GENERAL HVAC NOTES
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL AND EQUIPMENT
FOR A COMPLETE HVAC SYSTEM /N ACCORDANCE WITH THESE DRAWINGS.
THE FLORIDA BUILDING CODE 2007 AND THE LATEST EDITION OF THE
FOLLOWING PUBLICATIONS:
(A) ANS 89.1 MECHANICAL REFRIGERATION (B) NFPA PAMPHLETS 90A & 91
(C) SMACNA (D) ASHRAE.
2. ALL AIR CONDITIONING DUCTWORK SHALL BE 1 —I /2 "STANDARD DUTY
FOIL REINFORCED FIBERGLASS (F 6) MANUFACTURED LOGO PRINTED ON THE
VAPOR BARRIER WHEN IN UNCONDITIONED SPACE, AND 314 "STANDARD DUTY
FOIL REINFORCED FIBERGLASS (R -4) MANUFACTURED LOGO PRINTED ON THE
VAPOR BARRIER IN CONDITIONED SPACE OR RETURN PLENUM SPACE.
3. ALL EXHAUST DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL.
4. DUCT S IZE SHOWN ARE NET FREE AREA INSIDE.
5. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL
ALUMINUM CONSTRUCTION, WITH EXPOSED SURFACE CHEMICALLY TREATED TO
RECEIVE PAINT TO MATCH COLOR OR AIR GUIDE OR APPROVED EQUAL.
6. PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS.
7. THERMOSTATS SHALL BE COMBINATION COOLING / HEATING WITH SYSTEM
COOL / AUTO / HEAT/ OFF AND FAN ON /AUTO SELECTOR SWITCHES.
8. .REFRIGERANT PIPING SHALL BE COPPER TYPE "L" WITH 112" ARMAFLEX.
INSULATION SHALL BE PROVIDED FOR SUCTION LINES.
9. PROVIDE NEW FILTERS FOR FAN COIL BEFORE STARTING. THESE
PETERS MUST ALSO BE REPLACED PRIOR TO FINAL ACCEPTANCE BY OWNER.
10. GENERAL CONTRACTOR 6 TO HIRE AN INDEPENDENT TEST AND BALANCE
COMPANY WHICH SHALL PROVIDE 3 SET OF THE REPORT SIGN AND SEALED
BY THE PROFESSIONAL ENGINEER FROM THE COMPANY PRIOR OF ACCEPTANCE
OF WORK.
11. MECHANICAL CONTRACTOR ITS TO PROVIDE TURNING VANE AT ALL CHANGE OF DIRECTIONS
OR TO PROVIDE TURNING RADIO, ALL OUTLETS SHALL HAVE EXTRACTORS OR SCUPPERS.
AND SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE REGULATIONS.
LEGEND
j
CEILING GRILLE .SEF SIZE SCHEDULE
CFM
DUCT i O MATCH NECK SIZE TYP.
EN TEM
RETURN AIR GRILL
(D
THERMOSTAT
--- m
AIR FLOW DIRECTION (.ARROWS DENOTE
I WA Y. 2 WAY, ETC., SEE PLANS
-,1--
RETURN OR EXHAUST, SEE PLANS.
OAI.
OUTSIDE AIR INTAKE
OS
CEILING GRILL
A4J
AIR, HANDLER UNIT
0i
CONDENSING UNIT
CR I
CUBIC FEET PER MINUTE
1 ' ` DRILL BLOCKING TO FIT
OUTSIDE OF REF. LINES
ly ri — CAULK WATER TIGHT
METAL BOOT PAINTED TO
MATCH EXTERIOR FACADE
('
IN REF. LINES RUN IN ATTIC
t
—
(MIN,)
SUCTION CONNECTION
LIQUID CONNECTION
1 -1 /2" LONG "HE Tr, POWER
r— ACTIVATED PIN INTO SLAB
(TYPICAL OF 4)
— 4" CONCRETE SLAB
.Gtr
PROVIDE 4" PVC SLEEVE FOR 1.25 TO
3 TONS & 6" PVC SLEEVE FOR 3.5 TO
5 TONS IF REF. LINES RUN UNDER SLAB
CONDENSING UNIT MOUNTING DETAIL
N.T.S.
PROVIDE A MIN. OF 4" SPACE
OF AHU SIDE TO ASSURE
ADEQUATE ACCESS FOR
CONSTRUCTION & CLEANING
COIL/HEAT SECTION
FAN SECTION
FILTER ACCESS
NO COMBUSTIBLE MATERIALS
ALLOWED IN PLENUM
ATTIC
SPACE
SUPPLY
AIR DUCT
DISCHARGE\SALL BE
MECHANICAL ATTACHED
TO AHU
CEILING
WALLS
REF. UN ES
PROVI CAP —OFF W/
/—
114" PE FORATED FOR VENT
I2" MIN.'
PROVIDE E. . TRAP FLOW SWITCH
ON SECONDARY C.D. DRAIN TO
cJ SHUT DOWI I THE UNIT IN CASE OF
OVER FO
PREFAB M L. FRAME
F.F.
A.H.0 - 1 CLOSET INSTALLATION
N.T.S.
UNIT MUST BE INSTALLED TO 1 ,
WITHSTAND 150 MPH I� "101
R4�
HURRICANE FORCE WINDS NL�
& PROVIDE 1'7(1 /8"STRAP CALL
TIE DOWN TO UNIT
CONDENSING UNIT
4" THICK CONCRETE BASE —/
NOTE:
PROVIDE ANCHOR BOLT WITH A MINIMUM OF 500 POUND
PULL —OUT RESISTANCE. SHALL SECURE THE AIR CONDITIONING
CONNSER UNIT FROM WITHIN THE UNIT TO THE CONCRETE SLAB
ON WHICH THE UNIT RESTS FOR THEFT PREVENTION.
POWER & CONTROL
LOCATION
1
MINA
LIQUID LINE W/O
INSULATION
SUC71ON LINE W/ 1 12"ARMAFLEX
INSULAITON & VAPOR BARRIER
NOTE:
UNITS SHALL BE CLEAR BY 3"
MIN. FROM DRIP LINE.
CU MOUNTING DETAIL
• N.T.S.
314" DEEP x 1 /8" POWERED
ACTUATED PINS
FLEX DUCT UP TO 29
"WITH OR1G" DEEP
1- 1 /2"WIDEx26 GA
STRAP @ B" O/C PINS
I I
rl
DUCT HANG DETAIL
N.T.S.
3/+" CD. TO DISCHARGE
6 "A.F.G OUTSIDE TYP U.O.N.-
12" FROM STRUCTURE. (TYPICAL)
RIGID DUCT UP TO
29" WITH OR 16" DEEP
26 GA
G.M. STRIP AT SUPPORT
FAN-COIL
DESIGNATION
CFM
MB
EN TEM
ELECTRICAL DATA
MANUFAC.
MODEL
OBS
TOTAL ISENSIBLE1
PHASES
INSULA TED SUCTION LINE
I DB
VOLTS
(NO JOINTS ALLOWED]
-A
ZE+
•,
� , }� _:all: ;ik' -� .' 'j t;,r�II ---• �;_-
SEE FLOOR PLAN
COND.
Ti.1
FOR PIPE SIZES
19.6
1 14.8
LIilUIDUNE
1 75
240
1 1
5.0
(NO JO;NTSALLOWED)
1 20
RHEEM
SUCTION CONNECTION
LIQUID CONNECTION
1 -1 /2" LONG "HE Tr, POWER
r— ACTIVATED PIN INTO SLAB
(TYPICAL OF 4)
— 4" CONCRETE SLAB
.Gtr
PROVIDE 4" PVC SLEEVE FOR 1.25 TO
3 TONS & 6" PVC SLEEVE FOR 3.5 TO
5 TONS IF REF. LINES RUN UNDER SLAB
CONDENSING UNIT MOUNTING DETAIL
N.T.S.
PROVIDE A MIN. OF 4" SPACE
OF AHU SIDE TO ASSURE
ADEQUATE ACCESS FOR
CONSTRUCTION & CLEANING
COIL/HEAT SECTION
FAN SECTION
FILTER ACCESS
NO COMBUSTIBLE MATERIALS
ALLOWED IN PLENUM
ATTIC
SPACE
SUPPLY
AIR DUCT
DISCHARGE\SALL BE
MECHANICAL ATTACHED
TO AHU
CEILING
WALLS
REF. UN ES
PROVI CAP —OFF W/
/—
114" PE FORATED FOR VENT
I2" MIN.'
PROVIDE E. . TRAP FLOW SWITCH
ON SECONDARY C.D. DRAIN TO
cJ SHUT DOWI I THE UNIT IN CASE OF
OVER FO
PREFAB M L. FRAME
F.F.
A.H.0 - 1 CLOSET INSTALLATION
N.T.S.
UNIT MUST BE INSTALLED TO 1 ,
WITHSTAND 150 MPH I� "101
R4�
HURRICANE FORCE WINDS NL�
& PROVIDE 1'7(1 /8"STRAP CALL
TIE DOWN TO UNIT
CONDENSING UNIT
4" THICK CONCRETE BASE —/
NOTE:
PROVIDE ANCHOR BOLT WITH A MINIMUM OF 500 POUND
PULL —OUT RESISTANCE. SHALL SECURE THE AIR CONDITIONING
CONNSER UNIT FROM WITHIN THE UNIT TO THE CONCRETE SLAB
ON WHICH THE UNIT RESTS FOR THEFT PREVENTION.
POWER & CONTROL
LOCATION
1
MINA
LIQUID LINE W/O
INSULATION
SUC71ON LINE W/ 1 12"ARMAFLEX
INSULAITON & VAPOR BARRIER
NOTE:
UNITS SHALL BE CLEAR BY 3"
MIN. FROM DRIP LINE.
CU MOUNTING DETAIL
• N.T.S.
314" DEEP x 1 /8" POWERED
ACTUATED PINS
FLEX DUCT UP TO 29
"WITH OR1G" DEEP
1- 1 /2"WIDEx26 GA
STRAP @ B" O/C PINS
I I
rl
DUCT HANG DETAIL
N.T.S.
3/+" CD. TO DISCHARGE
6 "A.F.G OUTSIDE TYP U.O.N.-
12" FROM STRUCTURE. (TYPICAL)
RIGID DUCT UP TO
29" WITH OR 16" DEEP
26 GA
G.M. STRIP AT SUPPORT
FAN-COIL
DESIGNATION
CFM
MB
EN TEM
ELECTRICAL DATA
MANUFAC.
MODEL
OBS
TOTAL ISENSIBLE1
PHASES
WB
I DB
VOLTS
I PHASES
HMG KW
ZE+
FUSES
LIQ.
SUC.
COND.
AHU -3
600
19.6
1 14.8
1 67
1 75
240
1 1
5.0
1 12.5
1 20
RHEEM
RHLLHM2417JA
318"
314"
314"
+ LOAD AT 125% AS PER MANUFACTER SPECS.
CONDENSING UNIT
DESIGNATION
MBTUH
TEMP' ENT.
CONDENSER
ELECTRICAL DATA
MANUFAC.
MODEL
OBS OR SEER
AREA SERVED
VOLTS
PHASES
WIREAMP
FUSES
CU -3
19.6
95
240
I 1
15
T20
RHEEM
13AJM 18A01
14.5
SHOWN
FLOOR ME
PERFORATED
VENT CAP.
ZE
Z4
SLOPE 1/8 "/R RTU UNIT
*:::q
I -
UNION
2" MIN. FOR 2 -112 TONS
OR LESS, 3"MIN. FOR 3
TONS OR MORE.
CONDENSATE TRAP DETAIL
N.T.S.
L�
E
IJ AX
,LII1111(11�\\ ,
j
1
_- -----
_ _ _ _ _ REVISION
cl l"qq
I
r
_ I
II j II 'I
I I.
IT �
i
Z
v I
1 �
.r
i
i
I
i
i
I
GRASS EARTH
�1 IV 3/4 „ WASHED
ROCK BED
,,v 2
-- CD PIPE t
"MIN.
I _ 2'-0"MIN. —• -- -ire
TYPICAL CONDENSATE
FRENCH DRAIN DETAIL
N.T.S.
I
HVAC C>ESIGfV REG?UIRE:
YES
NO
DUCT SMOKE DETECTOR
X
FIRE DAMPERS)
X
SMOKE DAMPERS
_
X
FIRE RATE ENCLOSURE
X
FIRE RATED ROOF /FLOOR CEILING ASSEMBLY
X
FIRE STOPPING
X
SMOKE CONTROL
X
THERMOSTAT (PROGRAMMABLE)
X
zu
s ` z_,,
6u
Z,
-� 14650 S.W. 26 ST
SUITE #21 2
•x; MIAMI. FLA.
_ ;3 33175
OFFICE
a (305) 552 -853B
FAX
4� (305) 552 -8462
a:
I;3 E-MAIL
CMB @CMBENG.COM
L.C. uNo. 2B544
4...
EDMUNDO LAR13AESPADA
MECHANICAL ENGINEER
P.E. NO. 0056915
PROJECT. 10 0027
;. NUMBER'
Brf
DESIGN CONSULTANT GROUP
OF SOUTH FLORIDA II
M.J.CHIU
ARCHITECT
SILVIO VAZQUEZ
DESIGNER
219 ALMAUSPA CFCLP
BUTS 406
OCRAL GABLEB
FL. 33134
TEL 305-447-W
FAX 306-447 -11036
AA0002500
0
al
e�
0
M
M
M
Q
h
Cj O
a �
Opp w
O
tO
v 7
Y
v
f
Y
Y
•
l •
Y ,
rl
. 11.
�r
a
11
•
A
DATE 06 -07 -10
SCALE A5 SHOWW
DRAWN OMB
JOB 1014
ti