13-1341-018* i
ISSUE DATE: 12.05.13 PERMIT SET
No. UATE (C�ESLRIt�lIUN
I Project Team
,.
M.E. Engineering Consultants, Inc.
Ph:(305)905 -4652
CA 29121
R I C E
HOUSE OF KABOB -SOUTH MIAMI
5818 SOUTH DIXIE HIGHWAY
Miami, FL 33143
Project Number 130220 1
Drawing Name
ELECTRICAL POWER PLAN
Scale: Drawing Number
AS SHOWN E-200
Kitchen
Equipment
Schedule
NOTE 1 NOTE 9
i PROVIDE POWER AND COAXIAL CABLE OUTLET FOR TV CONNECTION IF ANY ITEM REQUIRES MORE THAN ONE POINT OF CONNECTION
0 6' -0" A.F.F. COORDINATE WITH OWNER FOR EXACT LOCATION THEN IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL
AND MOUNTING HEIGHT PRIOR INSTALLATION. CONTRACTOR TO PROVIDE THESE CONNECTIONS.
NOTE 2 NOTE 10
PROVIDE DATACOMM 70 -0020. TELEPHONE AND VIDEO MODULE ELECTRICAL CONTRACTOR TO PROVIDE 3/4 "C. FROM EACH
USED TO DISTRIBUTE BOTH TELEPHONE SERVICE AND VIDEO TEL /DATA OUTLET TO DATACOM PANEL. SEE DRAWING E -300 FOR
(CABLE. SATELLITE). SEE DETAIL ON DRAWING E -300. DETAILS.
NOTE 3 NOTE 11
CONTRACTOR SHALL COORDINATE AND VERIFY MOUNTING HEIGHTS FOR FOUNTAIN MACHINE CONTRACTOR SHALL PROVIDE A DEDICATED
FOR ALL ELECTRICAL OUTLETS, JUNCTION BOXES AND DISCONNECTS GROUNDED RECEPTACLE FOR EACH DRINK DISPENSER,
WITH KITCHEN CONSULTANT EQUIPMENT SPECS PRIOR TO CARBONATOR OR AIR COMPRESSOR AS PER MANUFACTURER SPECS
ROUGH —IN. IF NEEDED.
NOTE 4 NOTE 12
ELECTRICAL CONTRACTOR SHALL VERIFY ALL REQUIREMENTS FOR CEILING MOUNTED JUNCTION BOX TO FEED COOLER LIGHTS TO BE
KITCHEN EQUIPMENT CONNECTIONS AND MATCH PLUGS AND PROVIDED BY COOLER MANUFACTURER.
RECEPTACLES AS REQUIRED BY MANUFACTURER NOTE 13
NOTE 5 PROVIDE RECEPTACLE UNDER SINK FOR NEW PLUG IN
PROVIDE GFI PROTECTION TO ALL 125 VOLT, SINGLE PHASE, 15 TRANSFORMER SENSOR MODEL SLOAN #ETF -233. INSTALL
AND 20A. RECEPTACLES IN THE KITCHEN AREA (N.E.C. 210 (B)) CONTROL MODULE AND SOLENOID VALVE AS PER SLOAN SPECS.
NOTE 6 NOTE 14
ALL DISCONNECTS FOR FANS, CONDENSING UNITS AND ALL ITEMS PROVIDE TRANSFORMER PRI120V/24V AC SLOAN 3 EL -154 CLASS
THAT REQUIRES DISCONNECTS SHALL BE PROVIDED AND INSTALLED NUMBER U.L. LISTED 50 VA TO FEED ALL SENSORS AND COILS IN
BY ELECTRICAL CONTRACTOR. BOTH BATHROOMS. CONNECT ALL SENSORS AND COILS AS PER
NOTE 7 MANUFACTURER INSTALLATION INSTRUCTIONS.
ALL SWITCHES, MOTOR STARTERS FOR EXHAUST AND MAKE —UP AIR NOTE 15
SHALL BE PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. PROVIDE LOW VOLTAGE WIRING AS PER SLOAN MANUFACTURER
NOTE 8 SPECS.
ELECTRICAL CONTRACTOR SHALL PROVIDE ALL WIRING AND CONDUIT NOTE 16
FOR CONTROLS, TIMER, SHUT OFF VALVES AND EQUIPMENT PROVIDE OPTIMA SENSOR AND COVER 4X4 AS PER MANUFACTURER
SUPPLIED BY KITCHEN CONSULTANT. REFER TO CONTROL DIAGRAMS SPECS.
AND SPECIFICATIONS FOR ALL WIRING CONNECTIONS. NOTE 17
DENOTES JUNCTION BOX MOUNTED ABOVE DOOR TO POWER AIR
CURTAIN. INSTALL HAND OFF AUTOMATED SWITCH AND LIMIT SWITCH
AS PER MANUFACTURER SPECS.
Tag #
€ter
Manufacturer
Model #
width
ILength (D)
Height
Volt,
Amp /W
JPhase
Drain
Water
Propane
Remarks
1
Grinder
Torrey
M32 -5
392/7
10 (legs)
511/4
220
14
3
Cord with 20A twislock plug.
2
Triple Sink (in w /C)
Stainless Steel
MF3- 2424 -24L€t
123
30
35
2"
3/4" Cw /Hw
1 Faucet,1Spary
3
Scale (A /B)
Torrey
EQM 200/400 -w
33
35
47
120
1
4
Packer
DMC Commercial
DZ900 -2GB
412/7
372/5
421/2
220
3
S
Mixer
Robo
RT23
263/8
235/8
::
48 1/16
220
30
3
6
Hand Sink
Advance Tabco
7- PS -EC -SP
17
151/4
13
2"
1/2 CW /HW
1 Faucet
7
Tumbler
Varivac
VV -600
59
36
60
120
13
1
8
Burner(4Top)
Garland
GTOG24 -SU4
235/8
32
1913/16
3/4"
108,000 BTU (11"WC S.O.P/10"M.O.P). Propane
inletw /regulator
9
Charbroiler (A /B)
Bakers Pride
F36GS (Stone Model)
36
331/2
42
1"
120,000 BTU (10 "M.O.P)
10
Stock Pot (A/S/C)
Imperial
ISPA -18 /NG
18
21
24
3/4"
90'000BTU(10"M.O.P)
11
Fryer
Vulcan
LG300 -1
15.1/2
301/4
363/4
11/2"
1/2"
90,000 BTU (1Y M.O.P) Propane inletw /regulator
12
Triple Sink
Stainless Steel
3F3- 2424 -24L
1001/4
130
35
2"
3/4" Cw /HW
1 Faucet, I Spary
13
Prep. Sink
Stainless Steel
3F1. 2424 -24L
582/7
30
35
11/2"
1/2 Cw /Hw'
1 Faucet
14
Freezer
Beverage Air
HF2 -1S
52
32
73
120
12
1
15
Table
T9A488027
30
72
35
16
Microwave
Amana
R S
201/4
141/4
120
16
1
17
Table
A250
T9A250 179
30
30
96
35
18
Sandwich Station
TRUE
TPP -93
931/2
321/4
353/4
120
9.3
1
19
Pass Through
Beverage Air
PRD2•IBHG -XDX/ -005
52
34
781/2
120
12
1
20
Coffee Machine
Fw -1500w
120
1800W
1
1/2 "CW
21
Soup Container
Adcraft
DC-1596
141/2
291/2
81/2
120
.12.5
1
22
Table
Aero
HR1 -1G
15
96
35
23
Sauce Cooler
Beverage Air
26
32
79
120
5.8
I
24
Cabinet
SPOD -8S /c
25
Grab & Go
Marc
96
37 -1/2
431/2
120
15
1
W/D
26
Fountain Machine
Coke (8 Dispensers)
3MP- 2116 -12
31
26
28
120
20
1
W/D
27
Ice Machine
3/4"
1/2" Cw
28 1
Mop Sink (A/8)
Aero
24
19 116
1
3
1/2 "CW HW I
Bowl 21x15x12
* i
ISSUE DATE: 12.05.13 PERMIT SET
No. UATE (C�ESLRIt�lIUN
I Project Team
,.
M.E. Engineering Consultants, Inc.
Ph:(305)905 -4652
CA 29121
R I C E
HOUSE OF KABOB -SOUTH MIAMI
5818 SOUTH DIXIE HIGHWAY
Miami, FL 33143
Project Number 130220 1
Drawing Name
ELECTRICAL POWER PLAN
Scale: Drawing Number
AS SHOWN E-200