15-310-005ELECTRICAL SYMBOL LEGEND (c) (d) FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS ONLY. GENERAL ELECTRICAL NOTES ELECTRICAL COORDINATION NOTES EO.1ELECTRICAL GENERAL NOTES, SYMBOLS AND DETAILS, RISER, SCHEDULES _ E1.1 ELECTRICAL FLOOR PLAN, N ❑TES AND LIGHTING FIXTURE SCHEDULE Project #: 160201 PHASE WIRE VOLTAGE SINGLE PHASE a•a 1. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING $Q DIMMER SWITCH (M.H. = 48" A.F.F.) 17. ALL CONDUIT RUNS ARE SHOWN DIAGRAMATICALLY. THE EXACT ROUTING SHALL BE DETERMINED IN ° E S THE FIELD. UNLESS NOTED OTHERWISE. BASIC MATERIALS OCCUPANCY SENSOR NOTES: 18. WHERE CORE DRILLING OF FLOORS /WALLS IS REQUIRED, THE CONTRACTOR SHALL SEAL OPENINGS CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. SYMB ❑L DESCR- IPTI ❑N 1. THE ENTIRE INSTALLATION SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL GODS THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN SWITCHES. INDICATES SWITCHING CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND SEAL THE OPENING AROUND THE 2008 NEC, FLORIDA BUILDING CODE 2010 FBC, 2010 FLORIDA FIRE PREVENTION CODE, NFPA 1 MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR CONDUIT. POLES DUPLEX RECEPTACLE, 20 AMP., 125V., (M.H.= 1$ "A,F.F.) 19. PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PENETRATIONS, WALLS AND NFPA 101 2006 EDITIONS AND THE LATEST EDITIONS OF ALL LOCAL CODES, RULES AND DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN STRUCTURAL SLABS. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO m RECEPTACLE (16" A.F.F.) (EWC DENOTES ELECTRIC WATER COOLER. VERIFY PRIOR TO SUBMITTING BID, THE LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS, WALLS, ORDINANCES HAVING JURISDICTION. EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. wG COORDINATE WITH EWC INSTALLER FOR MOUNTING HEIGHT) 2. AS A MINIMUM, ALL EQUIPMENT SHALL MEET APPLICABLE STANDARDS, FOR TYPE OF 2. THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DRAWINGS, REFER TO ` TWO DUPLEX RECEPTACLES WITH COMMON COVER 20A., 125V..(18" A.F.F.) 1 EQUIPMENT AND INTENDED USE, OF THE FOLLOWING: AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI). ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT 2. THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL SPECIAL PURPOSE OUTLET, CORRD. W/ EQUIPT. SERVED, INCLUDING REQUIRED FUSES U.O.N. SWITCHES SHALL. BE HORSEPOWER RATED FOR MAX. G. b. ILLUMINATING ENGINEERS SOCIETY (IES). AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM). UNLESS NOTED OTHERWISE. 3. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL. CONTRACTOR TO PROVIDE ALL HORSEPOWER, HEAVY DUTY TYPE. 314" DUPLEX RECEPTACLE, 20 AMP., 125V., MOUNT ABOVE COUNTER 042 -AFF. 22. THE CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATINGS FOR EQUIPMENT PRIOR TO c. d. NATIONAL ELECTRICAL. MANUFACTURERS ASSOCIATION (NEMA). LABOR, MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS INSTALLATION. 3 SYMBOL DESCRIPTION ELECTRICAL BRANCH CIRCUIT PANELBOARD, RECESS MOUNTED. 23. ALL FUSES SHALL. BE CURRENT LIMITING, PER U.L., RATED 60OV. OR 250V. AS REQUIRED, WITH: NOTE: THESE STANDARDS ARE SUBORDINATE TO CODES AND STANDARDS SET BY U.L. SHOWN AND /OR NOTED ON THE PLANS. (c) NON TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FEEDING PANELS. GFCI DUPLEX RECEPTACLE, 20 AMP.. 125V., (M.H. =18 "A.F.F.) 3 IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE BY A LICENSED 4. IT SHALL. BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCE ORDERING OF LONG LEAD ITEMS, AS TO NOT INTEFERE WITH THE - -- - - (SEE PANEL SCHEDULE FOR DETAILS) GFCI DUPLEX RECEPTACLE, 20 AMP., 125V., MTD. ABOVE COUNTER VERIFY ( M ELECTRICAL CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. SAID CONTRACTOR PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE ® HEIGHT DUP RECEPTACLE, 20 AMP., 125V., MOUNTED IN BOTTOM OF POLE CIRCUIT BREAKERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMITTED. SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES. CONTRACTOR SHALL NOT ORDER ANY ITEMS UNTIL APPROVED SHOP DRAWINGS ARE 26. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R) WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT. CEILING SOFFIT FOR SHOW WINDOW LIGHTING 4, THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST RETURNED TO HIM. ® FLOOR OUTLET BOX AND DUPLEX RECEPT. 20 AMP., 125V., WITH 20 PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 5. THE CONTRACTOR SHALL KEEP ALL AREAS WHERE WORK IS BEING PERFORMED FREE a APPROPRIATE FLANGE. JUNCTION BOX, MOUNTING AS SHOWN 5. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE UNLESS NOTED OTHERWISE THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYSTEM AS 3 7 DEFECTS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM DATE OF ACCEPTANCE, U.O.N. END OF EACH WORK -DAY. 12 ELECTRIC MOTOR, NUMBER INDICATES HORSEPOWER 6• IT SHALL NOT BE THE INTENT OF THESE PLANS AND /OR SPECIFICATIONS TO SHAW EVERY 6. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO COORDINATE ALL WORK OF POLES ENCLOSURE TYPE: MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL BE EXPECTED TO FURNISH AND OUTSIDE LEASE SPACE WITH LANDLORD. ANY WORK OUTSIDE OF LEASE MUST BE BY 7 AM. AREAS MUST BE CLEAN AND 20 / -'-- -- AMP RATING /FRAME NEMA 3R- FOR 12 INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL. SYSTEM AND PROVIDE ALL REQUIREMENTS PERFORMED AFTER 7 PM AND COMPLETE R GENERAL RECEPTACLE EXTERIOR NEMA 1- NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. READY FOR BUILDING OCCUPANCY BY 6:00 AM EVERY MORNING. BATHRMIB.O.H. LTS Q131= FOR INTERIOR 'N--- 7, THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO ORIGINAL CONDITIONS, ANY 7. COORDINATION DETAILS OF ALL TRADES SHALL BE RESPONSIBILITY OF THE GENERAL 1 --FUSE SIZE( * DENOTES AS PER MANUFACTURER) A AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT, ETC. CAUSED DURING THE CONTRACTOR. 20 LIGHTING CONTROL TIME CLOCK 12 PERFORMANCE OF WORK. FBC CODE COMPLIANCE STATEMENTS: R PHOTOCELL, MOUNTED ON ROOF FACING NORTH 8. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE OR 2 ® SHUNT -TRIP BUTTON - FLUSH MOUNTED UNLESS OTHERWISE NOTED O DELAYS AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 1' AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE ® PLUG -IN STRIP WITH RECEPTACLES, 18" O.C. U.O.N. 2 2.4 BUILDING OWNER, INCLUDING SUBMITTAL DATA STATING EQUIPMENT RATING AND C 0.50 9. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE, ® CABLE TRAY R AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF OPERATION AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING di�- -- GROUND OR GROUND ROD AS NOTED 2.4 A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR MAINTENANCE WITH CLEARLY IDENTIFIED REQUIRED ROUTINE MAINTENANCE ACTIONS, --o CONDUIT TURNING UP CONDUIT STUB 1 LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. AND NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY. FBC -�•� T TURNING GOWN "--� CONDUIT CONTINUED CONDUIT DRINKING FOUNTAIN GFI 14 EC 505.7.4.2, 15 10. THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL 2. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF 12 NG (REFER TO LIGHTING FIXTURE SCHEDULE FOR SPECS.) 20 PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING SYMBOL DESCRIPTION 11. OTHERWISE. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE ALL LABOR, A SINGLE -LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. FBC A LIGHT FIXTURE DESIGNATION. MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND /OR SPARE 0 LIGHTING FIXTURE, SURFACE MOUNTED NOTED ON THE PLANS. EC 505.7.4.1. O LIGHTING FIXTURE (HID, FLUORESCENT OR INCANDESCENT), RECESSED 12, IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCE ORDERING MTD. OF LONG LEAD ITEMS, AS TO NOT INTEFERE WITH THE PRODUCTION OF OTHER TRADES 30 2 LIGHTING FIXTURE, WALL MOUNTED 1D RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT ORDER ANY ITEMS UNTIL TO PKU-1 (HEATER 5kw) 1.2 APPROVED SHOP DRAWINGS ARE RETURNED HIM. 3 0 EXIT LIGHT FIXTURE. DIRECTION ARROWS AS SHOWN 13. THE CONTRACTOR SHALL KEEP ALL AREAS WHERE WORK IS BEING PERFORMED FREE FROM DEBRI 12 1/2 °° WALL MOUNTED EXIT LIGHT FIXTURE (SHADED QUADRANT INDICATES 1 AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE END OF EA. WORKING DAY. C 2.50 FACE(S) OF FIXTURE) 14. ALL CONDUCTORS SHALL BE COPPER, TYPE THHN/THWN EXCEPT WHERE OTHERWISE REQUIRED BY 2 S R ® 2 X 2 FLUORESCENT LIGHT FIXTURE U.L. OR CODES. MINIMUM WIRE SIZE SHAD. BE #12 AWG, EXCLUDING CONTROL WIRING. 2 ® 2 X 4 FLUORESCENT LIGHT FIXTURE 15. ALUMINUM CONDUCTORS ARE NOT PERMITTED ANYWHERE. DIAGONAL SHADING DENOTES LIGHT FIXTURE CONNECTED TO 16. ALL CONDUCTORS SHALL BE IN 1/2- MIN. CONDUITS. ALL CONDUITS SHALL BE GALVANIZED RIGID SPACE MbbJ EMERGENCY BRANCH CIRCUIT OR, W /EMERG. BATTERY PACK. 23 STEEL (GRS) EXCEPT THAT: ► COMBINATION OF EXIT SIGN & EMERGENCY BATTERY WALL PACK WITH (a) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED ELBOWS AND RISERS ARE GRS, TWIN HEADS (REFER TO LTG. FIXTURE SCHEDULE FOR SPECS.) C WHERE SUBJECT TO PHYSICAL DAMAGE Q EMERGENCY BATTERY WALL PACK WITH TWIN HEADS (b) ELECTRICAL METALLIC TUBING (EMT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SPACE 24 SUBJECT TQ MECHANICAL DAMAGE DAMP OR CORROSIVE CONDITIONS, 10.8 STUD ELECTRICAL DRAWING INDEX (c) (d) FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS ONLY. DRAWING DESCRIPTION 1 2 EO.1ELECTRICAL GENERAL NOTES, SYMBOLS AND DETAILS, RISER, SCHEDULES _ E1.1 ELECTRICAL FLOOR PLAN, N ❑TES AND LIGHTING FIXTURE SCHEDULE 24' MINIM SEPARATION OMALL Tt? C X 4' EIECTRICIiL BOX ' 000 0 0 Q MUD RING DRYWALL FLUE PLATE APPLY 1/4" OF U.L. RATED INTUMESCENT COMPOUND (WHERE BOXES ARE INSTALLED LESS THAN 24" APART, OR WHERE BOX PLACEMENT IN 100 SQ. FT. OF ANY WALL EXCEEDS 100 SD. INCH.) ON ALL SIDES TOP AND BOTTOM OF BOX. BACK TO BACK ELECT. BOX MOUNTING DETAIL FOR RATED WALLS NOT TO SCALE a � � w 0 _o co Quo E E­ .5 Q � r � t B2STUD10 x 0 AA 26002514 - IB 26001404 1141 SE 6th TERRACE o` SUITE 1 FT. LAUDERDALE, FL 33316 o Phone (754) 300-7770 bbullock @sustainable- logic.net z� w x z a *+ n • r( °a � •rl TOGGLE SWITCH 120/277V. 20 AMP.,(M.H. =48" A.F.F.) LIQUID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED Cz a • FMN4 a TOGGLE SWITCH 120/277V. 20 AMP. ,(M.H. = 48- A.F.F.) 3 -WAY (c) (d) FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS ONLY. PER NEC 250 -50. $. MANUAL MOTOR STARTER, (M.H. =48" A.F.F.) ALL CONDUITS IN HAZARDOUS AREAS (PER NEC) SHAD. MEET THE REQUIREMENTS OF NEC CH. 5. Project #: 160201 PHASE WIRE VOLTAGE SINGLE PHASE a•a ::4 Cw a Ca � ° 04 �gz� �Q c� 4d �s2 $Q DIMMER SWITCH (M.H. = 48" A.F.F.) 17. ALL CONDUIT RUNS ARE SHOWN DIAGRAMATICALLY. THE EXACT ROUTING SHALL BE DETERMINED IN ° E S THE FIELD. UNLESS NOTED OTHERWISE. T OCCUPANCY SENSOR NOTES: 18. WHERE CORE DRILLING OF FLOORS /WALLS IS REQUIRED, THE CONTRACTOR SHALL SEAL OPENINGS CG2CUIT BREAKER IgQ,b WALL MOUNTED - OCCUPANCY SENSOR SWITCH,(M.H. =487A.F.F.) WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALL BRANCH FEEDER MFGR. /M# (SENSOR SWITCH / #WSD-PDT- 11P(21P) IF NEEDED) o,b COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER THAT IS CLEAN AND FUNCTIONAL. THE SWITCHES. INDICATES SWITCHING CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND SEAL THE OPENING AROUND THE GIRD, CEILING MOUNTED OCCUPANCY SENSOR - LIGHTING CIRCUIT CONDUIT. POLES CONTROLLER. MFGR. /MODEL# (SENSOR SWITCH /f CM-PDT) 19. PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PENETRATIONS, WALLS AND C 1. COORDINATE AND VERIFY EXACT PLACEMENT OF ALL OCCUPANCY SENSORS STRUCTURAL SLABS. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PDXES WITH MANUFACTURER PRIOR TO COMMENCEMENT OF WORK. VERIFY PRIOR TO SUBMITTING BID, THE LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS, WALLS, CONDUrT 2. OCCUPANCY SENSORS: ANY LOAD OVER 80OW 0120V AND 120OW 0277V AND STRUCTURAL SLABS. LIGHTING CONTRACTOR SHALL UTILIZE LOW VOLTAGE OCCUPANCY SENSORS WITH 20. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. 12 REMOTE POWER PACKS AS REQUIRED BY MANUFACTURER. 20 1 3. CONTRACTOR SHALL PROVIDE ALL SWITCHPACKS AND CONDUCTORS AS 21. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO ACCOMODATE EQUIPMENT 2. THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL REQUIRED FOR LAYOUTS AND CONTROLS SHOWN ON PLANS. SERVED, INCLUDING REQUIRED FUSES U.O.N. SWITCHES SHALL. BE HORSEPOWER RATED FOR MAX. 2 B WALL MOUNTED LV NFP SWITCH (M.H. =487A.F.F.) #B INDICATES NUMBER OF HORSEPOWER, HEAVY DUTY TYPE. 314" �=1 BUTTONS SERVICE AND DISTRIBUTION 22. THE CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATINGS FOR EQUIPMENT PRIOR TO 2 12 INSTALLATION. 3 SYMBOL DESCRIPTION ELECTRICAL BRANCH CIRCUIT PANELBOARD, RECESS MOUNTED. 23. ALL FUSES SHALL. BE CURRENT LIMITING, PER U.L., RATED 60OV. OR 250V. AS REQUIRED, WITH: 12 --low­ (SEE PANEL SCHEDULE FOR DETAILS) (c) NON TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FEEDING PANELS. 20 �....__. ELECTRICAL BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED. (b) TIME DELAY FUSES FOR MOTOR AND HVAC CIRCUITS. - -- - - (SEE PANEL SCHEDULE FOR DETAILS) 24. WIREWAYS SHALL BE SIZED AS REQUIRED, PER NEC, U.O.N. M -------- EXISTING EQUIPMENT TO REMAIN 25. ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL - MAGNETIC). TWO AND THREE 5 NEW EQUIPMENT OR WORK OF THIS PROJECT POLE CIRCUIT BREAKERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMITTED. 12 O CIRCUIT BREAKER, TYPE AND SIZE AS PER DRAWINGS. 26. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R) WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT. 20 TELEPHONE /COMPUTER RACEWAY SYSTEM 27. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS A CONSTRUED AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE LATER IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES AS REQUIRED FOR OTHER CLASSIFIED 20 SYMBOL DESCRIPTION AREAS. U.O.N. 12 a� TELEPHONE /COMPUTER TERMINAL BOARD "TTB" 28. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH U.L APPROVED WELDED CONNECTIONS GENERAL RECEPTACLE 6 UNLESS NOTED OTHERWISE THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYSTEM AS 3 1 . MAXIMUM OF 1/8- FROM THE FINISHED SURFACE OF THE DRYWALL AFTER THE DRYWALL IS PER NEC 250 -50. NEW Panel Name: A MANUFACTURER: SquareD or Equal LOCATION: BACK OF HOUSE MAIN LUGS: 100 AMPS A.I.C.: TO MATCH EXISTING FED FROM: METER CENTER DISCONNECT MOUNTING: RECESSED ENCLOSURE: NEMA 1 1 3 120/240V Project #: 160201 PHASE WIRE VOLTAGE 0,0 a•a ::4 Cw a Ca � ° 04 �gz� �Q c� 4d �s2 �M4 4/ • !P004 4-1 Un r-1 " LO ° E S CKT NO. T C O D E BRANCH FEEDER CG2CUIT BREAKER LOAD PHASE LASE CRCUff BREAKER BRANCH FEEDER C D E OgiTIPICATlON SWITCHES. T S VVIRE GIRD, CONDUIT TRIP POLES KVA A C KVA TRP PDXES WIRE GRD, CONDUrT 4A 1 LIGHTING L 12 12 1/2" 20 1 0.80 A 2. THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL 0.40 2 10 10 314" M PKU -1 ( y; COND. non conc. (FAN-only; ) 2 12 3 LIGHTING L 12 12 1/2" 20 1 0.80 C 0.40 M 4 3 5 SIGNAGE L 12 12 112" 20 1 1.20 A CONSTRUED AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE LATER 1.00 20 1 12 12 112" R GENERAL RECEPTACLE 6 COORDINATION DETAILS OF ALL TRADES SHALL BE RESPONSIBILITY OF THE GENERAL 3 7 ABOVE SHOW WINDOW L 12 12 1/2" 20 1 1.20 C 1.00 20 1 12 12 112" R GENERAL RECEPTACLE 8 9 BATHRMIB.O.H. LTS L 12 12 1/2" 20 1 0.50 A 1.00 20 1 12 12 112" R POS 10 2 iWH 1 O 12 12 31d" 20 2 2.4 C 0.50 20 1 12 12 1/2" R TBB RECEPTACLE 12 13 2.4 A 0.80 20 1 12 12 112" R DRINKING FOUNTAIN GFI 14 15 CASE LIGHTS L 12 12 112" 20 1 0.20 G 0.50 20 1 S SPARE 16 A 2.50 30 2 10 1D 314" PKU-1 (HEATER 5kw) 1.2 3 -12 -15 3 19 ABOVE SHOW WINDOW L 12 12 1/2 °° 20 1 1.20 C 2.50 20 2 S R 2 1 A SPACE 22 23 SPACE C SPACE 24 NOTES: 1. HACR Type Circuit Breaker 2. VerifyCB Size With EquipmentName Plate LTGJCONT LOAD @125% (L) 3. Lighting Circuits VIATlme Clack RECEPTACLES (per NEC) IRI 10.8 10.7 TOTAL CONNECTED LOAD: 21.5 KVA TOTAL LOAD DEMAND: 23.0 KVA CONNECTED LOAD 8.1 DWAND LOAD 7.6 4.3 4.3 5 °$ 5'6 MOTOR @100' /4M) LARGEST MOTOR @I 25wLM) KITCHEN LS,i85 /,(K) SPARES (S) OTHER LOAD (0) TOTAL LOAD DEMAND: 96 AMPS NEW TENANT LOAD WILL NOT IMPACT EXISTING ELECTRICAL SERVICE f METEF Q Q rgg ca 0.0 0.0 0.0 0.0 0.5 0.5 4.8 4.6 $ INTERCOM SYSTEM SPEAKER . MAXIMUM OF 1/8- FROM THE FINISHED SURFACE OF THE DRYWALL AFTER THE DRYWALL IS PER NEC 250 -50. FIRE ALARM/DETECTION TION SYSTEM INSTALLED. PROPER COORDINATION BETWEEN THE ELECTRICAL CONTRACTOR AND THE GENERAL NON - CONCURRENT LOAD IN) 0,0 a•a SYMBOL DESCRIPTION OUTLET BOXES SHALL BE SECURELY FASTENED. ANY AND ALL IMPROPERLY INSTALLED PLASTER COMPUTER/TELEPHONE OUTLET IN A SINGLE -GANG BOX MOUNTED AT 18" A.F.F. RINGS OR OUTLET BOXES SHALL BE REMOVED AND A NEW RING OR OUTLET INSTALLED AT THE 29. FOR EMERGENCY EXIT SIGNS AND EMERGENCY BATTERY PACKS MAKE CONNECTION AHEAD OF ALL VISUAL SIGNALING UNIT- FLASHING STROBE LIGHT ONLY (80" TO CONTRACTOR'S EXPENSE. I5 /75 CD BQTTOM)(NO AUDIO DEVICE) 31. THE CONTRACTOR SHALL SUBMIT 6 COPIES OF EQUIPMENT SHOP DRAWINGS FOR ELECTRICAL C = ABOVE THE COUNTER EQUIPMENT TO THE ENGINEER FOR REVIEW, PRIOR TO ORDERING SUCH EQUIPMENT. SWITCHES. (2)CD DUCT MOUNTED SMOKE DETECTOR, WITH SAMPLE TUBE, REMOTE TEST w } � ®��t � � j f �!!! AND HEAVY DUTY CONTROL RELAY. PAY 48" A F F } 30 PROPER PLASTER RINGS SHALL BE USED WITH OUTLET BOXES. PLASTER RINGS SHALL BE A ;u � ` � P = PueuC ( W = WALL MOUNTED (18" A.F.F. . MAXIMUM OF 1/8- FROM THE FINISHED SURFACE OF THE DRYWALL AFTER THE DRYWALL IS FIRE ALARM/DETECTION TION SYSTEM INSTALLED. PROPER COORDINATION BETWEEN THE ELECTRICAL CONTRACTOR AND THE GENERAL CONTRACTOR FOR RING INSTALLATION IS REQUIRED. NO "GOOF" RINGS WILL BE ALLOWED. ALL SYMBOL DESCRIPTION OUTLET BOXES SHALL BE SECURELY FASTENED. ANY AND ALL IMPROPERLY INSTALLED PLASTER RINGS OR OUTLET BOXES SHALL BE REMOVED AND A NEW RING OR OUTLET INSTALLED AT THE VISUAL SIGNALING UNIT- FLASHING STROBE LIGHT ONLY (80" TO CONTRACTOR'S EXPENSE. I5 /75 CD BQTTOM)(NO AUDIO DEVICE) 31. THE CONTRACTOR SHALL SUBMIT 6 COPIES OF EQUIPMENT SHOP DRAWINGS FOR ELECTRICAL EQUIPMENT TO THE ENGINEER FOR REVIEW, PRIOR TO ORDERING SUCH EQUIPMENT. (2)CD DUCT MOUNTED SMOKE DETECTOR, WITH SAMPLE TUBE, REMOTE TEST AND HEAVY DUTY CONTROL RELAY. ELECTRICAL COORDINATION NOTES GENERAL CONTRACTOR TO VERIFY MOUNTING HEIGHT OF ALL DEVICES WITH NOTE' ARCHITECT PRIOR TO DEVICE INSTALLATION. DETAIL REFERENCE 1. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND 4A SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID SHEET NUMBER REFERENCE WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, E -3 EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT. 2. THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE. EXISTING CONDITIONS NOTES 3 BE THE OR, WORK AS SHOWN AND 0 SUPERVISIONRESPONSIBILITY ESSARY 0 ACCOMPLISH THE WORK NOTED ON THE PLANS. 4. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCE 1. PRIOR TO SUBMITTING BIDS, THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE TO ORDERING OF LONG LEAD ITEMS, AS TO NOT INTEFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT ORDER ANY VERIFY EXISTING ELECTRICAL EQUIPMENT CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. FOLD VERIFY QUANTITIES OF EXISTING LIGHT ITEMS UNTIL APPROVED SHOP DRAWINGS ARE RETURNED TO HIM. FIXTURES, ELECTRICAL DEVICES, COMMUNICATION DEVICES, FIRE ALARM DEVICES, AND 5• THE CONTRACTOR SHALL KEEP ALL AREAS WHERE WORK IS BEING PERFORMED FREE FROM ELECTRICAL EQUIPMENT AS APPLICABLE. NOTIFY THE ARCHITECT AND ENGINEER OF 6 DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE END OF EACH ANY EXISTING CONDITIONS, WHICH WILL EFFECT THE SCOPE OF WORK AS SHOWN ON WORKING DAY. THE CONSTRUCTION DOCUMENTS. SUBMISSION OF A BID PROPOSAL WILL BE AND 7. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO COORDINATE ALL WORK OUTSIDE LEASE CONSTRUED AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE LATER SPACE WITH LANDLORD. ANY WORK OUTSIDE OF LEASE MUST BE PERFORMED AFTER 7 PM AND CLAIMS FOR MOBILIZATION, LABOR, EQUIPMENT, AND /OR MATERIALS REQUIRED COMPLETE BY 7 AM. AREAS MUST BE CLEAN AND READY FOR BUILDING OCCUPANCY BY 6 :00 BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED. AM EVERY MORNING. 2. PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PENETRATIONS, WALLS COORDINATION DETAILS OF ALL TRADES SHALL BE RESPONSIBILITY OF THE GENERAL TH NSIBILITY OF THE ELECTRfGAL 8 AND STRUCTURAL SLABS. IT SHALL BE E RESPO CONTRACTOR. CONTRACTOR TO VERIFY PRIOR TO SUBMITTING BID, THE LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS, WALLS, AND STRUCTURAL SLABS. TENANT - McLAUGHLIN STORE MAIN ELECTRICAL ROOM _ _ �- - - - - - - - -_:0 FO POLE MTD � I HT oU�E'f� TRANSFORMER i TRANSFOR 3PH EXISTING LINE WIREWAY "� I .;r� RISER GENERAL NOTE: NEW PANEL 'A' EXISTING EXISTING � �! 1. CONTRACTOR SHALL FIELD VERIFY CONDITIONS ff' EXISTING SUB -PANEL PANEL ••.. EXISTING I EXISTING fr 40GA 400A ELECTRICAL SERVICE EGlUIPhENT AND FEEDER, REPORT FOR ANY MAIN I MAIN DISCREPANCIES TO OWNER /ENGINEER PRIOR TO C❑NSTRLCTM AREA OF �� DISCONNECT DISCONNECT p I �; RISER KEY NOTES: ;� � ' �e g 120/240V 13 ?t ��"' I MAIN 1 2 i MAIN 2 2 (D EXISTING METER SOCKET WITH EXISTING 100A C.B. TO i 1 PH 3W '�� / I / REMAIN _ EXISTING PANELS TO BE DEMOLISHED DUE TO THEIR l-� i >t �. `„ I I CONDITION. JS 3 N PANEL TO BE PROVIDED AS SHOWN. 120/240V ` I I 120/240V 120/240V NEW 1� $W .,, 1 3 PH 4W 3 PH 4W i'; at I , 4 FIELD VERIFY AND LOCATE EXACT EXISTING FEEDER NEMA 1 _ �;/.aa. �-"" ROUTE. INTERCEPT EXISTING CONDUIT AND EXTEND TO _ NEW PANEL LOCATION AS REQUIRED (PROVIDE ALL 120/240V I NECESSARY FITTINGS). REMOVE EXISTING FEEDER AND 10 3W �' PROVIDE NEW FEEDER FROM EXISTING 100A NEMA 1 EXISTING LOAD WIREWAY ' I DISCONNECT IN MAIN ELECTRICAL ROOM TO NEW PANEL LOCATION. F -2 F -1 �.� I F FEEDER SCHEDULE: GRIIUND NEW lOQAMP FEEDER, _. _ __ _ _ - ®_ _I_ ._ _ _� -M-.•� f f f 1 fii FLOOR F -1 • s � i ! ' 3 #3 CU, #B CU GND IN EXISTING i -1/4 C ' AA1 NEW 100AMP FEEDER, 4 TO TENANTS TO TENANTS - F'2 3 #3 CU, #B CU GND IN NEW 1 -1 /4'C RISER NEW EQUIPMENT PARTIAL EXISTING ELECTRICAL N.T.S. EXISTING EQUIPMENT DEMOLISHED U A B C o