;DISTRIBUT•tC1N PANEL tA-
PL ,OC 7 OF I< APPROXIMATE L A E74 S IELECTR I CAC" ROOM AN I iS D f S CR I BUT I
NEL . U OUND R STING ND EXI S I SER REPLACE. EE APPROX I MAT 65 - II NWFOL,HANDH'00 ;1 < SERVI CE,: POLE -~ F
fir, 'a'-�,`r? -tom, __ _ ., -= .�• _ _. ": .. .- - .. -, ' -.- • -.. .
EXISTING MAIN DISTRIBUTION PANEL
IN ELECTRICAL ROOM.
PULL OUT EXISTING CONDUCTORS (2- 500MCM 8< 2- 250.MCM)
FROM EXISTING 3" RACEWAY. VERIFY CONDITION OF RACEWAY.
IF RACEWAY IS INTACT, PULL NEW 2- 500MCM AND 2- 250MCM
IN EXISTING RACEWAY.
IF RACEWAY IS DAMAGED. INSTALL NEW 3" RCSC FROM PANEL
TO NEW FPL HANDHOLE AND PULL NEW 2- 500MCM AND 2- 250MCM
IN NEW RACEWAY. RACEWAY SHALL BE INSTALLED IN 28" DEEP
TRENCH A MINIMUM OF 24" BELOW GRADE.
SERVICE REPAIR WORK RISER
ALL CONDUCTORS COPPER WITH TYPE THWN INSULATION
CURRIER ASSOCIATES
AM OF CONSULTING ENGINEERS (305)446-6555 -
FLA LIC. JEB 0000830
CHARLES CURRIER. ELECTRICAL ENGINEER: FLA-PE #11529