT FRESH AIR INTAKES IF READ IN CONJUNCTION WITH ARCH., PLUMBING, ELECTRICAL AND STRUCTURAL PLANS REQUIRED (SEE ARCHITECTS PLANS FOR RATINGS). PROVIDE RADIATION DAMPERS IN RATED AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS. DUCT AND PIPING CEILINGS FOR ALL CEILING OPENINGS, CEILING FANS, DIFFUSERS OR GRILLES RATED FOR OFFSETS, BENDS AND TRANSITIONS WILL BE REQUIRED TO PROVIDE AND INSTALL A USE IN THE CEILING ASSEMBLY AS SPECIFIED BY ARCHITECT. COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR AT NO 4. PROVIDE BACKDRAFT DAMPERS ON ALL EXHAUST FANS AND /OR INLINE FANS. ADDITIONAL COST TO THE OWNER. 7. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO BIDDING, 5. PROVIDE VIBRATION ISOLATORS ON ALL MECHANICAL EQUIPMENT AS CALLED FOR IN ORDERING, FABRICATION OR INSTALLATION OF MATERIALS OR EQUIPMENT. THE SPECIFICATIONS. IF NOT SPECIFIED, PROVIDE AS RECOMMENDED BY MANUFACTURER FOR QUIET OPERATION (WITH 99% ISOLATION EFFICIENCY). 6. PROVIDE A MIN. OF 10' CLEARANCE BETWEEN O/A INTAKES AND VTR OR EXHAUST NOTICE To CONTRACTORS: OPENINGS. ALL CONTRACTORS, PRIOR TO BID SUBMISSION PROCESS, SHALL VISIT PROPOSED 7. INDEPENDENT CONTRACTOR SHALL TEST AND BALANCE ALL MECHANICAL EQUIPMENT, AIR DEVICES, EXTRACTORS, DAMPERS, RTU'S & FAN RATES, ETC. TO PROVIDE THE DESIGN WORK SITE AND FIELD VERIFY ALL EXISTING CONDITIONS. ANY CONDITIONS THAT QUANTITIES AS SHOWN ON THE PLANS OR SCHEDULES. PROVIDE T & B REPORT IN DIFFER FROM THAT SHOWN ON THIS PLAN SHALL BE REPORTED TO ARCHITECT/ ACCORDANCE WITH THE AIR BALANCE COUNCIL STANDARDS. PROVIDE FINAL BALANCING FOR ENGINEER SO THAT NEW AND REVISED BID DRAWINGS OR INFORMATION MAY BE ALL SYSTEMS TO SATISFACTION OF OWNER AND ENGINEER. T &B CONTRACTOR SHALL VISIT ISSUED. MODIFICATIONS TO SCOPE OF WORK, WHICH RESULT FROM CONTRACTORS JOB SITE DURING CONSTRUCTION TO ENSURE THAT ALL DUCTS, DAMPERS, ETC. ARE NEGLECT TO VISIT THE SITE PRIOR TO SUBMITTING BID, SHALL BE CONTRACTOR'S INSTALLED FOR PROPER AND QUIET AIR DELIVERY. SOLE RESPONSIBILITY. B. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALLATION. SHOP DRAWING REQUIREMENTS 9. RUN INSULATED CONDENSATE DRAINS AS PER PLUMBING DRAWINGS. 1. SHOP DRAWINGS, SHALL BE SUBMITTED COMPLETE, TOGETHER AT ONE TIME AND MU 10. MOUNT ALL ROOFTOP EQUIPMENT FOR WIND LOADS AND MOUNTING HEIGHTS AS REQUIRED BY LOCAL CODES, ALL CURBS SHALL EXTEND 14" MIN. ABOVE FINISHED ROOF. COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS REFER TO STRUCTURAL DRAWINGS AND CALCULATIONS FOR WIND LOAD INFORMATION. OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSE 11. ALL PIPING AND DUCTWORK SHALL BE SLEEVED THRU WALLS, BEAMS, SLABS, ETC., AS FOR USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED. REQUIRED, AND COORDINATED WITH THE STRUCTURAL ENGINEER. REWORK BAR JOIST CROSS 3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE BRACING AND PROVIDE NECESSARY TRANSITIONS AS REQUIRED FOR DUCTWORK INSTALLATION. CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS 12. ALL INSULATION WILL HAVE FIRE /SMOKE RATING LESS THAN 25/50. PRIOR TO BID DATE. 13. PROVIDE MOTOR STARTERS AS FOLLOWS (UNLESS OTHERWISE RECOMMENDED BY MOTOR 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS MANUFACTURER): FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR A: PROVIDE OVERLOAD PROTECTION - 1/3 HP AND ABOVE (ALL PHASES). WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. B: PROVIDE ACROSS THE LINE VOLTAGE STARTING BELOW 25 HP. 5. SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A 14. ALL OUTDOOR EQUIPMENT SHALL COMPLY WITH LOCAL ZONING NOISE ORDINANCES. PURCHASE ORDER FROM THE CONTRACTOR OR IT SHALL BE REJECTED. MIN. REQUIREMENT SHALL NOT EXCEED A NOISE LEVEL OF 65 DB AS MEASURED RADIALLY 30 FT FROM THE EQUIPMENT IN ALL DIRECTIONS. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST 15. FILTERS SHALL BE IN PLACE DURING CONSTRUCTION. PROVIDE A NEW SET PRIOR TO BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER FROM THE TEST AND BALANCE AND A FINAL SET AT THE END OF ONE YEAR SERVICE PERIOD. CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED 16. CONTROLS: To HIM ON A C.O.D. BASIS. AIR CONDITIONING SYSTEMS SHALL BE STARTED AND STOPPED THRU INDIVIDUAL 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT THERMOSTATS. INDIVIDUAL THERMOSTATS SHALL START /STOP SUPPLY FANS AND ACTIVATE DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT COOLING /HEATING SYSTEMS AS SELECTED. ACTIVATION OF ANY UNIT SMOKE DETECTOR RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND /OR PERMIT CONTRACT SHALL SHUT DOWN ALL RTU'S AND ACTIVATE AUDIBLE AND VISUAL ALARMS. DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT B MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE 17. ELECTRICAL CONTROLS AND POWER WIRING: UNDER ELECTRICAL CONTRACT. CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. 8' CONTRACTOR SHALL SUBMIT 5 COPIES OF SHOP DRAWINGS. AIR DISTRIBUTION DUCTWORK NOTES" 1. REFER TO ARCHITECTURAL PLANS FOR CEILING TYPE. 2. PROVIDE OFF -WHITE FINISH (SUBJECT TO ARCHITECT'S APPROVAL). 3. ALL DUCTWORK WHERE ALLOWED BY LOCAL CODES AND AND CEILING RATING SHALL BE 1- LOW PRESSURE DUCT, SEAL. CLASS "C" AND AS FOLLOWS: A. ALL SUPPLY /RETURN AIR DUCTWORK SHALL BE FIBERGLASS DUCTBOARD, FABRICATED AND INSTALLED AS PER LATEST EDITION OF SMACNA "FIBROUS GLASS DUCT MANUAL ". 1 -1/2" THICK R -6.0 IN UNCOND. SPACE. 1" THICK R -4.2 IN COND. SPACE. B. EXHAUST AIR - GALVANIZED SHEETMETAL, 24 Go. MIN. C. FLEXIBLE DUCTWORK SHALL BE INSULATED WITH 142 THICK R -6.0 MIN. FIBERGLASS INSULATION. 3.1. ALL EXPOSED SUPPLY, INTAKE AND EXHAUST AIR DUCTWORK SHALL BE OF GALV. SHEET METAL CONSTRUCTION, FABRICATED & INSTALLED AS PER LATEST EDITION OF SMACNA "LOW PRESSURE DUCT MANUAL" INSULATE SUPPLY AIR DUCTWORK IN CONCEALED SPACES WITH 1 -1/2" THICK FIBERGLASS BLANKET INSULATION WITH FOIL VAPOR BARRIER (R -6.0 MIN.) 4. ALL DUCTWORK AND DIFFUSERS SHALL BE RATED FOR THE USE, PRESSURE AND TEMPERATURE SPECIFIED AND AS REQUIRED BY THE CEILING SYSTEM RATING. 5. SEAL. ALL DUCTS, JOINTS AND SEAMS IN AN APPROVED MANNER AND INSURE AGAINST LEAKAGE. ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS. 6. PROVIDE ACCESS DOORS AS REQUIRED FOR ALL MECHANICAL EQUIPMENT TO SERVICE AND VISUALLY CHECK ROTATION OF FANS AND MOTORS, POSITION OF DAMPERS, REPLACE FIRE DAMPER LINKS, ADJUST OR REPLACE CONTROLS, ETC. 7. PROVIDE VANED ELBOWS IN ALL CASES, SPUTTER DAMPERS WHERE INDICATED ON DRAWINGS AND VOLUME CONTROL DAMPERS IN ALL BRANCH DUCTS OR DIFFUSER CONNECTIONS. TURNING VAIN FOR SMACNA STANDARDS. M1 TYP. 90-DEGREE VANED NOT TO SCALE ELBOW DETAIL 4" TOILET EXHAUST ,,n DUCT (SHEETMETAL) VIBRATION HANGER SPRING TYPE W /NEOPRENE L ISOLATOR 3/8" THREADED RODS 0 V WHITE CEILING GRILLE NOTES 1.- PROVIDE BACKDRAFT DAMPER W/ BIRDSCREEN 2.- FLASH & SEAL WALL AND ROOF CAP 3.- PROVIDE INTERNAL ISOLATION AND SOUND INSULATION 4.- SUPPORT FAN FROM STRUCTURE M2 TYP. CABINET EXHAUST FAN DETAIL NOT TO SCALE CAULK TO PROVIDE`%/ WATERTIGHT SEAL . WALL CAP WITH BUILT -IN SPRING LOADED DAMPER AND RUBBERIZED GASKET DUCT CLAMP WALL WALL e ♦ i . ♦ e M3 WALL CAP DETAIL NOT TO SCALE I VENT LINE WITH PERFORATED CAP. 3" ABOVE TOP OF PRIMARY DRAIN PAN TEE C.O. PLUG (SCREWED) j UNION II CONNEC' FJ" TSP +1" A. SLOPE DRAIN LINE TO TSP +1" CONDENSATE RECEPTOR (MIN. (3' MIN.) 1/8" PER FOOT) B. DRAIN LINE SHALL BE COPPER TYPE "L" AND INSULATED. C. TSP = FAN TOTAL STATIC PRESSURE. DETAIL CONDENSATE P-TRAP NOT • SCALE B_ C MECHANICAL DRAWING INDEX DRAWING DESCRIPTION 1 M0.1 MECHANICAL GENERAL NOTES, SYMBOLS AND DETAILS - {- ------------ _ ............ ....... _.... ......... .------ .........._...... ..._._.. _..........- ._._.._........ -.. - ._......... - 2 Ml-1 MECHANICAL CEILING PLAN, SCHEDULES AND NOTES STRAP HANGERS -17- HANGER STRAPS 60" UNLESS FOOT OF STRAP IS PLACED UNDER A BOTTOM REINFORCEMENT. I' INIMUM -SCREWS MAY BE OMITTED IF HANGER LOOPS LOAD RATED �ASTENERS 24" DLAL MAX. Ll 50" DUI. MAX. BAND OF SAME SIZE AS HANGER STRAP. HANGERS MUST NOT DEFORM DUCT SHAPE GER RODS, WIRES OR STRAPS BJWk . , " - - `9i } -s x P n s SIZE BOLTS = FOR LOAD RA 11 Y r Y.s UTS ANGLE c ol ALTERNATE LOCATION (VERIFY UPPER °$ TRAPEZE LOAD CAPACITY.) ? a REINFORCEMENTS MAY BE USED FOR ATTACHMENT IF IT QUALIFIES FOR BOTH DUTIES. ' -. `= <; ROD SIZE BOLT(S) I; ONE HALF ROUND MAY BE FOR LOAD CREWS USED IF DUCT SHAPE IS SCREWS MAY BE MAINTEINED. OMITTED IF HANGER LOOPS RECTANGULAR DUCT HANGERS TABLE 4 -1 MINIMUM SIZE EFER TO SMACNA STANDARDS FOR LOAD LIMITS. I r LOWER HANGER ATTACHMENTS .P .m STRAP HANGERS f�flANGER SSTRAPS 60" MAX J MAXIMUM PAIR AT PAIR AT PAIR AT PAIR AT HALF OF 10 FT SPACING 8 FT SPACING 5 FT SPACING 4 FT SPACING DUCT WIRE/ (WIRE/ WIRE/ WIRE/ PERIMETER STRAP ROD STRAP ROD STRAP ROD STRAP ROD = 30" 1 "x22 GA. 10 GA. ) 1 "X22 GA. 10 GA. (.135) 1 "x22 GA. 12 GA. (.106) 1 "x22 GA. 12 GA. (.106-) = 72" 1 "x18 GA. 3/8" 1"x20 GA. 1/4' 1'x22 GA. 1 /4" 1"x22 GA. 1 /4" 2 E = 96" 1 "x16 GA. 3/8" 1 "x18 GA. 3/8' 1 "x20 GA. 3/8' 1 "x22 GA. 1 /4" 2 2 = 120" 1.5 "x16 GA. 1/2' 1 "x16 GA. 3/8" 1'x18 GA. 3/8' 1 "x20 GA. 1/4* ^ • r-1 E = 168" 1.5 "x16 GA. 1/2* 1.5 "x16 GA 1/2' 1 "x16 GA. 1/2* 1 "x18 GA. 3/8' 2 V T_q 00 1 nx � � ........... � �� . . � � �� Ww oo, Jill 2 = 192" - 1/2" 1.5 "x16 GA 1/2' 1 "x16 GA. 1/2- 1 "x16 GA. 3/8" J :::`z >:rr� U) ul PROJECT NO. DRAWN BY 15 -oo8 BIB MECHANICAL GENERAL NOTES, SYMBOLS AND 2 = 193' UP SPECIAL ANALYSIS REQUIRED AS PER SMACNA TABLE 4 -1 & FIG. 4 -4 TYP. DUCTWORK MOUNTING DETAILS NOT TO SCALE BOLT TO STEEL ANGLES WITH BOLTS, ONE AT EACH CORNER.- OUTDOOR AIR INTAKE - 24' -�! TURNED DOWN VD T gwkl STEEL ANGLES WELDED TO STEEL PLATE SECURED TO WALL WITH THRU BOLTS DET REFER TO STRUCTURAL DRAWINGS FOR DETAILS UNLESS FOOT rz OF STRAP IS PLACED UNDER A BOTTOM REINFORCEMENT Y X ROD REFER TO ARCHITECTURAL /STRUCTURAL FOR ROOF EQUIPMENT WIND LOAD CALCULATION, FINAL REQUIRED BOLTS ATTACHMENTS INFORMATION AND DETAILS. TYPICAL PACKAGED UNIT MOUNTING DETAIL NOT TO SCALE L 1+% Y I � eK Y I' 4K s 2 E­4 _2 :r r a �K. N La O W co Iti z O g5 w B2ST U Dio 0 AA 26002514 - IB 26001404 1141 SE 6th TERRACE SUITE 1 FT. LAUDERDALE, FL 33316 Phone (754) 30c ; 770 bbuUock @sustainable- logic.net ^ • r-1 E •� �a E 4-J 11 E V T_q 00 �C nx � � ........... � �� . . � � �� Ww oo, Jill M ! uj 0 w W F-: v z F ! r w Z144 W zz o § f: Z it om a. J :::`z >:rr� U) ul PROJECT NO. DRAWN BY 15 -oo8 BIB MECHANICAL GENERAL NOTES, SYMBOLS AND DETAILS m 0 . 1