12-732-006EQ 125/f 2
1080 sf @ 3w /5f
1080
3,240
EXISTING PANEL
VOLTAGE
120124011 PH 13W
3,000
W
MAX RATED
1 25
RECESSED, INDOOR
4,800
W
TYPE MAINS
M.L.O.
A/C PACKAGE UNIT HEATER
5,000
W
LOAD
A
B
AMPS
POLE
Wire
SUBTOTAL LOADS
Wire
POLE
AMPS
A
B
LOAD
KVA
KVA
CIRCUIT
CIRCUIT
KVA
KVA
A/C
2.50
50
100%
#6
I
2
# 1 2
2
20
_
2.40
WATER HEATER
2.50
-
2
3
4
2.40
TOTAL DEMAND LOAD
SPARE
-
15
#14
5
G
#12
1
20
-
SPARE
SPARE
1.50
20
# 12
7
8
#12
1
20
GL
LIGHTS /RECPT.
GEN LIGHTS
GL
20
# 12
9
10
# 12
1
20
GL
GFI
APPLIANCE -1
1.50
20
#12
1 1
12
# 12
1
20
GL
LIGHTS /RECPT.
LIGHTS
GL
20
# 12
13
14
# 14
20
1.58
APPLIANCE - 2
EMERGENCY LIGHTS
GL
20
# 12
15
1 G
# 12
20
GL
LIGHTS /RECPT.
51GN
20
#12
17
18
#12
20
GL
LIGHTS /RECPT.
SUBTOTAL KVA / 0
2.50
5.50
2.40
2.40
SUBTOTAL KVA / 0
SUBTOTAL '
8.00
4.80
SUBTOTAL '
GENERAL LIGHTING (GQ
3
W /5F
1080 517
3240
WATTS
PANEL SUBTOTAL
GENERAL LIGHTING
TOTAL LOAD
15T 10,000 WATT5
A/C LOAD 100%
12.80
3.24
I G.04
1 1 .04
5.00
I G.04
KVA
KVA
KVA
KVA
KVA
KVA
PANEL SUBTOTAL
GENERAL LIGHTING
TOTAL LOAD
EXISTING 125 AMP SERVICE TO REMAIN UN- CHANGED
I G.0
@
240
V/ I/ GOHZ =
G7
AMPS
EXISTING LOAD CALCULATION
1080 sf @ 3w /5f
1080
3,240
W
APPLIANCE REM. @ 1 500
2
3,000
W
WATER HEATER
4,800
W
A/C PACKAGE UNIT HEATER
5,000
W
A/C CONDENSING UNIT'
1,800
W
SUBTOTAL LOADS
1 6,040
W
FIRST 10,000 W
100%
1 1 ,040
W
AC Load
100%
5,000
W
REMAINDER @ 40%
_
W
-
240
V
TOTAL DEMAND LOAD
G7
AMP5
' NON SEQUENTIAL LOAD
LE IVE DEMO
GENERAL ELECTRICAL NOTES
I . ALL WORK REFLECTED ON THESE DOCUMENTS ARE IN COMPLIANCE WITH 201 O EDITION OF THE
"FLORIDA BUILDING CODE AND NEC 2008 (NFPA -70).
2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR AND IN A FIRST CLA55
WORKMAN LIKE MANNER.
3. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIONAL. CONTRACTOR TO PROVIDE LABOR,
MATERIALS, PERMITS, FEES, INSPECTIONS, TESTS ETC.
4. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST LIABILITY AND PROPERTY
DAMAGE FOR DURATION OF THE WORK.
5. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS
FOR A PERIOD OF NO LE55 THAN ONE YEAR FROM DATE OF FINAL INSPECTION AND BUILDING
DEPARTMENT APPROVAL. CORRECTION OF DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL
C05T TO OWNER AND INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF INSTALLATION
THAT MAY HAVE BEEN DAMAGED.
G. IT IS NOT THE INTENT OF THESE DRAWINGS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION.
THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL
SYSTEM AND PROVIDE ALL THE REQUIREMENTS NECESSARY FOR ALL THE EQUIPMENT FURNISHED
BY HIM OR OTHER TRADES TO BE PLACED IN PROPER WORKING ORDER.
7. DO NOT SCALE THE DRAWINGS. FOR CLARIFICATIONS REFER TO MANUFACTURER CUT 5HEET5 FOR
PRECISE LOCATIONS OF ELECTRICAL OUTLETS FOR UNDER CABINET MILLWORK EQUIPMENT. FOR
OTHER INQUIRIES CONTACT OWNER OR ARCHITECT.
8. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED BY
THE LATEST NEC CODE.
9. ALL 125 VOLT, 15 AND 20 AMP RECEPTACLES INSTALLED IN A RESIDENCE SHALL BE LISTED
TAMPER RESISTANT RECEPTACLES. NO EXCEPTIONS FOR RECEPTACLES ON CEILINGS, ABOVE
COUNTERS OR BEHIND APPLIANCES. NEC 40G. I I
10. PROVIDE ACCESSIBLE GFCI RECEPTACLE OUTLET WITHIN THE PERIMETER OF RESIDENTIAL
BALCONIES, DECKS, OR PORCHES LARGER THAN 20 SQUARE FEET IN AREA. THE RECEPTACLE
SHALL BE LOCATED NOT MORE THAN G V2 FEET ABOVE THE STANDING SURFACE. NEC 2 10.52 (E)
(3)
1 1 . EQUIPMENT GROUNDING CONDUCTORS ARE REQUIRED TO BE INSTALLED WITH ALL BRANCH,
CIRCUITS AND FEEDERS SUPPLYING SEPARATE BUILDINGS OR STRUCTURES. EXISTING
INSTALLATIONS ARE ALLOWED TO REMAIN GROUNDED TO THE NEUTRAL CONDUCTOR IF THERE 15
NO GROUNDING CONDUCTOR, NO CONTINUOUS METAL PATH (METAL GAS PIPE, METAL WATER PIPE,
OR METAL CONDUIT TO THE STRUCTURE) OR GROUND FAULT PROTECTED EQUIPMENT IN THE
STRUCTURE. NEC 250.32 (B)
12. WHERE HOLES ARE BORED IN JOISTS, RAFTERS OR WOOD MEMBERS FOR CABLES OR RACEWAYS,
THE EDGE OF THE HOLE MUST BE 1 I/4" FROM THE EDGE OF THE MEMBER OR IT MUST BE
PROTECTED BY NAIL PLATES WITH A MINIMUM THICKNESS OF I I/ I G INCH. NEC 300.4 (A)
13. ROMEX 15 NOT ALLOWED IN WET OR DAMP LOCATIONS. THE INSIDE OF RACEWAYS (EMT 4 PVC)
INSTALLED OUTDOORS ARE CONSIDERED WET LOCATIONS. OPEN 51DED PORCHES ARE
CONSIDERED DAMP LOCATIONS. NEC 300.9 .334.12
14. GAPS AROUND ELECTRIC PANELS, CABINETS AND CUTOUT BOXES ARE LIMITED TO 1/8 ". ALL HOLES
I I SI. -A 5 O I t 25 OR 5 0 VOLT RECEPTACLES U INSTALLED OUTDOORS OORSA N DAMP OR WET
LOCATIONS MUST BE A LISTED WEATHER - RESISTANT TYPE. NEC 406.8 (A), (B)
16. ALL BREAKERS IN PANELS MUST BE MARKED CLEARLY FOR THE LOADS SERVED. SPARE BREAKERS
MUST AL50 BE MARKED. NEC 408.4
17. LOAD DATA PROVIDED IS BASE ON INFORMATION SUPPLIED BY MANUFACTURERS OF VARIOUS
EQUIPMENT COMPONENTS. ALL EQUIPMENT AND PANEL SIZES SHALL BE VERIFIED BEFORE
ORDERING.
18. CIRCUITS SHOWN ON PLANS ARE USED TO DETERMINE LOAD DATA AND PANEL SIZE. THE
CONTRACTOR SHALL PROVIDE CIRCUIT ROUTING TO SUITE THE JOB CONDITIONS.
19. FURNISH AND INSTALL ALL FIXTURES AS CALLED FOR ON THE PLANS OR SELECTED BY
OWNER.ARCHITECT.
20. MINIMUM WIRE 51ZE SHALL BE # 14 AWG. UNLESS OTHERWISE NOTED ALL CONDUCTORS SHALL BE
COPPER WITH A THHN INSULATION FOR 51ZE #8 AND SMALLER. CONDUCTORS LARGER THAN #8
SHALL HAVE TYPE THW INSULATION. ALL CONDUCTORS # 10 AND SMALLER MAY BE SOLID AND
THOSE #8 AND LARGER SHALL BE STRANDED. ALUMINUM CONDUCTORS MAY BE ALLOWED FOR
SERVICE ENTRANCE, IF SPECIFICALLY APPROVED BY ELECTRICAL INSPECTOR.
21. ALL PRIMARY SERVICE CONDUCTORS SHALL BE RUN IN CONDUIT.
22. ALL CONDUITS SHALL BE GALVANIZED RIGID EXCEPT AS FOLLOWS:
1 .1 . CARLON PVC CONDUIT, TYPE "A" U.L. LISTED (OR EQUAL) MAY BE USED WERE INSTALLED
UNDERGROUND OUTDOORS, OR UNDER SLAB IN51DE THE BUILDING AS ALLOWED BY CODE.
THE CONDUIT FITTINGS AND CEMENT SHALL BE PRODUCED BY THE SAME MANUFACTURER.
1.2. ELECTRICAL METALLIC CONDUIT MAY BE USED INDOORS, OUT OF 501L AND WHERE NOT
SUBJECT TO PHYSICAL DAMAGE, IN INTERIOR PARTITIONS AND CEILINGS.
1.3. USE OF NON- METALIC TUBING (ENT) SHALL BE PERMITTED WHEN INSTALLED IN STRICT
ACCORDANCE WITH REQUIREMENTS OF NEC ARTICLE 362 AND TUBING SYSTEM
MANUFACTURE'S PRINTED INSTRUCTIONS.
1.4. USE OF METAL CLAD (MC) CABLE SHALL BE LIMITED TO BRANCH CIRCUIT AND BE INSTALLED IN
STRICT ACCORDANCE WITH NEC ARTICLE 330, AND CABLE SYSTEM MANUFACTURERS PRINTED
INSTRUCTIONS. EXCEPT, SHALL BE PROHIBITED FOR USE AS SERVICE CONDUCTOR.
1.5. USE OF NONMETALLIC CABLE (NM) (NMC) 4 (NM5) CABLE SHALL BE USED ONLY WHERE
SPECIFICALLY APPROVED BY OWNER 4 ARCHITECT AND ELECTRICAL INSPECTOR, AND SHALL BE
LIMITED TO BRACH CIRCUITING AND BE INSTALLED IN STRICT ACCORDANCE WITH NEC ARTICLE
33G, AND CABLE SYSTEM MANUFACTURERS PRINTED INSTRUCTIONS. EXCEPT SHALL BE
PROHIBITED FOR USE AS SERVICE CONDUCTOR.
23. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS
IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS AND
5HALLCONFORM TO NEMA STANDARDS. PLASTIC BOXES M AY BE USED WHERE PERMITTED UNDER
APPLICABLE CODES AND ORDINANCES.
24. PROVIDE UL LISTED COMBINATION SMOKE / CARBON MONOXIDE DETECTORS WITH DISTINCT
AUDIBLE ALARM AT LOCATIONS AS INDICATED ON PLANS AND TO SATISFACTION OF AUTHORITY
HAVING JURISDICTION. CONNECT SMOKE DETECTORS AHEAD OF SWITCH OF THE AFCI PROTECTED
CIRCUIT SERVING THE BEDROOMS. AT LEAST ONE LIGHT FIXTURE IN A BATHROOM OR THE KITCHEN
SHALL AL50 BE SERVED FROM THIS CIRCUIT. ALL DETECTORS THROUGHOUT THE DWELLING SHALL
BE INTERLOCKED 50 ACTIVATION OF ANY 5MOKE/CAR5ON MONOXIDE DETECTOR CAUSE
CORRESPONDING ALARM TO SOUND IN ALL DETECTORS. DEVICES SHALL BE "NIGHTHAWK MODEL
900 -01 14 /KN- CO5M -I5 AS MANUFACTURED BY "KIDDIE" OR APPROVED EQUAL WITH BATTERY
BACKUP, FLASHING LED LIGHTS, BEEP5, AND VERBAL WARNING MESSAGE.
25. QUANTITY AND LOCATION OF ELECTRICAL TELEPHONE, TV, DATA OUTLETS LIGHTS AND LIGHT
CONTROLS SHALL BE ADJUSTED TO SUIT THE OWNERS REQUIREMENTS AS PER OWNER/ARCHITECT
INSTRUCTIONS. THE SAID ARRANGEMENT SHALL NOT BE IN CONFLICT WITH APPLICABLE CODE.
2G. PROVIDE A MINIMUM OF ONE TELEPHONE, ONE DATA AND ONE TV CONNECTION IN EVERY
BEDROOM, FAMILY ROOM, OFFICE AND KITCHEN. LOCATION TO BE DETERMINED BY OWNER.
27. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY SERVICE AND LIGHTING FOR USE BY ALL
TRADES AS REQUIRED FOR CONSTRUCTION AND AUTHORITIES HAVING JURISDICTION.
FANJUL & ASSOCIATES, LLC
ARCHITECTURE, PLANNING & INTERIOR DESIGN
AA26000725
ARTURO G. FANJUL, RA
PRESIDENT
900 BAY DRIVE SUITE 208
MIAMI BEACH, FLORIDA
33141
PH. 305 726.8313
FAX 305 356.3686
arturo @fanjularchitects.com
"A BETTER LIFE THROUGH DESIGN"
ARTURO
STATE OF F
%JUL AROO 17585
REGISTERD ARCHITECT
CONSTRUCTION DOCUMENTS FOR:
LE MACARON
CAFE'
581 1 SUNSET DRIVE
SOUTH MIAMI
FOLIO: 09- 4025 -030 -0070
ELECTRICAL NOTES
REVISION INO.
DATE: 6/18/2012
SCALE: AS NOTED
DRAWN: AGF
CHECKED: AGF
JOB NO. 12 -0410
PERMIT NO.
OWNERSHIP
OF THESE DOCUMENTS & SPECIFICATIONS AS
INSTRUMENTS OF SERVICE ARE AND SHALL REMAIN
THE PROPERTY OF THE ARCHITECT WHETHER THE
PROJECTTHEY ARE MADE FOR IS EXECUTED OR NOT.
THEY SHALL NOT BE USED BY OWNER OR OTHERS ON
OTHER PROJECTS OR FOR ADDITIONS TO THIS
PROJECT BY OTHERS, EXCEPT BY AGREEMENT IN
WRITING AND WITH APPROPRIATE COMPENSATION TO
THE ARCHITECT.
E 2
IF
�..
,I
l� � J
-
%JUL AROO 17585
REGISTERD ARCHITECT
CONSTRUCTION DOCUMENTS FOR:
LE MACARON
CAFE'
581 1 SUNSET DRIVE
SOUTH MIAMI
FOLIO: 09- 4025 -030 -0070
ELECTRICAL NOTES
REVISION INO.
DATE: 6/18/2012
SCALE: AS NOTED
DRAWN: AGF
CHECKED: AGF
JOB NO. 12 -0410
PERMIT NO.
OWNERSHIP
OF THESE DOCUMENTS & SPECIFICATIONS AS
INSTRUMENTS OF SERVICE ARE AND SHALL REMAIN
THE PROPERTY OF THE ARCHITECT WHETHER THE
PROJECTTHEY ARE MADE FOR IS EXECUTED OR NOT.
THEY SHALL NOT BE USED BY OWNER OR OTHERS ON
OTHER PROJECTS OR FOR ADDITIONS TO THIS
PROJECT BY OTHERS, EXCEPT BY AGREEMENT IN
WRITING AND WITH APPROPRIATE COMPENSATION TO
THE ARCHITECT.