13-1341-021DEMAND LOAD CALCULATION 135.9 KVA - TOTAL CONNECTED LOAD PER N.E.C. 220 -13 102.7 NON KITCHEN LOADS 0 100% PER N.E.C. 220 -20 22 KITCHEN LOADS 0 65% PER N.E.C. 220 -31 0.7 25% OF CONTINUOUS LOAD PROVIDE A 120/240 3PH, 4W, 400 AMP SERVICE SHORT CIRCUIT CALCULATION AT HOUSE MAIN isco= 21,110 A (AT TRANSFORMER SECONDARY, AS PER FPL FAULT CURRENT LETTER ON THIS DRAWING) 50 FEET #500 Cu. CONDUCTORS f= 2 x L x 1 - (2)(50)(21,110) = 0.396 C x EL-L. (22,185)(240) M = 1 = 1 = 0.716 1 +f 1 +0.396 Isco = AVAILABLE FROM UTILITY x M = (21,110)(0.716) = 15,114 Amps AT MAIN FEEDERS MAIN TO BE 22K AIC MAIN TELEPHONE SERVICE AND VIDEO (CABLE, SATELLITE) TO BE CONNECTED TO DATACOMM SERVICE ENTRANCE. M DATACOMM 70 -0020 TYPICAL WALL MOUNTED TV OUTLET. COAXIAL CABLE TELEPHONE CABLE (MINIMUM CAT5) 20A, 120V DEDICATED CIRCUIT 3 #12 IN 1,/2-"C- TO L1 -29 Wa TYPICAL WALL MOUNTED TELEPHONE /DATA OUTLET. GROUND FLOOR EXTERIOR I INTERIOR 0) V) T11 EQUAL TYPE: TO: P ENENS P'' n e l 3L M41NS: 400 X40 V 3 Ph, 4 W MOUNTING: FLUSH TYPE MANS: M.L.O. LOCATION'. TENANT SPACE AIC: 22 K` CKT # DESCRIPTION POLE C.B. TMP (AMPS) WIR E CON- aulT VA A VA LOAD � VA LOAD VA LOAD VA CON- DU(r WIR E C'B. TRIP (AMPS) POLE DESCRIPTION CKT 1 1 20 #12 1;2" 1;200 1,936 2,436 1,200 1;2" 500 20 1 HCO.OT€RESU SfJN 2 3 2 3 GRINDER 3 20 #12 1/2-.1,936 3.060 1,500 2,436 #12 500 112 " #12 20 3 PAKER 4 5 912 1r2" 1,500 1,700 1,936 V2" #12 2,436 500 GAS SOLENOID VALVE 6 7 SCALE 1 6 7 V2" 1 200 2,320 1,120 2,900 5.780 20 1 2:880 1.0" #1 30 2 EXISTING R.T.U. # 2 8 9 MXER 3 30 #10 314" 2,900 20 5,780 SANDWICH STATION 2,880 11 RICROWAVE 1 20 #12 10. 11 3,720 1,500 1;2" #12 2,900 1 SNALLAPPLIANCE 128,940 26,040 2.5" #4i0 225 2 PANEL L1 12 13 EXISTING R.T.U. # 4 2 60 #10 1 314" 15,760 36,331 14 15 30,5711 1 20 #12 12" 1 14 15 1,800 1,2" #12 20 1 5,760 16 10,660 ICE NACHINE 4,900 20 #12 1.2" 1,500 3,000 16 17 HIGH LEG #12 20 1 SOUP CONTAINER 18 19 SMALLAPPLWNCE 4,900 4,900 1.0" #6 60 3 NEW R.T.U. # 1 18 19 #12 20 1 P.O.S. SYSTEM 20 2,076 6:9761 1 20 4.900 12" 700 1,900 1 1;200 20 21 COOLER 1 COND. UNIT 3 20 #12 1i2" 2,076 1 4,152 #12 2,076 1.200 3,000 1,800 14" 22 23 1 GRAS &GO 24 25 OFFICE RECEPTACLE 2:076 20 #12 4,1521 2,076 1.0" #6 20 3 COOLER 3 COND, UNIT 24 25 SOUTH SIDE SIGN #2 76 27 SOUTH SIDE SIGN # 1 1 2,768 4,844 12" 1,200 2,076 2.280 1,080 V2" #12 20 26 27 COOLER 2 COND. UNIT 3 30 #12 1/2" 12,7681 112° 3,268 920 500 112" 1 #12 20 1 1 WATER HEATER IGNITER 28 29 31 RECEPTACLES 1 #12 2,768 720 4,638 1,920 112" #12 20 2 REFRIG. VAN CHARGER 30 31 LIGHTING 1 20 #12 112" 750 2,670 1,500 1,920 #12 20 1 S%ALLAPPLIANCE 34 32 33 EXTERIOR GFI 1 20 #12 1i2" 500 1,920 1,500 112" 1,000 20 1 20 1 SPARE 34 35 HIGH LEG #12 1,2" 600 1,500 900 V2" 0 20 1 RECEPTACLES 38 39 HIGH LEG 36 37 SPARE 1 20 571 11,0001 2;000 #12 20 1,000 LIGHTING 40 20 1 SPARE 38 39 SPARE 1 20 1,632 1,000 #12 2,000 1 1.000 42 43 20 1 SPARE' 401 41 HIGH LEG 2,920 1,000 314" #10 25 1 0 44 45 EVAPORATOR COIL 1 20 HIGH LEG 42 TOTALS 61,037 29,796 45,116 CONNECTED LOAD (KVA): 135.9 DEIVIAND LOAD (KVA): 125.1 AMPSIPHASE: 305 TYPE' P2 TO: SP2rY NS Panel L f BUS: 250A40V. tf3.3Nd MOUNTINGFLUSH TYPE MN INS: DSO LOCATION: TENANT SPACE AIC: 18K CKT # DESCRIPTION POLE C.B TRIP (AMPS) WIRE CON- DUET VA 'A" VA LOAD ,,B" VA LOAD- VA CON- DUIT W,1� G.B. TIP (APAPS) POLE DESCRIPTION CKT # 1 SCALE 1 20 #12 1;2" 1;200 2;400 1,200 1;2" #12 20 1 HCO.OT€RESU SfJN 2 3 TUMBLER 1 20 #12 12" 1,560 3.060 1,500 1.2" #12 20 1 SMALLAPPLIA!4CE 4 5 SMALLAPPLWNCE 1 20- 912 1r2" 1,500 1,700 200 V2" #12 20 1 GAS SOLENOID VALVE 6 7 SCALE 1 20 #12 V2" 1 200 2,320 1,120 1a2" #12 20 1 SANDWICH STATION 8 9 FREEZER 1 20 #12 12" 1,440 2,560 1,120 1,2" #12 20 1 SANDWICH STATION 10 11 RICROWAVE 1 20 #12 1i2" 1,920 3,720 1,500 1;2" #12 20 1 SNALLAPPLIANCE 12 13 PASSTHROUGH 1 20 #12 V2" 1;440 2,940 1,500 1;2" #12 20 1 SPAALLAPPLIANCE 14 15 FOUNTAINErsNaCHINE 1 20 #12 12" 1,900 3.700 1,800 1,2" #12 20 1 COFFEEMkCHINE 16 17 ICE NACHINE 1 20 #12 1.2" 1,500 3,000 1,500 1,2" #12 20 1 SOUP CONTAINER 18 19 SMALLAPPLWNCE 1 1 20 #12 ,r2" 1 1,500 3,3001 1,200 V2" #12 20 1 P.O.S. SYSTEM 20 21 SAUCE COOLER 1 20 #12 12" 700 1,900 1 1;200 1,2" #12 20 1 P.O.S. SYSTEM 22 23 P.O.S. SYSTEM 1 20 #12 V2" 1.200 3,000 1,800 14" #12 20 1 GRAS &GO 24 25 OFFICE RECEPTACLE 1 20 #12 r;2" 360 1,560 1;200 1r2" #12 20 1 SOUTH SIDE SIGN #2 76 27 SOUTH SIDE SIGN # 1 1 20 #12 12" 1,200 2.280 1,080 V2" #12 20 1 RECEPTACLE 28 29 DATACM170 -0020 1 20 912 112° 200 920 720 1.2" #12 20 1 RECEPTACLE 30 31 RECEPTACLES 1 #12 1;2" 720 1,440 720 1r2" #12 20 1 ROOFG.F.L 32 33 RECEPTACLES 1 #12 12" 540 2,040 1,500 t2" #12 20 1 S%ALLAPPLIANCE 34 35 NORTH SIDE SIGN 1 E20 #12 1.2" 1,200 1,920 72C 112" #12 20 1 RECEPTACLES 36 37 EXTERIOR LIGHTING 1 #12 1,2" 600 1,500 900 V2" #12 20 1 RECEPTACLES 38 39 LIGHTING 1 #12 12" 133 571 438 1%2" #12 20 1 LIGHTING 40 41 EXHAUST FAN 1 1 20 912 1:2" 1,632 3,264 1,632 112" #12 20 1 EXHALI ST FAN 2 42 43 SUPPLYFAN I 1 1 25 #10 314" 1 1,9201 2,920 1,000 314" #10 25 1 AIR CURTAN 44 45 EVAPORATOR COIL 1 20 #12 12" 216 864 648 12" #12 20 1 EVAPORATOR COIL 46 47 DOOR LIGHTS:HEATER 1 20 #12 7.2" 240 480 240 t.2" #12 20 1 DOORLIGHTS:HEA€2R 48 49 COOLER LIGHTS 1 20 #12 L2" 1,176 1,392 216 1;2" #12 20 1 EVAPORATOR COIL 50 51 ISMALLAPPLIANCE 1 20 #12 12" 1,500 1.860 3601 12" 1 #12 20 1 1 DOOR LIGHTS .-HEATER 52 53 SPACE 1 0 SPACE 54 TO €AL$ 26,040 30,571 CONNECTED LOAD (KVA): 56Z DEMAND LOAD (KVA). 56.8 AMPSIPHASE 236 .(C) . Im ric ( ")- BUILDING SIGN AND EXTERIOR LIGHTS SHALL BE TURNED ON BY PHOTOCELL AND TURNED OFF.VIA TIME CLOCK. (C)- CONNECT THRU A 4 POLES MECHANICALLY HELD CONTACTOR °C" TIC- DINING AREA LIGHTING TO BE CONTROLLED BY A TIME CLOCK 02 ELECTRICAL PANEL SCHEDULES AND CALCULATIONS ..�� NEW K -7T 400A NEW OVERHEAD SERVICE, 4 -500 KCM FP &L METER CAN IN 2.5" R.G.S. CONTRACTOR SHALL INSTALLED BY COORDINATE ALL WORK WITH FPL CONCTRACTOR. 1 REPRESENTATIVE. NEW 400 AMP PANEL PANEL SERVICE ENTRANCE M MAIN BREAKER. 240 V 400A 250A 22 KAIC MLO 3 MLO 4 POLES 20A RATED MECHANICALLY HELD ELECTRICALLY OPERATED NORMALLY CLOSED CONTACTOR TO OPEN UPON HOOD FIRE SUPPRESSION SYSTEM ACTIVATE. PROVIDE WITH NEMA TYPE 1 ENCLOSURE. GROUND FLOOR G.W.P. 2 -5/8 "X 10' GND RODS MIMI #1/0 CU GND IN 3/4" C 1 - #6 CU GND IN 3/4" CONDUIT TO GAS PIPE. CLAMP PIPE ON UNPAINTED AREA WITH UL LISTED GROUND CLAMP October 24, 2013 ZIOLA MORALES, P.E. 9143 FOUNTAINEBLEAU BLVD #6 MIAMI, FL 33172 Re: Available Fault Current for RICE RESTURA.NT AT 5818 S DIXIE HWY 1 60 WA 1411NX50iANX4�."1« Thank you for contacting FPL about the available fault current at RICE RESTURANT AT 5818 S DIXIE HWY. Based on the plans you have provided dated October 24 2013, the maximum available fault current at the transformer secondary terminals is estimated to be 21110 symmetrical amperes at 120/240 volts. The protective device on the line side ofthe transformer currently in place or to be installed and serving your property located at the subject location is a 10 amp type "KS" fuse. The primary service voltage is 13.2kV L -L. This calculated symmetrical fault current is not intended for use as the basis for motor starting calculations and does not include: • Consideration for any motor contribution or • Fault current asymmetry, The FPL equipment currently serving or planned to serve your facility may change over time as a result of any number of factors, including but not limited to transformer replacements due to load growth, electrical grid changes or emergencies. As a result, although we are providing you with this information for the sole purpose of assisting you in the completion of your study, you and your client should not design, install or operate your system in reliance upon any expectation that the specific size and type of equipment currently in place will remain so. If and when the size and type of the equipment changes, our employees are not always in a position to immediately notify customers. d As the construction project progresses, any questions or information you may need can be communicated through me. I have enclosed my business card for easy reference and look I forward to hearing from you in the near future. Sincerely, Shina Rana Associate Engineer SEQUENCE OF OPERATION: ACTIVATION OF ANY AUTOMATIC OR MANUAL DEVICE OF HOOD FIRE PROTECTION SYSTEM SHALL INITIATE THE FOLLOWING FIRE EMERGENCY SEQUENCES: 1. START ALL EXHAUST FANS. 2. SHUT DOWN ALL CIRCUIT BREAKERS THAT SERVES EQUIPMENT UNDER THE HOOD. 3. SHUT DOWN GAS SOLENOID VALVE. 4. SHUT DOWN AC AIR SUPPLY FEEDER SCHEDULE 2 SETS OF 4 -3/0 1 - #3 GND THWN CU WIRE IN 2.0" C EACH. Q 2 - #12 IN 1" CONDUIT TO HOOD FIRE SUPPRESSION SYSTEM PANEL SHUT DOWN RELAY TO OPEN CONTACTOR TO DISCONNECT POWER TO CIRCUIT L1 -6. 3- #250 KCM & 1 - #4 GND THWN CU WIRE IN 2.5" C N.T.S. N.T.S. ISSUE DATE: 12.05.13 PERMIT SET No. I DATC I DESCR^ i 'TION All ideas, designs, arrangements, plans and specifications indicated or represented by this drawing are owned by and are the property of Borges +Associates, P.A., and were created, evolved and developed for use on and in connection with the specified project. No copies, transmissions, reproductions, or electronic manipulation of any portion of these drawings in whole or in part are to be made without the express written permission of Borges +Associates, PA. All copyrights reserved Q 2005 bor es + 9 associates i architecture urban - planning interior- design 200 S. Biscayne Blvd., Suite 800■ Miami, Florida 33131 305.374.9216 phone ■ 305.374.9217 fax Project Team 1 I C E HOUSE OF KABOB 5818 SOUTH Miami, Project Number 130220 Drawing Name M.E. Engineering Consultants, Inc. Ph:(305)905 -4652 CA 29121 ELECTRICAL RISERS AND PANEL SCHEDULES Scale: Drawing Number