15-323-002PROVIDE 4 RATED JUMPERS ON POOL RE5AR5 (90' FROM EACH OTHER) WITH " 8 Cu SOLID WIRE AROUND POOL --------------------- r---------------- - - - --+ x / I I I I I I I I I I TO POOL EQUIPMENT I I I I L M 8 COPPER SOLID WIRE 6' TO 8' BELOW GRADE I I I I 1 I I i I 1 -J 680.26 N.E.G. 2208 EDITION ALTERNATE EQUAL POTENTIAL BONDING GRID OF ONE Y 8 SOLID COPPER PLACED 18' TO 24' FROM THE INSIDE EDGE OF POOL ENCOMPAS5ING 360 DEGREES WITH 4 EQUAL BONDING POINTS TO THE POOL STEEL. THE EQUAL POTENTIAL BONDING NEEDS TO BE 6' TO 8' BELOW GRADE AND SECURED IN PLACE EXISTING ELECTRIC METER 320A RATED EXISTING 3 0 350 KcMIL, ITHUN Cu- 21/2'C 4' -0' WATER - -- COPING LEVEL b rt GL05RITE LED LIGHT MANUFACTURED BY PENTAIR UNDERWATER POOL LIGHT 23 WATTS 12 VOLT NEW 5 012 THWN CU IN 1/2' C EXISTING 3 " 350 KcMIL, THWN Cu- 21/2" C EXISTING H 300 300 N CU IN 2' C EXISTING 3 0 350 KcMIL, 1 " 2 GIRD THWN Cu- 211/2' C EXISTING 1.2 (GRD) (Cu) IN 3/4' C TO COP. AND 2 -%'# x 10' RODS 6' APART WALL OF POOL 2' PVC 6CH.40 N VA IAI U-1 r Tel Tv AS PER MANUFACTURER SPECIFICATIONS (SEE RISER DIAGRAM) WWI' Not .' : • �' INTEWATIC DISTRIBUTION COMBO WITH 300 WATTS TRANSFORMER AND TIMER D PUMP AND LIGHT SWITCH ° F JUNCTION BOX 3' 10 IN 11/2' C AS PER MANUFACTURER SPECIFICATIONS • 1� 3 12 IN /2�� SALT SYSTEM THRU TIMER 3'12 IN11/2'C (4) GLOBRITE LED LIGHT MANUFACTURED BY PENTAIR UNDERWATER POOL LIGHT 23 WATTS 12 VOLT DUAL SPEED 111/2 HP POOL PUMP R 11t" RISER DIAGRAM NOTE: ALL WIRIW% 5HALL M COPPER TI NLN POOL PUMP SHOW ON THIS SET OF PLANS IS IN COMPLIANCE WITH FBC, E403.5 Swimming pool H ;TRIM DATA ! SKIMMER I DENOTES DECK JETS PROP05ED POOL 'I VENT SIZE MAXIMUM LENGTH 3/4 1 ---- - - - - -- w..._ –r --------- ----- - - - - -- M 8 COPPER SOLID WIRE 6' TO 8' BELOW GRADE I I I I 1 I I i I 1 -J 680.26 N.E.G. 2208 EDITION ALTERNATE EQUAL POTENTIAL BONDING GRID OF ONE Y 8 SOLID COPPER PLACED 18' TO 24' FROM THE INSIDE EDGE OF POOL ENCOMPAS5ING 360 DEGREES WITH 4 EQUAL BONDING POINTS TO THE POOL STEEL. THE EQUAL POTENTIAL BONDING NEEDS TO BE 6' TO 8' BELOW GRADE AND SECURED IN PLACE EXISTING ELECTRIC METER 320A RATED EXISTING 3 0 350 KcMIL, ITHUN Cu- 21/2'C 4' -0' WATER - -- COPING LEVEL b rt GL05RITE LED LIGHT MANUFACTURED BY PENTAIR UNDERWATER POOL LIGHT 23 WATTS 12 VOLT NEW 5 012 THWN CU IN 1/2' C EXISTING 3 " 350 KcMIL, THWN Cu- 21/2" C EXISTING H 300 300 N CU IN 2' C EXISTING 3 0 350 KcMIL, 1 " 2 GIRD THWN Cu- 211/2' C EXISTING 1.2 (GRD) (Cu) IN 3/4' C TO COP. AND 2 -%'# x 10' RODS 6' APART WALL OF POOL 2' PVC 6CH.40 N VA IAI U-1 r Tel Tv AS PER MANUFACTURER SPECIFICATIONS (SEE RISER DIAGRAM) WWI' Not .' : • �' INTEWATIC DISTRIBUTION COMBO WITH 300 WATTS TRANSFORMER AND TIMER D PUMP AND LIGHT SWITCH ° F JUNCTION BOX 3' 10 IN 11/2' C AS PER MANUFACTURER SPECIFICATIONS • 1� 3 12 IN /2�� SALT SYSTEM THRU TIMER 3'12 IN11/2'C (4) GLOBRITE LED LIGHT MANUFACTURED BY PENTAIR UNDERWATER POOL LIGHT 23 WATTS 12 VOLT DUAL SPEED 111/2 HP POOL PUMP R 11t" RISER DIAGRAM NOTE: ALL WIRIW% 5HALL M COPPER TI NLN POOL PUMP SHOW ON THIS SET OF PLANS IS IN COMPLIANCE WITH FBC, E403.5 Swimming pool H ;TRIM DATA ! SKIMMER I DENOTES DECK JETS 120 � 240v VENT SIZE MAXIMUM LENGTH 3/4 1 1r 3W EiS� =A PAI a W 111/2 W/ 150A MCB CKT5 SERVE5 C.B. P KW 54 LF WIRE - COND. CKT- 29,31 POOL PUMP (GFCU 20 2 1.1 111/2'0 « 12 - 1/2' C CKT- 33 POOL LIGHT 20 1 03 " 12 - 1/2' C (GFCU GROUND FAULT CIRCUIT INTERRUPTER Ue 1. ALL ELECTRIC WIRING SHALL BE IN ACCORDANCE WITH NEC -NFPA -10- 2008 -680 2. PROVIDE GROUND WIRE SYSTEMS LOOP WITH " 8 COOPER WIRE FOR THE POOL DECK WIRE MESH AND STRUCTURAL STEEL. 3. ALL WIRING SHALL BE COPPER THWN 4. ALL SWIMMING POOL EQUIPMENTS SHALL BE THRU GFCI BREAKER (NEC 68022b) 5. CONTRACTOR SHALL ESTABLISH LOCATIONS OF UTILITIES AT THE SITE. MINIMUM CLEARANCE DIMENSIONS SHALL BE HELD AND SHALL BE AS REQUIRED BY THE LOCAL REGULATORY AGENCY IN GENERAL. HOLD A DISTANCE OF 10 FEET FROM OVERHEAD ELECTRIC LINES TO OPEN POOL WATER EDGE AND 5 FEET FROM UNDEWSROUND ELECTRIC LINES. 6. ELECTRICAL EQUIPMENT - METAL PARTS OF ELECTRICAL EQUIPMENT ASSOCIATED WITH THE POOL WATER CIRCULATING SYSTEM, INCLUDING PUMP MOTORS AND METAL PARTS OF EQUIPMENT ASSOCIATED WITH POOL COVERS, INCLUDING ELECTRIC MOTORS, SHALL BE BONDED.EXCEPTION: METAL PARTS OF LISTED EQUIPMENT INCORPORATING AN APPROVED SYSTEM OF DOUBLE INSULATION SHALL NOT BE BONDED. (NEC 68026.5) 1. POOL MOTORS REQUIRE OVERLOAD PROTECTION TO COMPLY WITH NEC 43032 POOL EQUIPMENT ON 4' CONCRETE PAD AND SECURED WITH 4- 14'0 ANCHOR BOLTS WITH NUTS AND WA5HER5 (TYPIGAL)- INTERMATIG DISTRIBUTION COMBO WITH 300 WATTS TRANSFORMER AND TIMER POOL BOTTOM 2'0 SUCTION LINE ---- 11/2'0 VENT LINE (FOR LENGTH -SEE SCHEDULE) PENTAIR MODEL 542031 (WHITE) AND 542041 (BLACK) ANTI VORTEX MAIN DRAIN COVER TESTED TO ASME A 112](3bM BY U.L. 8112 LISTED (TYPICAL OF 2) MAN DRAM MAI. 6' (MIN) CONCRETE ALL AROUND DRAIN SUMP 11/4' HYDRO -VALVE GRAVEL SUMP R4101b.6 Entrapment protection for suction outlets shall be installed in accordance with requirements of AN51 /APSP 1. THE MAXIMUM VACUUM WITH ONE SUMP PLUGGED AND A BODY" ENTRAPMENT ON THE OTHER SUMP NEVER EXCEEDS 45 INCHES OF MERCURY, THE ENTRAPMENT RELEA5E5 IN LESS THAN THREE SECONDS. TESTING WAS ACCOMPLISHED UNDER THE DIRECTION OF WILLIAM ROWLEY A REGISTERED ENGINEER OF STATE OF FLORIDA DATED DEC 8 / 2001 111/2'0 VENT PIPE 12' ABOVE GRADE WITH 0005E NECK I I I I I I I --------- - - - - -- DENOTES 11/2'0 LINES PLUMBING NOTES: I. ALL POOL AND EQUIPMENT PIPING SHALL BE SCHEDULE 40, PVC -PW, NON - THREADED, NSF APPROVED SUPPORTED CONTINUOUSLY ON GROUND OR ON MAXIMUM 4'0' CENTERS WITH CLEVIS HANGERS. 2. ALL SUCTION PIPING SHALL BE 2' DIAMETER AND ALL PRESSURE PIPING 1112' DIAMETER UNLE55 OTHERWISE NOTED. 3. POOL WATER DISPOSAL SHALL BE IN ACCORDANCE WITH LOCAL BUILDING DEPARTMENT REQUIREMENTS. 4, ANTI VORTEX MAIN DRAIN SHALL HAVE ITS PLATE SECURELY FASTENED WITH TAMPERPROOF SCREWS. 5. POOL VACUUM SHALL HAVE SPRING LOADED CAP IN ACCORDANCE WITH THE FLORIDA BUILDING CODE. 6. ALL PIPING SHALL BE INSTALLED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE- PLUMBING SECTION 309 1. THE WATER VELOCITY THROUGH ALL SUCTION PIPING SHALL 5E LE65 THAN 8 FEET PER SECOND. 6. THE WATER VELOCITY THROUGHOUT ALL PRESSURE PIPING SHALL BE LE56 THAN 10 FEET PER SECOND. t. ALL PIPING SHALL BE SUITABLE FOR EXPOSURE TO ULTRA VIOLET RADIATION AND NORMAL OPERATING TEMPERATURES. 10. VACUUM SHALL BE EQUIPPED WITH SELF - CLOSING SAFETY COVER REQUIRING TOOLS FOR REMOVAL 11/2'0 VENT PIPE 12' ABOVE GRADE WITH GOOSE NECK 111/2'0 VENT PIPE THE VENT SYSTEM 15 TO LIMIT THE TRANSM1551ON OF SUCTION AT THE OUTLET TO A MAXIMUM OF 45 IN OF MERCURY RFlEF VENT DUAL MT PIPE 5CHEDULE SKIMMER I DENOTES DECK JETS FLOW RATE VENT SIZE MAXIMUM LENGTH 3/4 1 43 GPM 55 GPM (TYPICAL OF 4) 30 LF 30 LF 111/2 15 GPM 11/2'0 40 LF 2 102 GPM 111/2'+ 54 LF 211/2 131 GPM SWIMOUT I DEEP 13 LF, 3 143 GPM 111/2'0 16 1 F. I 5 -61 ul O u1/ u, DEEP I STEPS (2) ANTI- VORTEX 12' 12' ' I MAIM DRAIN OP0 I 5ED I ITV L./ B, POOL I 30' -0' I I VACUUM 514ALL BE EQUIPPED WITH 6ELF- CI -051NG SAFETY COVER REQUIRING TOOLS FOR REMOVAL GLOBRI E L D UIGHT (TYPICAL 4) --------- - - - - -- DENOTES 11/2'0 LINES PLUMBING NOTES: I. ALL POOL AND EQUIPMENT PIPING SHALL BE SCHEDULE 40, PVC -PW, NON - THREADED, NSF APPROVED SUPPORTED CONTINUOUSLY ON GROUND OR ON MAXIMUM 4'0' CENTERS WITH CLEVIS HANGERS. 2. ALL SUCTION PIPING SHALL BE 2' DIAMETER AND ALL PRESSURE PIPING 1112' DIAMETER UNLE55 OTHERWISE NOTED. 3. POOL WATER DISPOSAL SHALL BE IN ACCORDANCE WITH LOCAL BUILDING DEPARTMENT REQUIREMENTS. 4, ANTI VORTEX MAIN DRAIN SHALL HAVE ITS PLATE SECURELY FASTENED WITH TAMPERPROOF SCREWS. 5. POOL VACUUM SHALL HAVE SPRING LOADED CAP IN ACCORDANCE WITH THE FLORIDA BUILDING CODE. 6. ALL PIPING SHALL BE INSTALLED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE- PLUMBING SECTION 309 1. THE WATER VELOCITY THROUGH ALL SUCTION PIPING SHALL 5E LE65 THAN 8 FEET PER SECOND. 6. THE WATER VELOCITY THROUGHOUT ALL PRESSURE PIPING SHALL BE LE56 THAN 10 FEET PER SECOND. t. ALL PIPING SHALL BE SUITABLE FOR EXPOSURE TO ULTRA VIOLET RADIATION AND NORMAL OPERATING TEMPERATURES. 10. VACUUM SHALL BE EQUIPPED WITH SELF - CLOSING SAFETY COVER REQUIRING TOOLS FOR REMOVAL 11/2'0 VENT PIPE 12' ABOVE GRADE WITH GOOSE NECK 111/2'0 VENT PIPE THE VENT SYSTEM 15 TO LIMIT THE TRANSM1551ON OF SUCTION AT THE OUTLET TO A MAXIMUM OF 45 IN OF MERCURY RFlEF VENT DUAL MT PIPE 5CHEDULE PUMP H.P. FLOW RATE VENT SIZE MAXIMUM LENGTH 3/4 1 43 GPM 55 GPM 11/2'0 1 '/2'0 30 LF 30 LF 111/2 15 GPM 11/2'0 40 LF 2 102 GPM 111/2'+ 54 LF 211/2 131 GPM 11/2'0 13 LF, 3 143 GPM 111/2'0 16 1 F. THESE VENT SYSTEM WILL LIMIT THE TRANSMISSION OF SUCTION AT THE OUTLET TO A MAXIMUM OF 4.5' OF MERCURY IN WATER COLUMN PPM DIAGUW WATER VELOCITY TO COMPLY FBC 2010 R4101b3 AND ANSI INSPI -5 2003 -52 POOL DATA & EQUPMW SITE t DEPTH __7 15' x 30' 35' TO 5' CAPACITY 13,5x0 GALLONS PERIMETER/AREA W L.F. / 450 SQFT. PUMP )IK 11/2 H.P. (DUAL SPEED) FILTER )IE CARTRIDGE (200 SQFT.) TILE � u SLIP RESISTANT + EXIT RAILINGS - �uL� U �uLLi U O D �wLL U u, ul O u1/ u, PPM DIAGUW WATER VELOCITY TO COMPLY FBC 2010 R4101b3 AND ANSI INSPI -5 2003 -52 POOL DATA & EQUPMW SITE t DEPTH __7 15' x 30' 35' TO 5' CAPACITY 13,5x0 GALLONS PERIMETER/AREA W L.F. / 450 SQFT. PUMP )IK 11/2 H.P. (DUAL SPEED) FILTER )IE CARTRIDGE (200 SQFT.) TILE 6' CHOICE TYPE OF PATIO SLIP RESISTANT + EXIT RAILINGS - COPING BRICF: = TURNOVER CC 3.02 HOUR X 13590 GALLONS RE- CIRCULATED IN 302 HOUR 200 GPM • 1 GPM FILTER RATED 200 SOFT. FILTER AREA AND 11/2 HP RE- CIRCULATION POOL ' PUMP, I PHASE, 230 V,15 GPM • 50' TDH N�E2l�r'' NO' LPL • � •'• L 0� , (� r <1 "ilftl'1.1i1��� REV15ION5 BY c�1 L& s K; 61 N nom° G U O ® -4"W LLJ 0 N C9 10 t I.D n ..i N 3 (L 6' m � W 9:3 N O r f w� via 1/V t, • 10 400 01 1C •�1C L=•- I ll 0— ImEmal OF O �� C� Q _} O y �r I"rr`w1 —1 u) DRAWN : RM.G. CHECKED - O.M.F. DATE : Marh '15 SCALE : SHOWN JOB NO.: 15 -01631 SHEET 2 OF 2 SHEETS