13-1341-022HVAC NOTES: 1. ALL WORK SHALL CONFORM WITH THE FLORIDA BUILDING CODE, 2010 EDITION, AND ALL OTHER APPLICABLE STATE AND LOCAL REGULATIONS AND ORDINANCES. 2. CONTRACTOR SHALL WARRANT ALL WORK TO BE FREE OF DEFECT IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE PROJECT. 3. PROVIDE ALL NECESSARY INSTRUCTIONS TO THE OWNER IN THE OPERATION OF THE MECHANICAL SYSTEMS. 4. PROVIDE EQUIPMENT MAINTENANCE AND INSTRUCTION MANUALS. THE MANUAL SHALL ESTABLISH ALL REQUIRED SCHEDULED MAINTENANCE THAT SHALL BE PERFORMED DURING THE LIFE OF THE BUILDING TO GUARANTY THE WORKING CONDITION OF THE INSTALLED SYSTEM AND THE MAINTENANCE OF A PROPER I.A.Q. IN THE BUILDING. MANUALS SHALL BE SUBMITTED TO THE ENGINEER FOR ACCEPTANCE. 5. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE OWNER BEFORE PROCEEDING WITH PURCHASE OR INSTALLATION OF ALL EQUIPMENT AND MATERIALS SPECIFIED IN THESE DOCUMENTS. 6. PROVIDE ALL NECESSARY ACCESS PANELS TO CONTROL VALVES, DAMPERS, ETC. 7. BALANCE ALL SYSTEMS TO PROVIDE AIR QUANTITIES AND CAPACITIES AS INDICATED ON DRAWINGS. ADJUST AND BALANCE DIFFUSERS IN ACCORDANCE WITH QUANTITIES SHOWN ON PLANS. (NATIONAL ENVIRONMENTAL BALANCING BUREAU PROCEDUAL STANDARDS (1991) OR AABC NAT. STANDARDS (1989) F) SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL. 8. ALL WORK SHALL BE FIELD CHECKED BEFORE INSTALLATION AND COORDINATED WITH ALL OTHER TRADES. 9. A/C CONTRACTOR IS RESPONSIBLE FOR OBTAINING HIS OWN PERMIT AND PAYING ALL PERMIT FEES. 10. ALL SIZES SHOWN FOR LINED AND UNLINED DUCTS ARE CLEAR INSIDE DUCT DIMENSIONS. 11. CONDITIONED AIR DUCTWORK SHALL BE CLASS "ONE" FIBER GLASS DUCT BOARD IN ACCORDANCE WITH SMACNA'S FIBROUS DUCT STANDARDS, R -6 IN CEILING SPACE. 12. PROVIDE VOLUME DAMPERS, TURNING VANES, ETC., IN DUCTWORK FOR PROPER AIR FLOW AND BALANCE. PROVIDE MULTIPLE VANE EXTRACTORS OR SPLITTERS WITH CONTROL RODS AT ALL OUTLETS CONNECTED CLOSER THAN TWO DUCT DIAMETERS TO MAIN SUPPLY DUCT AND WHERE SHOWN ON DRAWINGS. 13. REFRIGERANT PIPING SHALL BE SEAMLESS COPPER TYPE "L" HARD OR SOFT DRAWN OR ACR COPPER TUBING WITH WROUGHT COPPER SOLDER JOINT FITTINGS. SOLDER SHALL BE 95/5, APPLIED WITH SUITABLE FLUX. 14. INSULATE REFRIGERANT SUCTION PIPING WITH 3/4" FIRE RESISTANT FOAM PLASTIC OR CLOSED CELL POLYETHYLENE PRE MOLDED PIPE INSULATION. 15. PROVIDE AIR CONDITIONING UNITS WITH MATCHING HEAT -COOL PROGRAMMABLE THERMOSTATS WITH ON -OFF -AUTO SUB -BASE SWITCH, FURNISHED BY EQUIPMENT MANUFACTURER. 16. COORDINATE LOCATION OF DUCTWORK WITH OTHER TRADES, PARTICULARLY WHERE DUCTS RUN THROUGH STRUCTURAL ELEMENTS. PROVIDE ALL NECESSARY SLEEVES BEFORE CONCRETE IS POURED. 17. ALL CONTROL WIRING SHALL BE THE RESPONSIBILITY OF THE MECHANICAL SUB - CONTRACTOR. MECHANICAL SUB CONTRACTOR TO FURNISH ALL MOTORS, STARTERS, AND RELAYS, ETC. 18. VENTILATION DUCTWORK SHALL BE SHEET METAL PER SMACNA STANDARDS. FIBER GLASS DUCTS, EXHAUST AND RETURN AIR DUCTWORK NEED NOT BE INSULATED. 19. CONDENSATE DRAIN PIPING SHALL BE INSULATED WITH 3/4" AMCOAFLEX INSULATION 20. ALL MECHANICAL EQUIPMENT LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A WIND PRESSURE OF 60 PSF (140 MPH WINDS) FROM ANY DIRECTION AS PER F.B.C. 2010. 21. ALL FAN UNITS, MOTORS, COMPRESSORS, ETC., SHALL BE ISOLATED, AS REQUIRED, TO OPERATE QUIETLY SO THAT OBJECTIONABLE SOUND WILL BE HEARD IN THE OCCUPIED SPACES, DUE TO AIR VELOCITY, MOTOR HUM, VIBRATION, OR MECHANICAL MOVEMENT. OUTDOOR AIR VENTILATION SCHEDULE (AS PER TABLE 403.3 F.B.C. MECHANICAL) EQUIPMENT TAG OCCUPANCY CLASSIFICATION AREA SERVED (Square feet) AIR FLOW RATE (Cfm /sf) OCCUPANCY LOAD (# of persons) OUTDOOR AIR (CFM /Person) EXHAUST REQ,D (# of persons) TOTAL exhaust TOTAL intake REQUIRED PROVIDED REQUIRED PROVIDED (E) RTU -4 KITCHEN AREA 492 SF - -- 6 - -- 0.7 CFM /SF - 520 CFM - 1,030 CFM - -- 290 CFM (E) RTU -4 DELIVERY 330 SF 0.18 3 7.5 CFM /P --- - -- --- + 82 CFM 100 CFM (E) RTU -4 STORAGE 60 SF 0.12 - -- - -- - -- - -- - -- + 8 CFM 10 CFM (N) RTU -1 SEATING 1,565 SF 0.18 40 7.5 CFM /P - -- - -- - -- + 581 CFM 600 CFM (N) RTU -1 BATHROOMS 110 SF - -- - -- - -- 5%0 CFM /T -(2) 70 CFM - 140 CFM - -- - -- CFM (N) RTU -1 JANITOR 13 SF - -- - -- - -- 100 CFM -100 CFM - 100 CFM - -- - -- CFM (E) RTU -3 ENTRANCE 615 SF 0.06 - -- - -- - -- - -- - -- + 36 CFM 400 CFM (E) RTU -3 KITCHEN 250 SF - -- - -- - -- 0.7 CFM /SF -- THRU HOOD 12.4 EA TYPE PROPELLER PROPELLER U< QUANTITY 1 2 o DRIVE TYPE DIRECT DIRECT TOTALS FAN MOTOR SIZE (HP) 3,435 SF - -- - -- - -- - -- -760 CFM - 1,270 CFM + 683 + 1,400 NOTES BALANCE + 130 1- OUTDOOR AIR PROVISIONS FOR VENTILATION SHALL SATISFY THE MINIMUM REQUIREMENTS FOR ACCEPTABLE INDOOR AIR QUALITY AS PER ANSI /ASHARE STANDARD 62.1 -2010, VENTILATION RATE PROCEDURE. 2 -THE FULL VOLUME OF OUTSIDE AIR ESTABLISHED IN THIS SCHEDULE SHALL BE DELIVERED TO THE SPACE AT ALL TIMES THAT THE BUILDING IS OCCUPIED AIR FLOW BALANCING SCHEDULE - WHOLE BUILDING AREA SERVED AIR EXHAUSTED OR TRANSFERED. MAKE -UP AIR SUPPLIED OR TRANSFERED. EQUIP. TAG No. GRAND TOTAL KITCHEN HOOD - 2,538 - 2,610 - KEF -1 & KEF -2 ( -} 5,148 KITCHEN HOOD - ( +) 4,118 KSF -1 ( +} 4,118 KITCHEN & ENTRANCE - ( +) 400 (E) RTU -3 ( +) 400 BATHROOMS ( -) 140 - -- (2) EF -1 ( -) 140 JANITOR ( -) 100 - -- EF -2 ( -) 100 SEATTING 0.6 ( +} 600 (N) RTU -1 ( +) 600 KITCHEN & DELIVERY B ( +} 400 (E) RTU -4 ( +) 400 TITUS _J TOTAL CAPACITY (MBH) AIR 97.14 25.7 300 FL 40.46 63.1 z WHOLE BUILDING ( -} 4,320 ( +) 4,464 - ( +) 130 1- NOTICES THAT REMODELED KITCHEN HAS BEEN DESIGNED WITH THE INTENT TO MANTAIN A NEGATIVE PRESSURE, NEVER OVER 0.02" W.C. RELATIVE TO ALL INDOOR SPACES SURROUNDING THE KITCHEN SPACE, DURING COOKING HOURS, COMPLYING WITH "THE FLORIDA ENERGY EFFICIENCY CODE" SECTION 303.1 (A). 2- NOTICES THAT REMODELED KITCHEN IS OPEN TO MAIN SALES AREA. AIR DISTRIBUTION SCHEDULE SYMBOL USE TYPE ACCESSORIES MFG. REMARKS ROOF AREA SERVICE KITCHEN &ENTRANCE KITCHEN AND SEATING & MODEL DRAW THRU DRAW THRU NOMINAL TONS CEILING 7.5 TOTAL AIR (CFM) TDC - ROUND NECK - 24" x 24" A SUAPIPPLY DIFFSSER O.B.D. TITU LOUVERED FACE - SUPPLY - 91'DB /77WB /44'DB z QUANTITY / TYPE 1/ CENTRIFUGAL 1/ CENTRIFUGAL (HIGH) HORIZONTAL BLOW PATTERN EXTERNAL STATIC PRESSURE (IN. WC) 0.6 LOUVERED bor es + 9 FAN MOTOR SIZE (HP) 300FL- SIDE WALL AA- TYPE -1 -AG15 B SUPPLY GRILLE O.B.D. TITUS _J TOTAL CAPACITY (MBH) AIR 97.14 25.7 300 FL 40.46 63.1 z SQUARE 78.8/64.4 80.9/71 24" X 24" MODULE SIZE WITH C SUPPLY CEILING O.B.D. TITUS 6" X 6" DUCT SIZE. 2 WAY PATTERN. 1 AIR DIFFUSER 35.36 MCD w KW 9.6 12 = PHASE 24" X 24" RETURN DIFFUSER WITH 1 RETURN PERFORATED O.B.D. TITUS BORDER TYPE -3. PROVIDE AG95 SIZE (IN) AIR CEILING KITCHEN PAR OBD 30 REFRIGERANT TYPE DIFFUSER R -41 OA a: QUANTITY NOTES: 1. ALL DIFFUSER TO BE 4 WAY AIR FLOW UNLESS OTHERWISE INDICATED ON DRAWINGS. 2. MAXIMUM NOISE CRITERIA: 30/35. 3. MAXIMUM NECK VELOCITY: 500FPM. 4. DIFFUSERS AND GRILLES IN ALUMINUM CONSTRUCTION. ROOFTOP PACKAGE AIR CONDITIONING UNIT SCHEDULE FAN MARK (E) RTU -3 & 4 (N) RTU -1 LOCATION ROOF ROOF AREA SERVICE KITCHEN &ENTRANCE KITCHEN AND SEATING UNIT TYPE DRAW THRU DRAW THRU NOMINAL TONS 5.0 7.5 TOTAL AIR (CFM) 2,000 3,000 OUTSIDE AIR (CFM) 400 600 OUTSIDE ENTERING AIR TEMP.('F) SUMMER /WINTER 91'D13/77W6/44'D13 91'DB /77WB /44'DB z QUANTITY / TYPE 1/ CENTRIFUGAL 1/ CENTRIFUGAL (HIGH) U` EXTERNAL STATIC PRESSURE (IN. WC) 0.6 1 bor es + 9 FAN MOTOR SIZE (HP) 1.0 1.72 305.374.9216 phone 305.374.9217 fax MAXIMUM FAN SPEED (RPM) 1.075 834 _J TOTAL CAPACITY (MBH) 57.5 97.14 25.7 SENSIBLE CAPACITY (MBH) 40.46 63.1 z ENTERING AIR TEMPERATURE (DB /WB'F) 78.8/64.4 80.9/71 J 0 LEAVING AIR TEMPERATURE (DB /WB'F) 46.5/46.5 59.1/58.2 v AIR PRESSURE DROP (MAX.) IN. WC 0.65 1 Project Number 130220 TOTAL CAPACITY (MBH) 35.36 40.8 w KW 9.6 12 = PHASE 240 -1 240 -3 w TYPE 1" THROWAWAY 2" THROWAWAY -~' W SIZE (IN) (1) 24 x 30 x 1 (4) 16 X 20 KITCHEN EFFICIENCY ( %) 30 30 REFRIGERANT TYPE R -41 OA R -41 OA a: QUANTITY 1 2 0 TYPE SCROLL SCROLL ca RLA 17.6 12.4 EA TYPE PROPELLER PROPELLER U< QUANTITY 1 2 o DRIVE TYPE DIRECT DIRECT z 0 FAN MOTOR SIZE (HP) 1/3 1/8 MAXIMUM FAN SPEED (RPM) 1,100 825 ELECTRICAL SERVICE (V /PH /Hz) 240/1/60 240/3/60 EER /SEER 11.0 11.0 MANUFACTURER RHEEM CARRIER MODEL NUMBER RSKA- A060JK 50HJ008PHV5 --- RY WEIGHT(LBS) 580 830 DIMENSIONS W x D x H (INCHES) 47.5 X 52 X 41 59 X 88 X48 ACCESSORIES: 1., 3., 4., 5., & 7. 1., 3., 4., 5., & 6. ACCESSORIES: 1. SINGLE POINT POWER CONNECTION 2. PREMIER LINK DDC CONTROL 3. LIQUID LINE FILTER DRYER 4. MANUAL RESET HIGH PRESSURE SWITCHES 5. 14" HIGH CURB 144 Ibs 6. HIGH STATIC INDOOR MOTOR 7. O/A MOTORIZER DAMPER. FAN SCHEDULE FAN SONES MANUFACTURER AREA SERVED RPM REQUIRED HP CFM & S.P. ELECT. SERVICE DRIVE WEIGHT REMARKS ACCESSORIES TAG LEVEL OPENING VOLTS /PH /Hz LBS• All ideas, designs, arrangements, plans and specifications indicated or represented by this drawing MODEL ND MBER. developed for use on and in connection with the specified project. No copies, transmissions, reproductions, or electronic manipulation of any portion of these drawings in whole or in part are to be made without the express written permission of Borges + Associates, P.A. All copyrights reserved © 2005 bor es + 9 associates architecture urban - planning interior - design 200 S. Biscayne Blvd., Suite 800 ■ Miami, Florida 33131 305.374.9216 phone 305.374.9217 fax a.4W EF -1 1.1 BROAN BATHROOMS 900 N/A 25.7 100 ® 0.20" WG 120/1/60 DIRECT 9 SWITCH THRU LIGHTS, - -- M.E. Engineering Consultants, Inc. LP-80 CA 29121 Project Name R I C E (WATTS) 70 ® 0.25" WG Miami, FL 33143 Project Number 130220 Drawing Name INTEGRAL BACKDRAFT Scale: Drawing Number AS SHOWN (CEILING MOUNTED) DAMPER, UL -507 KEF -1 & KEF -2 -- CAPTIVE AIR KITCHEN 1,474/ REFER TO 0.75 2,538 @ 1.0" WG 120/1/60 BELT 84 UPBLAST CENTRIFUGAL 2, 3, 4 & 5. (BY HOOD DU85HFA HOOD 1,504 HOOD SHOP 2,610 @ 1.0" WG EXHAUST VENTILATOR MANUFACTURER) (ROOF MOUNTED) DRAWING. KSF -1 -- CAPTIVE AIR KITCHEN 799 REFER TO 0.5 4,118 0 0.50" WG 120/1/60 BELT 345 FILTERED KITCHEN 6 & 7. HOOD HOOD PACKAGE MANU ER) (RO OF MOUNTED) DRAWING. VEN ILATOR ACCESSORIES: 1. PROVIDE DISCONNECT SWITCH 4. GREASE TERMINATOR 2. RCG GALVANIZED CURB 5. GREASE TROUGH 3. HINGED BASE 6. FIBERGLASS FILTER MEDIA 7. MOTORIZED INTAKE DAMPER ISSUE DATE: No. DATE 13ESCKIF'TION All ideas, designs, arrangements, plans and specifications indicated or represented by this drawing are owned by and are the property of Borges + Associates, P.A., and were created, evolved and developed for use on and in connection with the specified project. No copies, transmissions, reproductions, or electronic manipulation of any portion of these drawings in whole or in part are to be made without the express written permission of Borges + Associates, P.A. All copyrights reserved © 2005 bor es + 9 associates architecture urban - planning interior - design 200 S. Biscayne Blvd., Suite 800 ■ Miami, Florida 33131 305.374.9216 phone 305.374.9217 fax a.4W > R f. "r r.. > •> ; w a y •i ae •'41 Elizabeth T. Prida, P.E. h59464 Project Team'; r j x M.E. Engineering Consultants, Inc. Ph:(305)905-4652 CA 29121 Project Name R I C E HOUSE OF KABOB - SOUTH MIAMI 5818 SOUTH DIXIE HIGHWAY Miami, FL 33143 Project Number 130220 Drawing Name HVAC NOTES AND SCHEDULES Scale: Drawing Number AS SHOWN M-000