10-557R-001ll. GENERAL HVAC NOTES 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE HVAC SYSTEM /N ACCORDANCE WITH THESE DRAWINGS. THE FLORIDA BUILDING CODE 2007 AND THE LATEST EDITION OF THE FOLLOWING PUBLICATIONS: (A) ANS 89.1 MECHANICAL REFRIGERATION (B) NFPA PAMPHLETS 90A & 91 (C) SMACNA (D) ASHRAE. 2. ALL AIR CONDITIONING DUCTWORK SHALL BE 1 —I /2 "STANDARD DUTY FOIL REINFORCED FIBERGLASS (F 6) MANUFACTURED LOGO PRINTED ON THE VAPOR BARRIER WHEN IN UNCONDITIONED SPACE, AND 314 "STANDARD DUTY FOIL REINFORCED FIBERGLASS (R -4) MANUFACTURED LOGO PRINTED ON THE VAPOR BARRIER IN CONDITIONED SPACE OR RETURN PLENUM SPACE. 3. ALL EXHAUST DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL. 4. DUCT S IZE SHOWN ARE NET FREE AREA INSIDE. 5. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL ALUMINUM CONSTRUCTION, WITH EXPOSED SURFACE CHEMICALLY TREATED TO RECEIVE PAINT TO MATCH COLOR OR AIR GUIDE OR APPROVED EQUAL. 6. PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS. 7. THERMOSTATS SHALL BE COMBINATION COOLING / HEATING WITH SYSTEM COOL / AUTO / HEAT/ OFF AND FAN ON /AUTO SELECTOR SWITCHES. 8. .REFRIGERANT PIPING SHALL BE COPPER TYPE "L" WITH 112" ARMAFLEX. INSULATION SHALL BE PROVIDED FOR SUCTION LINES. 9. PROVIDE NEW FILTERS FOR FAN COIL BEFORE STARTING. THESE PETERS MUST ALSO BE REPLACED PRIOR TO FINAL ACCEPTANCE BY OWNER. 10. GENERAL CONTRACTOR 6 TO HIRE AN INDEPENDENT TEST AND BALANCE COMPANY WHICH SHALL PROVIDE 3 SET OF THE REPORT SIGN AND SEALED BY THE PROFESSIONAL ENGINEER FROM THE COMPANY PRIOR OF ACCEPTANCE OF WORK. 11. MECHANICAL CONTRACTOR ITS TO PROVIDE TURNING VANE AT ALL CHANGE OF DIRECTIONS OR TO PROVIDE TURNING RADIO, ALL OUTLETS SHALL HAVE EXTRACTORS OR SCUPPERS. AND SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE REGULATIONS. LEGEND j CEILING GRILLE .SEF SIZE SCHEDULE CFM DUCT i O MATCH NECK SIZE TYP. EN TEM RETURN AIR GRILL (D THERMOSTAT --- m AIR FLOW DIRECTION (.ARROWS DENOTE I WA Y. 2 WAY, ETC., SEE PLANS -,1-- RETURN OR EXHAUST, SEE PLANS. OAI. OUTSIDE AIR INTAKE OS CEILING GRILL A4J AIR, HANDLER UNIT 0i CONDENSING UNIT CR I CUBIC FEET PER MINUTE 1 ' ` DRILL BLOCKING TO FIT OUTSIDE OF REF. LINES ly ri — CAULK WATER TIGHT METAL BOOT PAINTED TO MATCH EXTERIOR FACADE (' IN REF. LINES RUN IN ATTIC t — (MIN,) SUCTION CONNECTION LIQUID CONNECTION 1 -1 /2" LONG "HE Tr, POWER r— ACTIVATED PIN INTO SLAB (TYPICAL OF 4) — 4" CONCRETE SLAB .Gtr PROVIDE 4" PVC SLEEVE FOR 1.25 TO 3 TONS & 6" PVC SLEEVE FOR 3.5 TO 5 TONS IF REF. LINES RUN UNDER SLAB CONDENSING UNIT MOUNTING DETAIL N.T.S. PROVIDE A MIN. OF 4" SPACE OF AHU SIDE TO ASSURE ADEQUATE ACCESS FOR CONSTRUCTION & CLEANING COIL/HEAT SECTION FAN SECTION FILTER ACCESS NO COMBUSTIBLE MATERIALS ALLOWED IN PLENUM ATTIC SPACE SUPPLY AIR DUCT DISCHARGE\SALL BE MECHANICAL ATTACHED TO AHU CEILING WALLS REF. UN ES PROVI CAP —OFF W/ /— 114" PE FORATED FOR VENT I2" MIN.' PROVIDE E. . TRAP FLOW SWITCH ON SECONDARY C.D. DRAIN TO cJ SHUT DOWI I THE UNIT IN CASE OF OVER FO PREFAB M L. FRAME F.F. A.H.0 - 1 CLOSET INSTALLATION N.T.S. UNIT MUST BE INSTALLED TO 1 , WITHSTAND 150 MPH I� "101 R4� HURRICANE FORCE WINDS NL� & PROVIDE 1'7(1 /8"STRAP CALL TIE DOWN TO UNIT CONDENSING UNIT 4" THICK CONCRETE BASE —/ NOTE: PROVIDE ANCHOR BOLT WITH A MINIMUM OF 500 POUND PULL —OUT RESISTANCE. SHALL SECURE THE AIR CONDITIONING CONNSER UNIT FROM WITHIN THE UNIT TO THE CONCRETE SLAB ON WHICH THE UNIT RESTS FOR THEFT PREVENTION. POWER & CONTROL LOCATION 1 MINA LIQUID LINE W/O INSULATION SUC71ON LINE W/ 1 12"ARMAFLEX INSULAITON & VAPOR BARRIER NOTE: UNITS SHALL BE CLEAR BY 3" MIN. FROM DRIP LINE. CU MOUNTING DETAIL • N.T.S. 314" DEEP x 1 /8" POWERED ACTUATED PINS FLEX DUCT UP TO 29 "WITH OR1G" DEEP 1- 1 /2"WIDEx26 GA STRAP @ B" O/C PINS I I rl DUCT HANG DETAIL N.T.S. 3/+" CD. TO DISCHARGE 6 "A.F.G OUTSIDE TYP U.O.N.- 12" FROM STRUCTURE. (TYPICAL) RIGID DUCT UP TO 29" WITH OR 16" DEEP 26 GA G.M. STRIP AT SUPPORT FAN-COIL DESIGNATION CFM MB EN TEM ELECTRICAL DATA MANUFAC. MODEL OBS TOTAL ISENSIBLE1 PHASES INSULA TED SUCTION LINE I DB VOLTS (NO JOINTS ALLOWED] -A ZE+ •, � , }� _:all: ;ik' -� .' 'j t;,r�II ---• �;_- SEE FLOOR PLAN COND. Ti.1 FOR PIPE SIZES 19.6 1 14.8 LIilUIDUNE 1 75 240 1 1 5.0 (NO JO;NTSALLOWED) 1 20 RHEEM SUCTION CONNECTION LIQUID CONNECTION 1 -1 /2" LONG "HE Tr, POWER r— ACTIVATED PIN INTO SLAB (TYPICAL OF 4) — 4" CONCRETE SLAB .Gtr PROVIDE 4" PVC SLEEVE FOR 1.25 TO 3 TONS & 6" PVC SLEEVE FOR 3.5 TO 5 TONS IF REF. LINES RUN UNDER SLAB CONDENSING UNIT MOUNTING DETAIL N.T.S. PROVIDE A MIN. OF 4" SPACE OF AHU SIDE TO ASSURE ADEQUATE ACCESS FOR CONSTRUCTION & CLEANING COIL/HEAT SECTION FAN SECTION FILTER ACCESS NO COMBUSTIBLE MATERIALS ALLOWED IN PLENUM ATTIC SPACE SUPPLY AIR DUCT DISCHARGE\SALL BE MECHANICAL ATTACHED TO AHU CEILING WALLS REF. UN ES PROVI CAP —OFF W/ /— 114" PE FORATED FOR VENT I2" MIN.' PROVIDE E. . TRAP FLOW SWITCH ON SECONDARY C.D. DRAIN TO cJ SHUT DOWI I THE UNIT IN CASE OF OVER FO PREFAB M L. FRAME F.F. A.H.0 - 1 CLOSET INSTALLATION N.T.S. UNIT MUST BE INSTALLED TO 1 , WITHSTAND 150 MPH I� "101 R4� HURRICANE FORCE WINDS NL� & PROVIDE 1'7(1 /8"STRAP CALL TIE DOWN TO UNIT CONDENSING UNIT 4" THICK CONCRETE BASE —/ NOTE: PROVIDE ANCHOR BOLT WITH A MINIMUM OF 500 POUND PULL —OUT RESISTANCE. SHALL SECURE THE AIR CONDITIONING CONNSER UNIT FROM WITHIN THE UNIT TO THE CONCRETE SLAB ON WHICH THE UNIT RESTS FOR THEFT PREVENTION. POWER & CONTROL LOCATION 1 MINA LIQUID LINE W/O INSULATION SUC71ON LINE W/ 1 12"ARMAFLEX INSULAITON & VAPOR BARRIER NOTE: UNITS SHALL BE CLEAR BY 3" MIN. FROM DRIP LINE. CU MOUNTING DETAIL • N.T.S. 314" DEEP x 1 /8" POWERED ACTUATED PINS FLEX DUCT UP TO 29 "WITH OR1G" DEEP 1- 1 /2"WIDEx26 GA STRAP @ B" O/C PINS I I rl DUCT HANG DETAIL N.T.S. 3/+" CD. TO DISCHARGE 6 "A.F.G OUTSIDE TYP U.O.N.- 12" FROM STRUCTURE. (TYPICAL) RIGID DUCT UP TO 29" WITH OR 16" DEEP 26 GA G.M. STRIP AT SUPPORT FAN-COIL DESIGNATION CFM MB EN TEM ELECTRICAL DATA MANUFAC. MODEL OBS TOTAL ISENSIBLE1 PHASES WB I DB VOLTS I PHASES HMG KW ZE+ FUSES LIQ. SUC. COND. AHU -3 600 19.6 1 14.8 1 67 1 75 240 1 1 5.0 1 12.5 1 20 RHEEM RHLLHM2417JA 318" 314" 314" + LOAD AT 125% AS PER MANUFACTER SPECS. CONDENSING UNIT DESIGNATION MBTUH TEMP' ENT. CONDENSER ELECTRICAL DATA MANUFAC. MODEL OBS OR SEER AREA SERVED VOLTS PHASES WIREAMP FUSES CU -3 19.6 95 240 I 1 15 T20 RHEEM 13AJM 18A01 14.5 SHOWN FLOOR ME PERFORATED VENT CAP. ZE Z4 SLOPE 1/8 "/R RTU UNIT *:::q I - UNION 2" MIN. FOR 2 -112 TONS OR LESS, 3"MIN. FOR 3 TONS OR MORE. CONDENSATE TRAP DETAIL N.T.S. L� E IJ AX ,LII1111(11�\\ , j 1 _- ----- _ _ _ _ _ REVISION cl l"qq I r _ I II j II 'I I I. IT � i Z v I 1 � .r i i I i i I GRASS EARTH �1 IV 3/4 „ WASHED ROCK BED ,,v 2 -- CD PIPE t "MIN. I _ 2'-0"MIN. —• -- -ire TYPICAL CONDENSATE FRENCH DRAIN DETAIL N.T.S. I HVAC C>ESIGfV REG?UIRE: YES NO DUCT SMOKE DETECTOR X FIRE DAMPERS) X SMOKE DAMPERS _ X FIRE RATE ENCLOSURE X FIRE RATED ROOF /FLOOR CEILING ASSEMBLY X FIRE STOPPING X SMOKE CONTROL X THERMOSTAT (PROGRAMMABLE) X zu s ` z_,, 6u Z, -� 14650 S.W. 26 ST SUITE #21 2 •x; MIAMI. FLA. _ ;3 33175 OFFICE a (305) 552 -853B FAX 4� (305) 552 -8462 a: I;3 E-MAIL CMB @CMBENG.COM L.C. uNo. 2B544 4... EDMUNDO LAR13AESPADA MECHANICAL ENGINEER P.E. NO. 0056915 PROJECT. 10 0027 ;. NUMBER' Brf DESIGN CONSULTANT GROUP OF SOUTH FLORIDA II M.J.CHIU ARCHITECT SILVIO VAZQUEZ DESIGNER 219 ALMAUSPA CFCLP BUTS 406 OCRAL GABLEB FL. 33134 TEL 305-447-W FAX 306-447 -11036 AA0002500 0 al e� 0 M M M Q h Cj O a � Opp w O tO v 7 Y v f Y Y • l • Y , rl . 11. �r a 11 • A DATE 06 -07 -10 SCALE A5 SHOWW DRAWN OMB JOB 1014 ti