10-557-0121. ALL WORK SHALL BE DONE IN ACCORDANCE WITH NFPA 70 (NEC 2008) AND FBC 2008. 2 PROVIDEALL REQUIRED CONNECTIONS FOR OTHER TRADES, INCLUDING TEMPORARY POWER. 3. OBTAIN ALL PERMITS FOR WORK UNDER THIS CONTRACT. 4. CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS, WHEN APPLICABLE. 5. ALL EQUIPMENT HAS BEEN RATED AS INDICATED IN PANEL SCHEDULE. ELECTRICAL CONTRACTOR TO BE RESPONSIBLE TO NOTIFY THE ELECTRICAL ENGINEER IF ANY CHANGE IN MANUFACTURER SPECIFICATIONS PRIOR ORDERING. 6. ALL OUTLETS MOUNTED ON COMMON WALL BETWEEN ROOMS SHALL NOT BE MOUNTED BACK TO BACK. THEY SHALL BE STAGGERED TO PREVENT SOUND TRANSMISSION AND FIRE PROTECTION. 7. THERMOSTAT WIRING SHALL BE DONE BY ELECTRICAL CONTRACTOR PER DIAGRAMS BY UNIT MANUFACTURER. SEE MECHANICAL DRAWINGS FOR EXACT LOCATION. 8. ALL BATHROOMS, GARAGES, OUTDOOR LOCATIONS, KITCHEN AND WET BARS RECEPTACLES SHALL BE PROTECTED BY GFCI (NEC 210.8(A)). 9. RECEPTACLES AND ELECTRIC BOXES INSTALLED OUTDOORS TO BE WEATHERPROOF PROTECTED (NEC 406.8) AND G.F.I. PROTECTION. 10. ALL WIRING SHALL BE COPPER THHWITHWNITHW EXCEPT OTHERWISE HAS NOTED. OTHER TYPES MAY BE USED IF ACCEPTED BY CODE. 11, NO RECEPTACLES SHALL BE LOCATED ABOVE KITCHEN SINK. RECEPTACLES IN TOP OF KITCHEN OR BAR COUNTER SHALL BE PROVIDED WITH GFCI PROTECTION. 12 ALL DUPLEX RECEPTACLES SHALL BE 120V- 15/20A -2P -3W GROUNDED, TAMPER PROOF COVER, GROUND PRONG UP ,STANDARD GRADE, COLOR CODING. RECEPTACLES SHALL BE MANUFACTURED BY SLATE DECORATOR SERIES OF COLOR SELECTED BY ARCHITECT, EXCEPT OTHERWISE HAS NOTED. EXISTING 13. ALL CONDUITS SHALL BE CONCEALED IN CEILING, WALL OR FLOOR. 14. ALL RECEPTACLES SHALL BE WIRED IN ACCORDANCE WITH NEC TO ENSURE CORRECT POLARITY. 15, PROVIDE FIRE STOPS IFALL ELECTRICAL CONDUITS CROSSING FIRE RATED CEILING AND /OR WALLS. CONSULT WITH ARCHITECT BEFORE PROCEEDING WITH ANY PENETRATION THROUGH WALL AND CEILING. 16. ALL DUPLEX RECEPTACLES SHALL BE INSTALLED IN VERTICAL POSITION AT + 18"AFF MINIMUM UNLESS OTHERWISE NOTED. 17. ALL CIRCUIT BREAKERS IN ALL PANELS, DISTRIBUTION PANELS, ETC., MUST BE CLEARLY IDENTIFIED ON DOOR SCHEDULE OR WITH PLASTIC STRIPS AFFIXED PERMANENTLY TO PANEL DOOR. ALL PANELS, D.P., ETC. MUSTBESTENCILED ON THE OUTSIDE DOOR OR TO HAVER PLASTIC LABEL SHOWING NAME OF PANEL, VOLTAGE, AND PHASE AS SHOWN ON THIS SET OF PLANS. 18. ALL CB FOR HVAC AND REFRIGERATION SYSTEMS SHALL BE HACR LISTED (NEC 440.21), 19. PROVIDE EMPTY CONDUITS WITH PULL WIRE FOR TELEPHONE, DATA /COMM.. CABLING AND CATV SYSTEMS AS REQUIRED BY UTILITY Co. 20. ELECTRIC RANGE RECEPTACLE TO BE I201240V­50A-3P­4W GROUNDED, FLUSH MOUNTED AND +20" MAX.. AFF. 21. ELECTRIC DRYER RECEPTACLE TO BE 120/240V- 30A -3P-4W GROUNDED, FLUSH MOUNTED AND +44" MAX.. AFF. 22. ALL SMOKE DETECTOR WITH BATTERY BACK-UP AND BUILT-IN BUZZER (120V, 85 dB @ 10') TO COMPLY WITH F.B.C., NFPA 101 AND NFPA 72. MULTIPLE DETECTORS TO SOUND SIMULTANEOUSLY DURING ALARM. 23. ALL SMOKE DETECTOR TO BE CONNECTED TO LIGHTING CIRCUITS AT THE SAME CIRCUIT HOT ALL TIME AND TO BE AFCI PROTECTED. 24. ALL BRANCH CIRCUITS THAT SUPPLY 120Y, 15120A OUTLETS INSTALLED IN BEDROOMS SHALL BE PROTECTED BYANAFCI (NEC 210.12(8)). TYPE: LOAD CENTER SERVICE. SHOWN VOLTAGE: 1201240V, IPH, 3W MOUNTING: FLUSH PANEL B MAIN BUS: NEUTRAL: MAIN: AICS. 125 150 MCB 10,000 SERVICE existing CL IS -1� C) z 1-11, Uj LU 95 _N REMARKS z U 2,350 z u REMARKS uj _uNj UNI 3,603 GENERAL LIGHTING AT 3 W.S.F 7,050 3,759 0 01 01 10,809 SMALL APPLIANCES CIRCUITS, SPACE I 2 SPACE 01 3 SMALL APPLIANCES LOAD 4,500 0 0 - 0 RANGE / OVEN OR COOK TOP 8,000 0 SPACE 3 4 SPACE DOUBLE OVEN 8,000 0 0 0 8,000 20 1 520 112 12 GATE MOTOR (E) 5 6 AHU-2 10 112 0 3575 2 20 - 15 1 0 112 12 GENERAL LIGHTING (E) 7 - 8 0 15 1 1,500 112 12 GENERAL LIGHTING (E) 9 10 CU-2 10 112 a 2250 2 20 0 15 1 1,5010, 112 12 GENERAL LIGHTING (E) - 11 - 12 15 1 0 112 12 GENERAL LIGHTING 13 14 OH DOOR 12 112 0 720 1 20 -1 15 1 0 112 12 GENERAL LIGHTING 15 16 SPACE - - 0 - - 0 -A k--- 15 1 0 112 12 GENERAL LIGHTING 17 18 SPACE 0 OTHER LOAD 120V 1,000 0 0 0 15 1 OTHER LOAD 240V 112 12 GENERAL LIGHTING 19 20 SPACE CONNEG&D LOAD WITHOUT A/C LOAD 45,400 5,259 0 0 0 ---AV FIRST 10000 AT 1007 10,000 5,259 - 0 SPACE 21 22 SPACE 0 0 0 16,264. A/C LOAD AS PER NEC 220.83 (C) AI­­ 5,575 0 0 0 10,968 SPACE 1231-1--41VI 24, SPACE 0 0 37,232 AT 240 VOLT 123 4511 0 0 0 CONNECTED LOAD: SEE LOAD CALCULATION SO-FT OF CONDITION SPACE (3 VAISQ.FT.) AS PER NEC 220-3 (a) FEEDER: SEE RISER FED FROM: SEE RISER LOAD CALCULATION PNE"A". PNL"B" SERVICE existing added SQUARE FEET OF CONDITION SPACE 2,350 1,253 0 0 0 3,603 GENERAL LIGHTING AT 3 W.S.F 7,050 3,759 0 01 01 10,809 SMALL APPLIANCES CIRCUITS, 31 0 0 0 01 3 SMALL APPLIANCES LOAD 4,500 0 0 0 0 RANGE / OVEN OR COOK TOP 8,000 0 0 0 0 8,000 DOUBLE OVEN 8,000 0 0 0 8,000 DRYER 5,000 0 0 0- 0 5,000 HOT WATER HEATER 4,500 0 0 0 0 4,00 SPRINKLER PUMP 7,500 0 0 0 01 i'sw POOL EQUIPMENT 1,500 0 0 0 Q 1,500 SPA EQUIPMENT 0 0 0 0 0 0 OTHER LIGHTING a 0 0 0 0 0 LAUNDRY RECEPTACLE 1,5010, 1,500, 0 01 .0 3,000 REFRIGERATOR 1,000 0 0 01 1,000 DISHWASHER 7,200 01 0 0 01 1,200 DISPOSAL 01 0 0 01 650 CEILING FANS -0 0 GARAGE DOOR OPENER & GATE MOTOR 0 0 0 0 0 0 WHIRPOOL 0 0 0 -0 0 OTHER LOAD 120V 1,000 0 0 0 0 1,000 OTHER LOAD 240V 0 0 0 CONNEG&D LOAD WITHOUT A/C LOAD 45,400 5,259 0 0 0 50,659 FIRST 10000 AT 1007 10,000 5,259 0 0 0 10,000 REST AT4D% 14,160 0 0 0 16,264. A/C LOAD AS PER NEC 220.83 (C) 5,393 5,575 0 0 0 10,968 TOTAL 29,553 10,834 0 0 0 37,232 AT 240 VOLT 123 4511 0 0 0 iss NEUTRAL LOAD CALCULATION GENERAL LIGHT, WASHER AND SMALL APP. 13,050 5,259 ! 0 ! 0 0 18,309 FIRST 3000 AT 100% 3,000 3,000 0 0 0 3,000 REST AT 357o 3,518 791 0 0 0 5,358_ RANGE AT 707 51600 0 0 0 0 5,600 DOUBLE OVEN AT 707o 5,600 0 0 0 0 5,600 DRYER AT 707 3,5010 0 0 0 0 3,500 OTHER LOAD 3,850 0 0 0 0 3,850 TOTAL NEUTRAL LOAD 25,068 3,791 0 0 0 26,908 AT 240 VOLT 104 16 0 0 0 172 SERVICE SHALL BE: NC NEMA 3R 250 AMP RAIWC,, 22 KAIC RATING 2# 310 CU THWN 1# 1/0 CU THWN IN 2" DOWN PIPE TO FPL X FORMER 150 Al2P EXISTING 15OAl2P m CB MLO PANEL 'A" TO REMAIN NO CHARGE L - - -J MC183 I Al2P EXIS71NG 3# 1 CU THWN IN I j" EMT CONDUff TO BE REUSED EXISTING ISXIING , ANELB" RELOCATED ,410 CW PIPE I TO FOUNDATION STEEL BAR AS PER NEC 250.52 (A) 7 FLOOR ELECTRICAL PLAN SCALE: 114" = 1 I -011 t L,vo FY_ R S (3. -z e!2 awe V DESIGN CONSULTANT GROUP OF SOUTH FLORIDA 11 'IF M.J.CHIU ARCHITECT SILVIO VAZQUEZ DESIGNER 290 AU4ALMA CFICLIE SUITE 4w CORAL CABLES FL. 3M TEL 305-447-9" FAX 305-447-M LICENM Na AA00025DO 4 dill 0 1 'LN 14 0 ro-7-mo-1 a MAYM CM5 JOB.. SHEET 14B50 S.W. 26 ST SUITE: #21 2 MIAMI, FLA. 33175 OFFICE (305) 552-B53B FAX (305) 552-8452 E-MAIL "t CMB@?CMEIE:NG.COM .C. NO. 28544 JOSE MORAGAS ELECTRICAL ENGINEER w a _F P.E No. 0015115 *200 ­;�J R EC T NUMBER: 1 0002.7