15-310-006D,-'-�ELECTRICAL FLOOR (incl. case lights) PLAN
SCALE: 1/4 " =1' -0"
o A a
LRT LIGHT (J) &
(G /H) OCABINET TOP
!ITCHED SEPARATELY.
8"AFF ABOVE CABINET
IS FOR
POWER AT
- LOCATION
)INATED WITH
SCOPE OF WORK
INTERIOR TENANT IMPROVEMENT. EXISTING OLD PANELS DEMOLITION AND
REPLACEMENT WITH NEW. NEW ELECTRICAL POWER LIGHTING LAYOUT.
DRAWING KEY NOTES
L! 1 ALL EXIT SIGNS AND EMERGENCY LIGHTS SHALL. BE CONNECTED TO LOCAL LIGHT
—D CIRCUIT AHEAD OF ANY LIGHT SWITCH.
COORDINATE EXACT LOCATION FOR ALL SWITCHES WITH OWNER /ARCHITECT
(TYPICAL).
('-i1 NEW PANEL AT THE NEW LOCATION. INTERCEPT AND EXTEND EXISTING CIRCUITS
WITH NEW WIRES AND CONDUIT TO NEW LOCATION. CONTRACTOR SHALL ASSURE
PROPER WORKING CLEARANCE FOR ELECTRICAL PANEL INSTALLATION AS REQUIRED
BY NEC110.26. COORDINATE WITH MECHANICAL DRAWING PRIOR TO INSTALLATION.
ABOVE SHOW WINDOW TOP OF THE WINDOW. COORDINATE ATE EXACT MOUNTING WITH ARCHITEICTURALOF THE
DRAWINGS.
COMBINATION USB CHARGING RECEPTACLE WITH SINGLE /DUPLEX RECEPTACLE.
DUAL USB CHARGING PORTS RATING 2.1A /700MA AT 5V AND THE RECEPTACLE
RATING 20A/15A AT 125V. DEVICE MUST BE UL LISTED. (COOPER TR7746/tR7740
OR EQUAL)
(- 2'x2'x5 /8" FIRE TREATED PLYWOOD TELEPHONE BACKBOARD. PAINT BOTH SIDES
�-=-� WITH GREY FIRE RETARDANT PAINT AS REQUIRED. PROVIDE QUAD RECEPTACLES AS
SHOWN (VERIFY EXACT LOCATION (BELOW CEILING), SIZE, AND REQUIREMENTS WITH
THE CLIENT /OWNER)
J —BOX FOR SIGAGE. FIELD VERIFY EXACT LOCATION / CONNECT SIGAGE AND
DISCONNECT AS REQUIRED PER MANUFACTURER.
EXHAUST FAN TO BE INTERLOCKED WITH THE LIGHT SWITCH.
CONTRACTOR FIELD VERIFY EXISTING GFI RECEPTACLE WITHIN 25FT. FOR
MECHANICAL EQUIPMENT. CONNECT TO ELECTRICAL CIRCUIT AS SHOWN, OUTDOOR
RECEPTACLES HAVE TO BE WEATHER — RESISTANT AS PER NEC406.8.
0- FIELD COORDINATE EXACT POS /PRINTER LOCATIONS PRIOR TO ROUGH IN.
COORDINATE ISOLATED GROUND (IG) REQUIREMENTS AT ALL POS /PRINTER
LOCATIONS WITH SYSTEM PROVIDER. HIGH SPEED DATA LINE & MODEM LINE
REQUIRED
NEW INSTANT WATER HEATER /REFER TO PLUMBING PLAN & SPECIFICATIONS FOR
FINAL REQUIREMENTS.
12 NIGHT LIGHT Q CONNECT TO NEAREST LIGHTING CIRCUIT AHEAD OF SWITCHING.
GENERAL NOTE:
— REFER TO ARCHITECTURAL ELEVATIONS FOR ALL OUTLETS LOCATIONS /MOUNTING
HEIGHTS AND COLOR FINISHES.
EX — DENOTES EXISTING.
ER — DENOTES EXISTING/ RELOCATED
LIGHTING FIXTURE SCHEDULE
A
HEADS VOLTAGE TRACK At
SOLAIS LIGHTING XI24/25 /309/1600/WH /J/HL
2 WATT LID MODULE
MAX LP
/ .tt
MAX. LP
I Im
LP PROVIDED
rm
PER
® B
RECESSED WIDE -BEAM
AMERLUX HORNET NDL- HP- S- 20- LO-E -120 /
224
192
DOWNUGHT
H0L- HP- SD- MWW -WF -3000
(1) 20 WATT' LEI) MODULE
®C
RmEm
Hm� HDL- HP -S-20 -LED -E -120 /
' 14
RESTROOM
WALL WASHER
HOL- 1PX- SUN -MWW. -3000
(1) 20 WATT' LEI! MODULE
22
RECESSED BINDLE -HEAD
AMERLUX HORNET HP- R/aR- FRAME -1- LED- /20/HP
- ' � - -
1359
D
ADJUSTABLE SPOT
H- -
+�
(1) 18 WATT LED MODULE
® E
RECESSED DOUBLE -HEAD
AMERLUX HORNET HP- R/SR- FRAME-2- 4M>- 120/MP
[-
O
ADJUSTABLE SPOT
�- +HEK
(2) 18 WATT' LED MODULE
SURFACE
COLUMBIA LIGHTING WC4 -232- -E-U
MOUNT
(2) 32 WATT T8
G
STAGGERED STRIP
1 -3- M
UP -LIGHT AT CABINET TOP
COLUMBIA LIGHTING SS- 3-1 -26
'3' 25 WATT T8
4--
STAGGERED STRIP
UP -UGHT AT CABINET TOP
COLUMBIA LIGHTING SS- 4-1 -32
• •
4 32 WATT T8
DANALRE (ALL TYPE -3- UNLESS OTHERWISE
*-
CABINET ART LIGHT
NOTED) "2*. DL2S -S30; '3'; D;3S -S3O
12 18 WATT LED
DECORATIVE WALL LIGHT
PHILIPS FORECAST TORCH SCONCE - F5427
25 WATT HALOGEN
CANDELBRA
EM OH
DECORATIVE WALL LIGHT W
EM. BACKUP BATTERY
LIGFTfOLIEFt 'CIRT2.�JNE" 8700S2LJEM -TPR
22 WATT PHILLIPS FC9T5
WITH 90 MIN BATTERY.
OEM
RECESSED EMERGENCY LIGHT
NAVILTTE NRG SERIES
8V BW WATT BI-PIN
HALOGEN LAMP.
WITH 90 MIN BATTERY.
EM
CONCEALED EMERGENCY
ISOUTE GENIE SERIES
TWO 25W MR 11 LAMPS
THREE 3W LEM
LIGHT
90 MIN BATTERY.
O
DENOTES FIXTURE ON
NIGTTIME LIGHTING CIRCUIT
WITH TIMER
COMBINATION /
NAVIt1tE NIIPI.
120Y WITH 90 MIN.
'
EMERGENCY LINT
5..4W BATTERY
W/
F"I"Wim EMERGENCY
ILIGHTS
a 4w 12QV R MIN.
NOTES:
1. LIGHTING FIXTURE SCHEDULE IS SHOWN FOR REFERENCES ON ELECTRIC CHARACTERISTICS ONLY. UNLESS
OTHERWISE INDICATED BY ENGINEER, ARCHITECT, OR OWNER.
2. CONTRACTOR TO ENSURE THAT MOUNTING DEVICES AND ACCESSORIES ARE CORRECT FOR CEILING AND WALL IN
WHICH THE FIXTURES ARE M BE INSTALLED.
3. REFER TO ARCHITECTURAL CEILING PLANS FOR EXACT LOCATION OF LIGHT FIXTURES
4. ALL LIGHT FIXTURES SHALL BE REVIEWED AND APPROVED BY ARCHITECT / OWNER PRIOR TO FORWARDING TO
ENGINEER FOR REVIEW.
5. ALL LIGHT FIXTURES AND LAMPS WILL BE FURNISHED AND INSTALLED BY TENANT'S CONTRACTOR, UNLESS
OTHERWISE NOTED. THIS CONTRACTOR SHALL. BE RESPONSIBLE FOR ORDERING. RECEIVING, STORING, AND
PROTECTING FROM THEFT
6. SUBSTITUTIONS ARE ALLOWED FOR SIMILAR PRODUCTS ONLY TO SHORTEN LEAD TIMES.
7. FACTORY SUBMITTALL//UTS EET TO BE APPROVED BY ARCHITECT BEFORE ORDERING
8. ALL NEW FLUOR ESC LIGHT FIXTURES THAT UTILIZE DOUBLE —ENDED LAMPS AND CONTAIN BALLASTS THAT CAN
BE SERVICED IN PLACE SHALL BE EQUIPPED WITH DISCONNECTING MEANS AS PER NEC -2008 (410.130(G)j.
9. ALL LUMINARIES SHALL BEAR THE UL LISTING NUMBER FROM NATIONAL RECOGNIZED TESTING LABORATORRYY.
LIGHTING POWER DENSITIES IN COMPLIANCE WITH 2010 FBC-ENERGY
CONSERVATION
(TABLE 505.5.0
SPACE
DESIGNATION
AREA
.R
MAX LP
/ .tt
MAX. LP
I Im
LP PROVIDED
rm
LPD PROVIDED
IWAQ.&I
BACK OF HOUSE
149
f.8
224
192
1.3
SALES
848
1.7
1102
88e
' 14
RESTROOM
38
04 `.-
34
22
0.6
TOTAL
1359
1102
LPD - LIGHT POWER DENSITY
LP - LIGHT POWE R
B Q C
SCONI
DRINK
COORI
HE3GH
LOCATION OF GANGED
(SEPARATE SWITCH FL;
FIXTURE TYPE)
('•) 12 VERTICAL TRA
MOUNTED TO
LIGHTING CEILING PLAN
1 \ 03.12.15
ENTIRE SHEET REVISED: OWNER
REQUESTED REVISIONS 03.11.15
D
0
PROJECT NO, DRAWN
15 -008 BIB
0
ELECTRICAL
PLAN,
�FLOOR
NOTES AND LIGHTING
FIXTURE SCHEDULE
1 �
1 1
N
Q�
El A
O