08-1111R-003MEZZANINE FLOOR PLAN SCALE: 1/8' - l' -0' SECOND. SCALE: 1/8' a l' -0' FIRST FLOOR SCALE: 1/8" - V -0' FACP do POWER SUPPLIES ARE LOCATED IN A MECHANICALLY VENTILATED AREA THIS IS A NON SPRINKLED BUILDING SCOPE OF WORK CHANGE FACP FROM UNIMODE 4520 TO UNIMODE 9600 AND ADD ADDITIONAL DEVICES AS SHOWN ON PLANS. MOVE 2 EXISTING NAC CKTS FROM UNIMODE 4520 TO NEW POWER SUPPLY. PR ❑VIDE POWER SUPPLY TO POWER EXISTING SMOKE DETECTORS. REVISION: CHANGE EXISTING HORN STROBES FROM 15/15CD TO 75CD AND RE -WIRE ALL NAC CKTS. REMOVE BEAM DETECTOR & ADD SMOKE DETECTORS. ADD P.O.C. TO ANSUL SYSTEM & DOOR HOLDERS. FIRE ALARM NOTES 1. THIS IS A POWER LIMITED FIRE ALARM SYSTEM. ALL DEVICES OR UNITS SHALL BE INSTALLED USING APPROVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE 1170 AND THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE*760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL WIRING ORDINANCES. 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE *760 POWER LIMITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCTORS SHALL HAVE MINIMUM RATING OF 300V AND SHALL BE OF SOLID COPPER OR BUNCH- TINNED STRANDED COPPER CONDUCTORS. THESE CONDUCTORS OR CABLES SHALL BE FPLP OR FPLR IN ACCORDANCE WITH NEC ARTICLE 760 AND NEC ARTICLE 725 CLASS 2 OR 3 CIRCUITS. 3. CONDUCTORS OR CABLES USED IN DUCTS OR PLENUM TYPE CEILING FOR ENVIRONMENT A:4 S4A_1- EMPLOY THE USE OF ELECTRICAL METAL TUBING OR PLENUM RATED INSULATED TYPE CABLE (FPLP). THE CABLE SHALL BE UL LISTED FOR SUCH USE AND MEET ALL THE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION. 4. ALL INDICATING DEVICES SHALL BE MOUNTED AT 80' A.F.F. FROM THE FLOOR TO THE BOTTOM OF THE LENS UNLESS OTHERWISE NOTED, AND SHALL BE UL LISTED 1971 ADA 75 CANDELA MINIMUM. 5. ALL MANUAL - INITIATING DEVICES SHALL BE MOUNTED AT 48' TO CENTER A.F.F. UNLESS OTHERWISE NOTED. 6. CUSTOMER TO PROVIDE (2) PHONE LINES FOR CERTIFICATED CENTRAL STATION MONITORING WITH DIFFERENT LONG DISTANCE CARRIERS. 7. ELECTRICAL CONTRACTOR TO PROVIDE IIOV DEDICATED CIRCUIT WITH 2OAMP CIRCUIT BREAKER, USING 12AWG THHN TYPE WIRE WITH 600V MINIMUM INSULATION. IN 1/2' MINIMUM CONDUIT. THE THE CIRCUIT BREAKER NUMBER AND PANEL SMALL BE NOTED AND MARKED IN ACCORDANCE TO NFPA 72, AND ANY LOCAL ORDINANCE. B. ALL INDICATING CIRCUITS SHALL BE STYLE Y (CLASS B) UNLESS OTHERWISE SPECIFIED. ALL INITIATING ADDRESSABLE DEVICES SHALL CONNECT WITH TWO WIRES TO ONE OF THE CONTROL PANELS SLC LOOPS. 9. DUCT DETECTOR SEQUENCE OF OPERATION UPON ALARM DUCT DETECTOR SHALL ACTIVATE ANY TROUBLE CONDITION WILL BE ANNUNCIATEDIT THE MAIN PANEL, AND ANNUNCIATOR, ALSO SHUTDOWN A/C UNIT 10. ANY DUCT DETECTOR ALARM SHALL CAUSE THE AIR HANDLERS TO SHUT DOWN. 11. THIS SYSTEM WILL BE CERTIFICATED AS A CENTRAL STATION SERVICE FIRE ALARM SYSTEM. 12. ALLOWABLE AMPACITY ACCORDING TO CONDUCTOR SIZE. SIZE(AWG) ALLOWABLE AMPACITY 18 6 16 8 14 CONTRACTOR SHALL COORDINATE ALL MOUNTING HEIGHTS AND FINAL LOCATIONS 17 12 23 10 28 13. MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METAL TUBING. TYPE CONDUCTOR TRADE SIZES IN INCHES LETTER SIZE (AWG) 112' 3/4' V 1 -1/4' 1 -1/2' 2' 2 -1/2' TEN, TFFN 18AWG 22 38 63 108 148 244 TFN, TFFN 16AWG 17 29 48 83 113 186 THHN 14AWG 12 22 35 61 84 138 241 THVN 12AWG 09 16 26 45 61 101 176 THVN -2 IOAWG 05 10 16 28 38 63 111 Q FIRE ALARM MANUAL PULL STATION ADT- BG -I2LX a,q WEATHERPROOF FIRE ALARM MANUAL PULL STATION ADT- BG -12LOB WIRE LEGEND CHART TYPE CONDUCTORS /DESCRIPTION MARKINGS A 2 COND 19 AWG SOLID ADT493490 2C /IBAWG TYPE FPLP /CMP(UL) B 4 COND 18 AVG SOLID ADT494449 4C /18AWG TYPE FPLP /CMP(UL) C 2 COND 14 AVG SOLID ADT493491 2C /14AWG TYPE FPLP /CMP(UL) D 2 C13ND 18 AWG SOLID SHLD 860830A 2C /18AWG TYPE FPLP /CMPQIL) E 4 COND IB AWG S13LID SHLD 860836 4C /1BAW,3 TYPE FPLP /CMPQx.) F 4 COND 22 AWG SOLID ADT494468 4C /22AWG TYPE FPLP /CMP(UL) G 12 COND 22 AWG SOLID ADT494469 12C /22AWG TYPE FPLP /CMP(UL) H 2 COND 18 AWG SOLID BLACK BURIAL 180010 2C /IBAWG TYPE FPLP /IRR(UL) IA. ALL EQUIPMENT COMPATIBLE AND UL LISTED FOR FIRE SERVICE. 1/2' MA EMC FOR STUBS 40X FILL FOR ALL CONDUIT. 13. THE DESIGN INSTALLATION COMPLIES WITH FBC 11- 4.28.3 SEQUENCE OF OPERATION ANY INITIATING DEVICE ACTIVATED SHALL CAUSE THE FIRE ALARM PANEL TO GO INTO ALARM CONDITION, ON INITIATING DEVICE SUPERVISORY SIGNAL SHALL CAUSE THE FIRE ALARM PANEL TO SHOW A SUPERVISORY CONDITION, ALSO ON ANY TROUBLE CONDITION, BOTH THESE SIGNALS WILL DISPLAY THE DEVICE OR ZONE ON THE FRONT PANELS WELL AS ANY REMOTE ANNUNCIATORS CONNECTED TO SYSTEM. ACTIVATE INDICATING DEVICES, TRANSMIT SIGNAL TO OFFSITE LISTED CENTRAL STATION AND ACTIVATE OR OPERATE OPERATE ANY AUX. RELAYS OR FUNCTONSAS NOTED ON FLOOR PLAN. SEE SEQUENCE OF OPERATION MATRIX AS SHOWN ON PLANS. FIRE ALARM LEGEND CONTRACTOR SHALL COORDINATE ALL MOUNTING HEIGHTS AND FINAL LOCATIONS OF DEVICES WITH A REPRESENTATIVE (PRIOR TO ROUGH -IN). OTY SYMBOL DESCRIPTION PART/ CATALOG / MANUFACTURER 1 _E�ff FIRE ALARM CABINET - INSTALLED 5' -0' AFF UNIMODE 9600 ADT 1 8 POWER SUPPLY FCPS -24FS6 ADT 3 m POWER SUPPLY FCPS -24FSB ADT i 13 1 Q FIRE ALARM MANUAL PULL STATION ADT- BG -I2LX a,q WEATHERPROOF FIRE ALARM MANUAL PULL STATION ADT- BG -12LOB ADT FIREUTE 27 0` FIRE ALARM HORN - STROBE -'RED' CANDELLA 75 P2R SYSTEM SENSOR 9 g Y FIRE ALARM HORN - STROBE -'RED' CANDELLA 110 P2R SYSTEM SENSOR 1 WEATHERPROOF HORN - STROBE -'RED' CANDELLA 75 P2RK SYSTEM SENSOR 36 FIRE ALARM STROBE -'RED' CANDELLA 75 SR SYSTEM SENSOR 1 7s CEILING STROBE -'RED' CANDELLA 75 SCR SYSTEM SENSOR �- 4 QD DUCT SMOKE DETECTOR P.O.C. BY OTHERS 58 Op PHOTO ELECTRIC SMOKE DETECTOR 3534 -2 CRT ADT 20 O PHOTO ELECTRIC SMOKE DETECTOR SD355 ADT 25 O HEAT DETECTOR 4220 -135 ADT 3 © CONTROL RELAY CRF -300 ADT 102 MONITOR MODULE MMF -300 ADT 1 0 LCD ANNUNCIATOR LCO -80F ADT 1 a ANSUL SYSTEM P.O.C. BY OTHERS 2 0 DOOR HOLDER P.O.C. BY OTHERS T REVISIONS SECURITY SERVICES, INC. . 2801 GATEWAY DRIVE POMPANO BEACH, ' FLORIDA 33069 (954) 917 -2400 FAX (954) jH.T. 917 -2419 NO.: OATES: GEORGE A MANGINEW EF 0001121 p 8 /22 /00 FIR ST NATIONAL BANK 2 OF SOUTH FLORIDA N:A1LOSJA%VCHPE 3 5750 SUNSET DRIVE 1FLONDA3BE6 4 S. MIAMI, FL. 33143 MI RWI7CAL LID: Q**� 5 DESGED BY: DWG BY: p ADT FIRE ALARM PLAN R C / L 6 DATE !CALL S M N .: DM0. NO.: 7 8/11/00 1 1/8' . 1' -0' 1 , 2 149 - 03915 -38