1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL AND EQUIPMENT
FOR A COMPLETE HVAC SYSTEM IN ACCORDANCE WITH THESE DRAWINGS.
THE FLORIDA BUILDING CODE 2007 AND THE LATEST EDITION OF THE
FOLLOWING PUBLICATIONS: ANS (C) SMACNA MECHANICAL REFRIGERATION (B) NFPA PAMPHLETS 90A & 91
2 ALL AIR CONDITIONING DUCTWORK SHALL BE 1 -112 "STANDARD DUTY
FOIL REINFORCED F'BERGLASS (R-6) MANUFACTURED LOGO PRINTED ON THE
VAPOR BARRIER WHEN IN UNCONDITIONED SPACE, AND 3/4 "STANDARD DUTY
FOIL REINFORCED FIBERGLASS (R -4) MANUFACTURED LOGO PRINTED ON THE
VAPOR BARRIER IN CONDITIONED SPACE OR RETURN PLENUM SPACE.
3. ALL EXHAUST DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL.
4. DUCT SIZE SHOWN ARE NET FREE AREA INSIDE
5. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BEALL
ALUMINUM CONSTRUCTION, WITH EXPOSED SURFACE CHEMICALLY TREATED TO
RECEIVE PAINT TO MATCH COLOR OR AIR GUIDE OR APPROVED EQUAL.
6. PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS.
Z THERMOSTATS SHALL BE COMBINATION COOLING 0 HEATING WITH SYSTEM
COOL/ AUTO/ HEAT/ OFF AND FAN ON/ AUTO SELECTOR SWITCHES.
8. REFRIGERANT PIPING SHALL BE COPPER TYPE A" WITH 1/2°' ARMAFLEX.
INSULATION SHALL BE PROVIDED FOR SUCTION LINES.
9. PROVIDE NEW FILTERS FOR FAN COIL BEFORE STARTING. THESE
FILTERS MUST ALSO BE REPLACED PRIOR TO FINAL ACCEPTANCE BY OWNER.
10. GENERAL CONTRACTOR IS TO HIRE AN INDEPENDENT TEST AND BALANCE
COMPANY WHICH SHALL PROVIDE 3 SET OF THE REPORT SIGN AND SEALED
BY THE PROFESSIONAL ENGINEER FROM THE COMPANY PRIOR OF ACCEPTANCE
OF WORK.
11. MECHANICAL CONTRACTOR ITS TO PROVIDE TURNING VANE AT ALL CHANGE OF DIRECTIONS
OR TO PROVIDE TURNING RADIO, ALL OUTLETS SHALL HAVE EXTRACTORS OR SCUPPERS.
AND SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE REGULATIONS.
®
CEILING GRILLE SEE SIZE SCHEDULE
SUPPLY
DUCT TO MATCH NECK SIZE TYP.
Q
RETURN AIR GRILL
MANUFAC.
THERMOSTAT
DISCHARGED SHALL BE
AIR FLOW DIRECTION ( ARROWS DENOTE
-- •--
l WAY, 2 WAY, ETC., SEE PLANS
—J�• --
RETURN OR EXHAUST, SEE PLANS.
OAL
OUTSIDE AIR INTAKE
CCs
CEILING GRILL
A J-V
AIR HANDLER UNIT
GU
CONDENSING UNIT
mi
CUBIC FEET PER MINUTE
DRILL BLOCKING TO FIT
OUTSIDE OF REF. LINES
CAULK WATER TIGHT
METAL BOOT PAINTED TO
MATCH EXTERIOR FACADE
IN REF. LINES RUN IN ATTIC
(MIN.)
SUCTION CONNECTION
j LIQUID CONNECTION
1 -112" LONG "HELT1' POWER
ACTIVATED PIN INTO SLAB
(TYPICAL OF 4)
y
4" CONCRETE SLAB
INSULATED SUCTION LINE
(NO JOINTS ALLOWED)
SEE FLOOR PLAN
FOR PIPE SIZES
LIQUID LINE
(NO JOINTS ALLOWED] � �-�" � " ' ° -
PROVIDE 4" PVC SLEEVE FOR 1.25 TO
3 TONS & 6" PVC SLEEVE FOR 3.5 TO
5 TONS IF REF, LINES RUN UNDER SLAB
CONDENSING UNIT MOUNTING DETAIL
N.T.S.
f
gfJ81 NJ
I
fool• r
t
4" THICK CONCRETE BASE
N.T.S.
NOTE
PROVIDE ANCHOR BOLT WITH A MINIMUM OF 500 POUND
PULL -OUT RESISTANCE. SHALL SECURE THE AIR CONDITIONING
CONNSER UNIT FROM WITHIN THE UNIT TO THE CONCRETE SLAB
ON WHICH THE UNR RESTS FOR THEFT PREVENTION.
' POWER & CONTROL
LOCATION
1'
IN
LIQUID LINE W/O
INSULATION
SUCTION LINE W/ 1 /2" ARMAFLEX
INSULATION & VAPOR BARRIER
NOTE
UNITS SHALL BE CLEAR BY 3"
MIN. FROM DRIP LINE.
CU MOUNTING DETAIL
314" DEEP x 1/8" POWERED
ACTUATED PINS
FLEX DUCT UP TO 29
'WITH ORIG "DEEP
N.T.S.
O
DUCT HANG DETAIL
N.T.S.
s
RIGID DUCT UP TO
29" WITH OR T 6" DEEP
3" WIDEx 26 GA
G.M. STRIP AT SUPPORT
STUD
I
to
A CG P2XP2
FAN-COIL
DESIGNATION
SUPPLY
MBTUH
ENTERING 7EM
AIR DUCT
MANUFAC.
MODEL
DISCHARGED SHALL BE
TOTAL
ATTIC
MECHANICAL ATTACHED
DB
SPACE
TO AHU
HTNG KW
PROVIDEA MIN. OF 4"SPACE _
I q
UQ.
OF AHU SIDE TO ASSURE
ADEQUATE ACCESS FOR
CEIUN
WALLS
AHU -3
CONSTRUCTION & CLEANING `
19.6
14,8
1{
REF. UN
240
T
PROVIDE CAP -OFF W/
1 125
COIL/HEAT SECTION I
1 /4" PERFORATED FOR VENT
RHLLHM2417JA
FAN SECTION t
a
12"MIN.
314"
FILTER ACCESS —
a
�
I PROVIDE E.Z. TRAP FLOW SWITCH
NO COMBUSTIBLE MATERIALS
ON SECON�ARY C.D. DRAIN TO
B SHUT DOWN THE UNIT IN CASE OF
ALLOWED IN PLENUM
OVER FLOI�V.
PREFAB M L. FRAME
i F.F.
A.H.0 - 1 CLOSET INSTALLATION
DRILL BLOCKING TO FIT
OUTSIDE OF REF. LINES
CAULK WATER TIGHT
METAL BOOT PAINTED TO
MATCH EXTERIOR FACADE
IN REF. LINES RUN IN ATTIC
(MIN.)
SUCTION CONNECTION
j LIQUID CONNECTION
1 -112" LONG "HELT1' POWER
ACTIVATED PIN INTO SLAB
(TYPICAL OF 4)
y
4" CONCRETE SLAB
INSULATED SUCTION LINE
(NO JOINTS ALLOWED)
SEE FLOOR PLAN
FOR PIPE SIZES
LIQUID LINE
(NO JOINTS ALLOWED] � �-�" � " ' ° -
PROVIDE 4" PVC SLEEVE FOR 1.25 TO
3 TONS & 6" PVC SLEEVE FOR 3.5 TO
5 TONS IF REF, LINES RUN UNDER SLAB
CONDENSING UNIT MOUNTING DETAIL
N.T.S.
f
gfJ81 NJ
I
fool• r
t
4" THICK CONCRETE BASE
N.T.S.
NOTE
PROVIDE ANCHOR BOLT WITH A MINIMUM OF 500 POUND
PULL -OUT RESISTANCE. SHALL SECURE THE AIR CONDITIONING
CONNSER UNIT FROM WITHIN THE UNIT TO THE CONCRETE SLAB
ON WHICH THE UNR RESTS FOR THEFT PREVENTION.
' POWER & CONTROL
LOCATION
1'
IN
LIQUID LINE W/O
INSULATION
SUCTION LINE W/ 1 /2" ARMAFLEX
INSULATION & VAPOR BARRIER
NOTE
UNITS SHALL BE CLEAR BY 3"
MIN. FROM DRIP LINE.
CU MOUNTING DETAIL
314" DEEP x 1/8" POWERED
ACTUATED PINS
FLEX DUCT UP TO 29
'WITH ORIG "DEEP
N.T.S.
O
DUCT HANG DETAIL
N.T.S.
s
RIGID DUCT UP TO
29" WITH OR T 6" DEEP
3" WIDEx 26 GA
G.M. STRIP AT SUPPORT
STUD
I
to
A CG P2XP2
FAN-COIL
DESIGNATION
CFM
MBTUH
ENTERING 7EM
ELECTRICAL DATA
MANUFAC.
MODEL
OBS
TOTAL
SENSIBLE
WB
DB
VOLTS
PHASES
HTNG KW
240
FUSES
UQ.
SUC.
COND.
AHU -3
600
19.6
14,8
67
75
240
T
5.0
1 125
20
RHEEM
RHLLHM2417JA
318"
314"
314"
+ LOAD AT 125% AS PER MANUFACTER SPECS.
CONDENSING UNIT
DESIGNATION
MBTUH
TEMP. ENT.
CONDENSER
ELECTRICAL DATA
MANUFAC.
MODEL
OBS OR SEER
AREA SERVED
VOLTS
I PHASES
IWIREAMP4
FUSES
CU -3
19.6
95
240
1
15
20
RHEEM
i3AJM 18A01
14.5
SHOWN
12
3
1
>
YES
NO
DUCT SMOKE DETECTOR
X
FIRE DAMPERS)
X
SMOKE DAMPERS
X
FIRE RATE ENCLOSURE
X
FIRE RATED ROOF /FLOOR CEILING ASSEMBLY
X
FIRE STOPPING
Q
SMOKE CONTROL
X
THERMOSTAT (PROGRAMMABLE)
X
qq
0
¢N
I,
C NEO F L CL I
a
— i
ENTRY
/f
314. CD & TRAP
REF: UN
NO A/C SPACE NEW ATTIC
ACCESS PANEL
PERFORATED
VENT CAP.
SLOPE 1/8" /FT
Z
N
RTU UNIT
2" MIN. FOR 2-112 TONS
OR LESS, 3" MIN. FOR 3
TONS OR MORE.
CONDENSATE TRAP DETAIL
N.T.S.
l
1
t
z
d
t
i
4
i
C
9°
k!
II
�I i€,_
K.I T
r
ti
rr
„jE i
0
CU -3
SCALE: 114 = 1 ' —O t`
..n
cA DTu
6- VIA
HVAC DESIGN RECZLJ►RE:
YES
NO
DUCT SMOKE DETECTOR
X
FIRE DAMPERS)
X
SMOKE DAMPERS
X
FIRE RATE ENCLOSURE
X
FIRE RATED ROOF /FLOOR CEILING ASSEMBLY
X
FIRE STOPPING
X
SMOKE CONTROL
X
THERMOSTAT (PROGRAMMABLE)
X
R.EVBM BY
U.
W
V3
z
DATE 06 -07 -10
SCALE A5 5HOM
DRAWN OM13
JOB 1014
SHM7
14850 B.W. 26 ST
SUITE #212
MIAMI, FLA.
33175
OFFICE
(305) 552 -B538
FAX
(305 ?.552 -8462'"
E-MAIL
rma@rmE3ENr..com
° , "¢4Pa�"�'
L.C. No. 28544
EDMUNDO.LARCiAESP / i,DA � ����® 7'tf� '�°
MECHANICAL. ENGINEER . a'� ?"-
P.E..
t