13-1341-026APLLIA
1. INSTALLATION SHALL COMPLY W —NFPA 96 /LOCAL CODES.
2. HOOD SHALL BE 18 GAGE STAINLESS STEEL (TYPE 304). ALL SEAMS AND JOINTS
SHALL BE LIQUID TIGHT CONTINUOUS EXTERNAL WELD.
3.
A. EXHAUST DUCTWORK SHALL BE 16G CARBON STEEL ALL WELDED CONSTRUCTION.
B. SUPPLY DUCTWORK SHALL BE 22G GALVANIZED STEEL.
4. HOOD SHALL HAVE: SPARKS ARRESTER DEVICES AND FILTERS SHALL BE LOCATED
AT A MINIMUM 4 FT ABOVE THE APPLIANCE COOKING SURFACE.
5. MAKEUP AIR FOR REPLACEMENT IN SOLID FUEL COOKING APPLIANCE SHALL
MAINTAIN A POSITIVE PRESSURE WITHIN THE SPACE. INTERLOCK PEF -1 WITH HP -1
FAN TO PROVIDE MORE THAN THE EXHAUST RATE OF THE HOOD THRU OUTSIDE AIR
WITHIN THE SPACE ALL THE TIME THE HOOD IS IN OPERATION.
6. EXHAUST AIR DUCT SHALL BE IN A 2 HOURS FIRE RESISTANT ENCLOSURE. A
6" MIN. CLEARANCE FROM NON — COMBUSTIBLE OR LIMITED COMBUSTIBLE
ENCLOSURE WALLS IS REQUIRED.
7. PROVIDE ACCESS PANEL FOR CLEANING AND INSPECTION EVERY 12 FT FOR
HORIZONTAL DUCTS, AND AT EVERY FLOOR FOR VERTICAL DUCTS. ACCESS PANELS
SHALL BE GREASETIGHT, FASTENERS TO SECURE ACCESS PANELS SHALL BE
CARBON STEEL OR STAINLESS STEEL AND SHALL NOT PENETRATE DUCT WALLS.
HOOD NOTES:
1. INSTALLATION SHALL COMPLY W —NFPA 96 /LOCAL CODES.
2. HOOD SHALL BE 18 GAGE STAINLESS STEEL (TYPE 304). ALL SEAMS AND JOINTS
SHALL BE LIQUID TIGHT CONTINUOUS EXTERNAL WELD.
3.
A. EXHAUST DUCTWORK SHALL BE 16C CARBON STEEL ALL WELDED CONSTRUCTION.
B. SUPPLY DUCTWORK SHALL BE 22C GALVANIZED STEEL,
4. HOOD SHALL HAVE: A WET CHEMICAL FIRE PROTECTION SYSTEM NOZZLES
EXPLOSION PROOF LIGHT, STEEL MESH GREASE FILTERS, GREASE DRIP TRAY
DRAINING TO 22 GAGE STAINLESS STEEL GREASE RECEPTACLE.
EXHAUST FAN NOTE:
FAN SHALL BE MOUNTED ON NON — COMBUSTIBLE ROOF CURB ACCORDING TO
NFPA -96. DISCHARGE OF FAN SHALL BE 40" MIN. FROM ROOF SURFACE AND 10'
MIN. HORIZONTALLY FROM ANY FRESH AIR INTAKE OR THE SUPPLY FAN. FIRE MODE
REQUIRES EXHAUST FAN TO BE ON WHENEVER THE EXTINGUISHING SYSTEM IS
ACTIVATED.
i[r,
FAN SHALL BE MOUNTED ON ROOF CURB 10' MIN. FROM EXHAUST FAN OR
PLUMBING VENT. S. FAN SHALL BE ELECTRICALLY INTERLOCKED WITH EXHAUST FAN
AND WITH HOOD FIRE SUPPRESSION SYSTEM TO BE "OFF" IN CASE OF FIRE.
KITCHEN VENTILATION NOTES:
1. THE KITCHEN VENTILATION SYSTEM HAS BEEN DESIGNED WITH THE INTENT TO
MANTAIN A NEGATIVE PRESSURE, NEVER OVER 0.02" W.C. RELATIVE TO ALL INDOOR
SPACES SURROUNDING THE KITCHEN SPACE, DURING COOKING HOURS, COMPLYING
WITH "THE FLORIDA ENERGY EFFICIENCY CODE" SECTION 303.1 (A).
2. ALL EXHAUST AND MAKE UP AIR SYSTEM COMPONENTS (FANS, DAMPERS, ETC.)
SHALL BE INTERLOCKED IN SUCH A WAY THAT THE BALANCE PRESCRIBED IN (1)
ABOVE IS MAINTAINED THROUGHOUT ALL COOKING HOURS, AND ALL VARIATIONS OF
COOKING OPERATIONS. PROVIDE PILOT LIGHT IN KITCHEN AREA INTERLOCKED TO
SUPPLY & EXHAUST FANS.
a. SUPPLY AND EXHAUST FANS ARE INTERLOCKED WITH PILOT LIGHT IN KITCHEN
AREA.
b. FIRE MODE REQUIRES EXHAUST FAN CONTINUES TO OPERATE AND SUPPLY FAN
STOPS.
c. HOOD EXHAUST FANS SHALL OPERATE WHENEVER THE EXTINGUISHING SYSTEM IS
ACTIVATED.
d. FIXED PIPE EXTINGUISHING SYSTEMS IN A SINGLE HAZARD AREA SHALL BE
ARRANGED FOR SIMULTANEOUS AUTOMATIC OPERATION UPON ACTIVATION OF ANYONE
OF THE SYSTEMS.
BELT DRIVE W/ ADJUSTABLE PULLEYS
REMOVABLE MOTOR DOME
KEF -1
DISCONNECT SWITCH
WOOD NAILER (TYPICAL)
HINGE ASSEMBLY AS PER NFPA
VENTED CURB EXTENSION
ADAPTER CURB CAP 0.05 ALUMINUM
W/ WELDED CORNERS
ANCHOR CURB TO CURB EXTENSION
USING 1/4 "x2 "L SELF TAPPING SHEET
METAL SCREWS EVERY 6" O/C (8 MIN.)
PREFABRICATED CURB FOR
INSULATED ROOF INSTALLATION
SECURE CU W/ 1/8" STAINLESS STEEL
CABLE OR STRAPS ANCHOR TO METAL
STRUCTURE WITH 3/8" BOLTS, NUTS
AND WASHERS IN A CRISSCROSS
PATTERN OVER UNIT, ALSO PROVIDE
BOOKLETS TO ADJUST.
PERMANENTLY LUBRICATED BALL BEARING
—MOTOR
VIBRATION ISOLATORS
— CENTRIFUGAL FAN
ANCHOR FAN TO CURB USING 1/4" x
2" L SELF TAPPING SHEET METAL
SCREWS EVERY 6" 0/C (8-MINIMUM)
GREASE CONTAINER ANCHOR CURB
-WELD DUCT TO FLANGE TO SEAL TOP
OF CURB OPENING (MINIMUM 18" ABOVE
Q(FE��
�C1RB' SECURED TO ROOF USING 1/4" x 6" L
� SELF TAPPING SCREWS, TOGGLE BOLTS OR THD
NIZ RODS AT CORNERS EVERY 12" 0/C MAX.
r� BUILT -UP ROOFING
I 3" MIN. - 1
3/8" BOLT AND NUT OR 3/8 "x2" EXISTING WOOD DECK OVER WOOD
ANCHOR 6" 0/C JOIST.
(8 MIN.) ' 18" MIN.
RAME OPENING WITH 3 "x3 "x1/4"
WOOD JOIST ANGLES
NOTE: WELDED GREASE EXHAUST
MECHANICAL CONTRACTOR SHALL FIELD VERIFY EXISTING MOUNTING CONDITIONS OF EXISTING DUCT.PROVIDED WITH A U.L. LISTED
FAN AND MAKE ALL NECESSARY ARRANGEMENTS TO COMPLY WITH CURRENT CODE SAFETY THERMAL CERAMIC BLANKET 1 -1/2"
REQUIREMENTS. THICK, PROVIDES 2 -HR. FIRE RATING
GREASE DUCT BRACING AND SUPPORTS SHALL BE OF NONCOMBUSTIBLE MATERIAL SECURELY INSTALLED PER MANUFACTURER'S LISTING
ATTACHED TO THE STRUCTURE AND DESIGNED TO CARRY GRAVITY AND SEISMIC LOADS WITHIN (3M FIRE FIRE DUCT WRAP OR
THE STRESS LIMITATIONS OF THE FLORIDA BUILDING CODE, BUILDING. BOLTS, SCREWS, RIVETS EQUIVALENT)
AND OTHER MECHANICAL FASTENERS SHALL NOT PENETRATE DUCT WALLS
FAN CURB TO ROOF CONNECTION SHALL BE SECURED TO WINDSTAND WIND LOADS OF 164
MPH WITH A SAFETY FACTOR OF AT LEAST FOUR (4).
EXHAUST FAN HOOD TYPE -1 INSTALLATION DETAILS
N.T.S.
NOTES:
i PROVIDE OPENING IN WALL MINIMUM 1/8" PER
FOOT LARGER THAN OVERALL SIZE OF DAMPER STEEL BLADES W/
AND SLEEVE ASSEMBLY. MAXIMUM OPENING INTERLOCKING
SHALL NOT EXCEED 1�8" IN BOTH MOUNTING JOINTS
HORIZONTAL AND VERTICAL DIRECTION PER
FOOT PLUS ONE INCH. OPENING SHALL NOT ANGLES.
BE LESS THAN .1 /4" LARGER FOR ANY SIZE DYNAMIC FIRE
(� DAMPER AND SLEEVE ASSEMBLY. DAMPER UL 555
SLEEVE DAM ERS FU E MINIMUM OF 16 D E RATED
P TO36"WX 24 "H AN 14 GAGE
IF DAMS WIDTH EXCEEDS 36" OR HEIGHT ,(D t
SLEEVE
3" MAX. ON
ALL SIDES.
e
PREFABRICATED
CURB
INTERNAL LINING
INSTALL EXTERNAL
DUCT OUTSIDE
COLLAR SECTION
SEAL ALL AROUND
W /SILICONE SELANT
do SECURE W /GALV.
SHEET METAL SCREWS
031- i e
DUCT - ROOF PENETRATION DETAIL
N.T.S.
ANCHOR FAN TO CURB
USING 1/4" x 2" L
SELF TAPPING SHEET
METAL SCREWS EVERY
6" O/C (8-MINIMUM)
FI LTEf
SUPP
12" C
MIN.(T
ON
N�Z
/ WOOD DECK OVER
/ WOOD JOIST.
FRAME OPENING WITH
3 "x3"x1 /4" ANGLES
GALVANIZED STEEL
SUPPLY DUCT
CURB SECURED TO ROOF USING
1/4" x 6" L SELF TAPPING SCREWS,
TOGGLE BOLTS OR THD RODS AT
CORNERS EVERY 12" O/C MAX.
SECURE CU W/ 1/8" STAINLESS
STEEL CABLE OR STRAPS ANCHOR TO
METAL STRUCTURE WITH 3/8" BOLTS,
NUTS AND WASHERS IN A
CRISSCROSS PATTERN OVER UNIT,
ALSO PROVIDE BOOKLETS TO ADJUST.
=6
X12
WOOD NAILER (TYPICAL)
PREFABRICATED CURB
__FOR INSULATED ROOF
INSTALLATION
,, INSULATION
3/8" BOLT AND NUT
OR 3/8 "x2" ANCHOR
— 6" 0/C (8 MIN.)
NOTE:
MECHANICAL CONTRACTOR SHALL FIELD VERIFY EXISTING SITE
CONDITIONS AND COMPLY WITH CURRENT CODE SAFETY
REQUIREMENTS.
DUCTS SUBJECT TO POSITIVE PRESSURE AND DUCTS
CONVEYING MOISTURE -LADEN OR WASTE - HEAT -LADEN AIR
SHALL BE CONSTRUCTED, JOINED AND SEALED IN AN
APPROVED MANNER.
SUPPLY FAN HOOD TYPE -1 INSTALLATION DETAILS
N.T.S.
M
'REF. ROOF CURB MANUF.
�Y LOREN COOK MOD. VCC
VENTED)
" MINERAL WOOD
A FIRE BARRIER 1000 N /S, 1003 S/L
3 2000+ SILICONE SEALANT FOR WALL
3SEMBLY APPLY SEALANT TO BOTH
DES OF CEILING
i GAUGE WELDED STEEL GREASE
(H. DUCT. PROVIDE
A FIRE DUCT WRAP AS PER
aNUFACTURER RECOMMENDATIONS.
ETAL STUDS
VASHABLE REMOVABLE NON COMBUSTIBLE
ALUMINIUM FILTERS
U.L APPROVED)
3
MOUNTING ANGLES SHALL BE A MINIMUM OF
1 1/2- X 1 1/2- X 14 GAGE AND /
FASTENED WITH LG. WELDS, OR 3/10680 IVETST 0 SLEEVE AT
3I A�
A MAXIMUM SPACING OF 12" WITH A MINIMUM
OF TWO CONNECTIONS IN EACH SIDE TOP
ARCHITECTURAL
PLANS.
(EXISTING FIRE
DATE
DESCRIPf.GN
s
;`_'
y 24
U.L. APPROVED
INCAND. VAPOR 45'
PROOF UGTH
12 42
REMOVABLE GREASE RECEPT. LESS THAN
1 GAL CAPACITY
AND BOTTOM. MOUNTING ANGLES SHALL
RATED CEILING
All ideas, designs, arrangements, plans and specifications indicated or represented by this drawing
are owned by and are the property of Borges + Associates, P.A., and were created, evolved and
developed for use on and in connection with the specified project. No copies, transmissions,
reproductions, or electronic manipulation of any portion of these drawings in whole or in part are to
be made without the express written permission of Borges + Associates, P.A.
All copyrights reserved U 2005
bor es +
9
associates
OVERLAP WALL A MINIMUM OF ONE INCH.
CONSTRUCTION)
305.374.9216 phone 305.374.9217 fax
r
,
,fir _ ®•�� 41 as
4
a
p. }r 4 1
• All
: `a``
x
20-
Dizabeth I Prida, 'P.E #59464
Project Team, ,.
a
I
M.E. Engineering Consultants, Inc.
Ph:(305)9054652
CA 29121
4
FIRE DAMPER UNOBSTRUCTED OPENING SIZE
_
' 4
5818 SOUTH DIXIE HIGHWAY
CONNECT ANGLES W/
Project Number 130220
° 1 1/2 "x1 1/2 "x1/8"
KITCHEN HOOD DETAILS
Scale:
i
�
AS SHOWN
o
t
ADJUSTABLE VANE 2"
SUPPLY AIR DIFF.
22 GA STAINLES —STEEL PANEL
IS SAME SIZE AS OPENING IN WALL ABOVE
"
1/4 DIA. BOLT
* DIMENSIONS TO
GALVANIZED ANGLE
THE CEILING (OWAC) SIZE SEE PLANS FOR
DIMENSIONS. IRE AMPEff TYPE WITH BLADES
DAMPER
1 MIN. OVERLAP
TYP. 2 PLACES
SUIT DUCT SIZE
SUPPORT (TYPICAL)
6"
OUT OF AIR STREAM. WALL OPENING ABOVE
(FOUR SIDES)
* PLUS INSTALLATION.
TO CHANNEL
— "�-
LING
DOENOTI LUDEE BSLADE STORAGE POCKETS
6
WELD PIPE
HEIGHT. COORDINATE.
TYP. 2
C 4" STEEL
ALL AROUND 6"
PLACES
CHANNEL WELDED
3 16 (�)
z
S— JONT, SLEEVE TO DUCT.
3/16
TO PIPE SUPPORT
71
EXTERIOR CONCRETE WALL
6
DUCTWORK. SEE PLANS FOR SIZES. MAKE F
°
A
°
SIZE SAME AS CONNECTED DUCTWORK SIZE
7
2 1/2" DIA. STD. PIPE
12" x 12" x 3/8" PLATE
LINO ON PLANS.
� >-
>1
W/(4)1/4" DIA. ANCHOR
WEIGHT COLUMN
BOLTS WITH HILTI KWIK
7
DUCTWORK ACCESS DOOR -(AD). MAKE ITS
SEE FLASHING DETAIL
N
(OR EQUAL) 2" EMBEDMENT
z
°
WIDTH THE WIDTH OF THE' LESS 2
INCHES (BUT NOT LESS THAN 6 INCHES)) AND
DETAIL ON ARCH. DWGS.
°
EXISTING ROOF
ITS LENGTH NOT LESS THAN 1/2 THE HEIGTH
OF THE FIRE DAMPER (BUT NOT LESS THAN
12 INCHES,. PROVIDE ACCESS DOOR IN
CEILING T GAIN ACCESS TO DUCTWORK
ACCESS DOOR IF CEILING IS INACCESSIBLE.
TYPICAL FIRE (F) DAMPER INSTALLATION -
WITH DUCTWORK CONNECTION DETAIL
N.T.S.
M 111 DETAILS
ROOF DUCT SUPPORT DETAIL.
N.T.S.
KITCHEN HOOD TYPE -1 SYSTEM DETAILS
N.T.S.
N.T.S.
ISSUE DATE:
No.
DATE
DESCRIPf.GN
All ideas, designs, arrangements, plans and specifications indicated or represented by this drawing
are owned by and are the property of Borges + Associates, P.A., and were created, evolved and
developed for use on and in connection with the specified project. No copies, transmissions,
reproductions, or electronic manipulation of any portion of these drawings in whole or in part are to
be made without the express written permission of Borges + Associates, P.A.
All copyrights reserved U 2005
bor es +
9
associates
architecture urban - planning interior- design
200 S. Biscayne Blvd., Suite 800 ■ Miami, Florida 33131
305.374.9216 phone 305.374.9217 fax
r
,
,fir _ ®•�� 41 as
4
a
p. }r 4 1
• All
: `a``
x
Dizabeth I Prida, 'P.E #59464
Project Team, ,.
a
I
M.E. Engineering Consultants, Inc.
Ph:(305)9054652
CA 29121
Project'Name .
R I E
HOUSE OF KABOB - SOUTH MIAMI
5818 SOUTH DIXIE HIGHWAY
Miami, FL 33143
Project Number 130220
Drawing Name
KITCHEN HOOD DETAILS
Scale:
Drawing Number
AS SHOWN
M-401