13-489R-004GENERAL NOTES: 1. UL RANGE HOOD: MATERIAL: 18 GAUGE STAINLESS STEEL CONSTRUCTION ON EXPOSED SURFACES 18 GA. GALV. ON EXH. PLENUM ALL CONTINUOUS EXTERNAL LIQUID TIGHT WELDS, POLISHED. FILTERS UL CLASSIFIED BAFFLE TYPE. SET IN HOOD @ 45 DEGREE ANGLE, INCANDESCENT LIGHT FIXTURES UL LISTED FOR USE IN COMMERCIAL COOKING HOODS. GREASE TRAY BELOW FILTERS WITH REMOVABLE GREASE CONTAINER, LIQUID VOLUME LESS THAN 1 QUART. ALL IN COMPLIANCE WITH NFPA #96 AND LOCAL BUILDING CODES. 2. TYPE I RANGE HOOD EXHAUST DUCTS: MATERIAL: 16 GAUGE GALVANIZED STEEL, CONSTRUCTION ALL CONTINUOUS LIQUID TIGHT EXTERNAL WELDS. DUCT IS CONNECTED BY 1/2" FLANGES FULL WELDED. DUCTS TO SLOPE TOWARD HOOD. CLEANING ACCESS AT CHANGE IN DIRECTION OF DUCT RUN EXCEPT AT HOOD CHANGE 3. RANGE HOOD SUPPLY DUCTS: MATERIAL: GALVANIZED SHEET METAL GAUGES, HANGING AND REINFORCING PER SMACNA STANDARDS. 4. RANGE HOOD EXHAUST FAN: AS SPECIFIED ON DRAWING AND CONFORMING TO SMOKE AND GREASE - LADEN VAPOR REMOVAL UL LISTED SUBJECT BULLETIN 762 YZHW. 5. RANGE HOOD SUPPLY FAN: AS SPECIFIED ON DRAWINGS AND CONFORMING TO A NATIONAL TESTING AUTHORITY FOR PERFORMANCE CERTIFICATION. TO BE LOCATED A MINIMUM OF 10' -0" FROM ANY EXHAUST FAN, PLUMBING VENT AND FLUE STACKS. 6. ELECTRICAL: ELECTRICAL HOOK UP AND EQUIPMENT SUCH AS MOTOR STARTERS, SWITCHES, CONTROLS AND COMPONENTS OTHER THAN WHAT IS SPECIFICALLY MENTIONED ON DRAWINGS IS BY OTHERS. 7. FIRE SUPPRESSION SYSTEM: FIRE SUPPRESSION SYSTEM UNDER SEPERATE PERMIT PRIOR TO FINAL INSPECTION. 8. EQUIPMENT SCREENING: ALL ROOF EQUIPMENT TO BE CONCEALED FROM PUBLIC VIEW, IF REQUIRED, IS TO BE FURNISHED BY OWNER /G.C. UNDER SEPARATE PERMIT. 9. COMPLIANCE: SYSTEM TO BE MANUFACTURED AND INSTALLED IN STRICT ACCORDANCE WITH NFPA #96, LOCAL FIRE PREVENTION BUREAU MECH. AND HEALTH DEPT. STANDARDS REQUIREMENTS BY ELECTRICAL CONTRACTOR. 1. WIRE EACH FAN CIRCUIT FROM CIRCUIT BREAKER TO LINE SIDE OF CONTACTOR IN CONTROL PANEL. 2. WIRE EACH FAN FROM LOAD SIDE OF CONTACTOR IN CONTROL PANEL TO FAN DISCONNECT SWITCHES ON FAN. DISCONNECT SWITCHES PROVIDED ON FANS. 3. WIRE A 120V 20 AMP CIRCUIT TO TERMINALS L AND N IN CONTROL PANEL. 4. WIRE FROM CONTROL PANEL TERMINALS NO AND N TO HORN /STROBE DEVICE IN KITCHEN. 120V HORN /STROBE DEVICE TO BE PROVIDED BY ELECTRICAL CONTACTOR. 5. WIRE FROM CONTROL PANEL TERMINALS NO AND N TO SHUNT TRIP BREAKERS IN CIRCUIT BREAKER PANEL. ALL ELECTRIC RECEPTACLES OR HARDWIRED APPLIANCES UNDER THE HOOD OR FEEDING EQUIPMENT UNDER THE HOOD NEED TO SHUT DOWN UPON FIRE SYSTEM ACTIVATION. SHUNT TRIP BREAKERS PROVIDED BY ELECTRICAL CONTRACTOR. 6. FIRE ALARM CONNECTIONS -IF A FIRE ALARM IS PRESENT IT NEEDS TO BE CONNECTED TO A SPARE MICRO SWITCH WE HAVE AT THE FIRE SYSTEM CONTROL HEAD. IF AN ALARM IS PRESENT A HORN /STROBE DEVICE IS NOT REQUIRED. 7. IF ANY OTHER NEW OR EXISTING HOOD SYSTEMS ARE WITHIN THE SAME ROOM AS EACH OTHER AND THEY OPERATE INDIVIDUALLY ALL SUPPLY FANS MUST SHUT DOWN UPON ANY OF THE FIRE SYSTEM ACTIVATIONS. THIS CAN BE ACCOMPLISHED THROUGH SHUNT TRIP BREAKERS OR A SPARE SET OF CONTACTS WE HAVE ON OUR °FIRE RELAY" IN OUR CONTROL PANEL. CONTACT THE FACTORY FOR YOUR SPECIFIC SCENARIO. 8. HEAT SENSORS NEED TO BE WIRED FROM EACH HOOD COLLAR TO CORRESPONDING SENSOR RELAY IN CONTROL PANEL. 9. LIGHTS ARE PRE WIRED ON TOP OF EACH HOOD TO A SINGLE JUNCTION BOX. JUMPERS NEED TO BE PROVIDED AND INSTALLED IN BETWEEN HOOD SECTIONS AND FROM THE NEAREST HOOD TO THE CONTROL PANEL AND WIRE TO TERMINALS 14 AND 15. 10. WHEN THERE IS NOT A FIRE CABINET BUILT INTO OUR HOOD THE MICRO SWITCH MUST BE WIRED FROM THE FIRE SYSTEM CONTROL BOX TO OUR CONTROL PANEL. THE COM WIRE (BLUE) GOES TO TERMINAL C IN OUR PANEL, THE NORMALLY CLOSED WIRE (YELLOW) GOES TO TERMINAL NC IN OUR PANEL AND THE NORMALLY OPEN WIRE (BROWN) GOES TO TERMINAL 3 IN OUR CONTROL PANEL. ITH MIN. OF TMETAL SCREWS SELF TAPPING SCREW, TOGGLE BOLT OR ROD 0 CORNERS MINIMUM OF 4 PER PITCH ABOVE WILL PROVIDE A CONNECTION OF PAN TO ROOF THAT WILL WITHSTAND WIND OF 170 MPH WITH A SAFETY FACTOR OF AST FOUR. MUA-DUCT ROOF SUPPORT DETAIL - � ��i��������. ♦C I� ♦♦ ♦�� DETAIL 3" REDUCTION METHOD 12 GA. HANGER WELDED TO TOP OF HOOD 3 3/8 "0 ALL THREADED ROD FASTENED TO TOP CORE OF EXISTING BAR JOIST W/ BEAM CLAMPS AND TO 1 5/8" UNISTRUT OR 2 "X2 "Xj" ANGLE IRON W/ 3/8 "0 BOLTS , WASHERS AND NUTS. BAR JOIST 3/8 "0 ALL - THREAD ROD TO 12 GA. HANGER WITH WASHERS AND NUTS, TOP & BOTTOM. STOP OF HOOD HOOD HANGING DETAIL N.T.S. EXHAUST CIRCUIT PHASE 208V -230V 3 PHASE SET 0 20.0 AMP BREAKER ALI TO 7.9/k EXHAUST CIRCUIT C3 PHHASE 208V -230V 3 PHASE 20.0 AMP BREAKER LI T2.08A SUPPLY CIRCUIT 3 PHASE 208V -230V 3 PHASE 20.0 AMP BREAKER I I TO SET 110.a F HOOD DEPOT - I TEMPmTURE i SEAR I C -- I I _ I I I HO=W DSOT I TEMPERATURE _J2 _J SENSOR RELAY DUCT SENSOR FIELD MOUNTED AND WIRED TSS2 EXHAUST FAN 11 208V 230V 3 PHASE 2.0 Hp 7.5 AMPS EXHAUST FAN H 208V -230V 3 PHASE 1/2 Hp 2.4 AMPS HOOD # CONTROL OPTIONS FIELD WIRING TYPE R T1 Q HOOD SWITCH LIGHT SWITCH - - - FACTORY WIRING LJ A INSTALLER Is REOUIRED TO PROVIDE AND UTLITY CABINET MOUNTED AND MOUNTED AND RELAY MOUNTED WITH AUTO ON TEMP SETPOINT CFM INSTALL APPROVED MEANS OF TYPE MIRED IN PANEL WIRED IN PANEL MIRED FOR 18' X I8' X V TYPE I DISCONNECT HOOD - LIGHT (2) 24" x 10" IHINGED ELECTRICAL ENCLOSURE B. ALL OUTPUTS FROM TERMINAL 13.3 SQFT )FOR N -Na Y OR N .m EXHAUST FILTERS BLOCKS ARE 120V ONLY EXHAUST CIRCUIT PHASE 208V -230V 3 PHASE SET 0 20.0 AMP BREAKER ALI TO 7.9/k EXHAUST CIRCUIT C3 PHHASE 208V -230V 3 PHASE 20.0 AMP BREAKER LI T2.08A SUPPLY CIRCUIT 3 PHASE 208V -230V 3 PHASE 20.0 AMP BREAKER I I TO SET 110.a F HOOD DEPOT - I TEMPmTURE i SEAR I C -- I I _ I I I HO=W DSOT I TEMPERATURE _J2 _J SENSOR RELAY DUCT SENSOR FIELD MOUNTED AND WIRED TSS2 EXHAUST FAN 11 208V 230V 3 PHASE 2.0 Hp 7.5 AMPS EXHAUST FAN H 208V -230V 3 PHASE 1/2 Hp 2.4 AMPS INSIDE DASHED LINE REPRESENTS ACTUAL COHRtOL PANEL ENCLOSURE. EVERYTHING OUTSIDE OF LINE IS WIRED FROM OUTSIDE OF CONTROL PANEL. U.L. FILE MH 18803 HOOD SCHEDULE =- --- - - HOOD # ° SUPPLY FAN /1 208V 3 MODEL # -230V PHASE L �} 3.0 Hp 10.6AMPS TYPE R T1 Q D LIGHTS FILTERS LJ WGT UTLITY CABINET --- SJVITC�!ES SIZE RELAY MOUNTED WITH AUTO ON TEMP SETPOINT CFM ADJUSTABLE FROM INSIDE THE CONTROL BOX. TYPE INSIDE DASHED LINE REPRESENTS ACTUAL COHRtOL PANEL ENCLOSURE. EVERYTHING OUTSIDE OF LINE IS WIRED FROM OUTSIDE OF CONTROL PANEL. U.L. FILE MH 18803 HOOD SCHEDULE =- --- - - HOOD # MFG. MODEL # LENGTH TYPE EXHAUST COLLAR AREA OF EXHAUST VELOCITY THRU LIGHTS FILTERS MATERIAL WGT UTLITY CABINET --- SJVITC�!ES SIZE S.P. CFM QTY. TYPE QTY 7H X W TYPE SIZE LOCATION HOOD - LIGHT (2) 24" x 10" 1/4" 1443 13.3 SQFT 108 FPM FILTERS EXHAUST FILTERS #1 7' -8" 1 HOOD DEPOT SIMA- 1446025416 10' -0" TYPE 1 HOOD 32" x 18" 5/8" 6000 28.77 SQFT 209 FPM 6 INCANDESCENT (12) 20" X 20" S/S KASON 430 S/S 650 LBS 15" REMOTE REMOTE REMOTE 14" 24" x 10" 1/4" 1173 7.3 SQFT 161 FPM 40 L EXPOSED CABINET CABINET 2 HOOD DEPOT NDF- 0724525114 6' -0" TYPE I HOOD 11" x 11" 5/8" 1380 8.22 SQFT 168 FPM 2 INCANDESCENT (2) 20" X 16:: (2) 20 X 20 S/S KASON 430 S 300 LBS 15" REMOTE REMOTE CABINET REMOTE CABINET EXPOSED ED MUA PLENUM SCHEDULE PLENUM # HOOD # LENGTH WIDTH SUPPLY COLLAR AREA OF MUA PERF VELOCITY THRU MUA PERF WGT SIZE S.P. CFM 1A #1 10' -0" 16" (2) 24" x 10" 1/4" 1443 13.3 SQFT 108 FPM 70 LBS 1B #1 10' -0" 16" (2) 24" x 10" 1/4" 1443 13.3 SQFT 108 FPM 70 LBS 1 C #1 7' -8" 16" 24" x 10" 1/4" 1107 10.2 SQFT 108 FPM 50 LBS 1D #1 7' -8" 16" - 24" x 10" 1/4" 1107 10.2 SQFT 108 FPM 50 LBS 2 #2 6' -3" 14" 24" x 10" 1/4" 1173 7.3 SQFT 161 FPM 40 L HVAC DESIGN CRITERIA HOOD # YES NO FIRE DAMPER 7380 X SMOKE DAMPER VOLTAGE X FIRE RATED CEILING TOTAL AIR VOLUME X DUCT SMOKE DETECTOR JENCO X FIRE RATED ENCLOSURE 1.125" X AIR BALANCE SCHEDULE HOOD # EX CFM SUPPLY CFM AIR EXHAUSTED FROM HOODS 7380 S.P. AIR SUPPLIED TO HOODS VOLTAGE 6273 AMPS TOTAL AIR VOLUME 7380 6273 HOOD 1 GREASE DUCT VELOCITY SCHEDULE DUCT AREA = L X W / 144 = SQ.FT. DUCT VELOCITY = CFM DIVIDED BY DUCT AREA =FPM DUCT AREA = 32 X 18 / 144= 4.00 SQ.FT. DUCT VELOCITY = 6000 / 4.00 = 1500 FPM #12 SELF TAPPING SCREW, TOGGLE BOLT OR—) THD. ROD 0 CORNERS & 12" O.C. MAXIMUM FOR ALL FAN CURBS AND PLATFORMS, ABOVE WILL PROVIDE A CONNECTION OF FAN CURB TO ROOF THAT WILL WITHSTAND WIND LOADS OF 170 MPH WITH A SAFETY FACTOR OF AT LEAST FOUR. IF PANEL IS REMOTE MOUNTED. OR FIRE FIRE SYSTEM SYSTEM IS FELD MOUNTED THEN MICRO HIM SWITCH SWITCH MARES MUST BE FIELD WIRED. CONTACTS WHEN SYSTEM IS SET --DZE SYSTEM MICRO SWITCH EXHAUST FAN CONTINUES TO RUN UNDER FIRE CONDITION EVEN WITH HOOD SWITCH TAI -1 OFF r I NCNC (NORMALLY CLOSEt)) TO BE USED FOR APPLIAN(X COMTACTO I NO (NORMALLY OPEN) TO BE USED FOR HORNS, STROBES. SHUNT TRIPS. ETC. I m e m SON. -J r- i NOTE 3: _(D m NC (D - - J He m NC m - Ia (D 3 0 m r- slf NOTE a G m 3 m Jr m NO (D � - NO ID - m 4 m - - - m 4 ID TO HOBO mwm - - - 5 2 a) FROM HOOD SWITCH md) 5 db (D 14 a) HDDD U (M L L L i1toT m 15 a) ION 1 d m 16 a) - - m 17 C (I) N (D To PRAT ORa1ND - J iD m N m m N m N m . NE!rrRel CONTROL CIRCUIT HO 120V 1PHASE INPUT POWER L a) �- I_ 15 AMP BREAKER MQD L 0 m GROUND TO II G P O GROUND 1 m c db m �u2 FIRE �IRELAYI FIRE RELAY2 MCI FAN SCHEDULE HOOD # FANS MFG. MODEL # CFM S.P. HP VOLTAGE RPM AMPS WGT #1 EF -1 JENCO CM -24 6000 1.125" 2.0 208V/30 865 6.8 340 LBS #2 EF -2 JENCO TXB -15 1380 .85" 1/2 208V/30 1168 2.4 95 LBS #1 &2 SF -1 JENCO KSF -18 6273 1/2" 3.0 208V/30 819 10.6 310 LBS BS L 2 low NOW 719 "� 1 457/8' I 24 3/4' 41.2 t 2 M 35 " 417/8 HOOD #2 CM -24 EXHAUST FAN DETAIL TXB -15 EXHAUST FAN DETAIL KSF -18 SUPPLY FAN DETAIL N.T.S. N.T.S. N.T.S. GREASE DUCT VELOCITY SCHEDULE DUCT AREA = L X W / 144 = SQ.FT. 2 DUCT VELOCITY = CFM DIVIDED BY DUCT AREA =FPM THE FOLLOWING ARRANGEMENT WILL PROVIDE A CONNECTION OF FAN TO ROOF CURB THAT WILL WITHSTAND r_l WIND LOADS OF 170 MPH WITH A SAFETY FACTOR OF AT LEAST FOUR. DUCT AREA = 11 X 11 / 144= 0.84 SQ.FT. DUCT VELOCITY = 1380 / 0.84 = 1642 FPM PLATFORM DETAIL N.T.S. EXHAUST FAN ATTACHED TO PLATFORM /CURB WITH 22 GA. X 1" GALVANIZED STEEL METAL STRAPS AND #10 X 1" SHEETMETAL SCREWS, 3 STRAPS PER SIDE (6 TOTAL) WILL PROVIDE A CONNENCTION OF FAN CURB TO ROOF THAT WILL WITHSTAND WIND LOADS OF 170 MPH WITH A SAFETY FACTOR OF AT LEAST FOUR. FAN TO BE SECURED TO CURB WITH PRE - ENGINEERED HINGES 18 GAUGE GALVANIZED STEEL CONTINUOUSLY WELDED LIQUID TIGHT ROOF CURB #12 SELF TAPPING SCREW, TOGGLE BOLT OR THD. ROD 0 CORNERS & 12" O.C. MAXIMUM FOR ALL FAN CURBS AND PLATFORMS, ABOVE WILL PROVIDE A CONNECTION OF FAN CURB TO ROOF THAT WILL WITHSTAND WIND LOADS OF 170 MPH WITH A SAFETY FACTOR OF AT LEAST FOUR. 12 GAG A' ko) ff 1 Y JITCC I MC. I ML SCREWS W/ RUBBER WASHERS FAN HURRICANE STRAPPING DETAIL FAN BASE SECURED WITH MIN. OF 2 #14 SHEETMETAL SCREWS EXHAUST FAN ON THREE SIDES FAN BASE SECURED WITH MIN. OF 16 GAUGE GALVANIZED STEEL 2 #14 SHEETMETAL SCREWS - CURB BASE CAP CONTINUOUSLY ON ALL FOUR SIDES WELDED LIQUID TIGHT TO EXHAUST DUCT TO SUPPORT FAN IN CASE OF FIRE 18 GAUGE GALVANIZED STEEL GREASE CONTAINER CONTINUOUSLY WELDED LIQUID PER NFPA #96 TIGHT ROOF CURB 16 GAUGE GALVANIZED STEEL EXHAUST DUCT CONTINUOUSLY WELDED LIQUID TIGHT ROOF CURB DETAIL (N.T.S) DUCT TEMPERATURE SENSOR DETAIL DUCT TEMPERATURE SENSOR TEMPERATURE SENSOR TO BE PLACED IN THE GREASE EXHAUST DUCT TO ACTIVATE THE EXHAUST HOOD SYSTEM PER FLORIDA MECHANICAL CODE 507.2.1.1 OPERATION. WHICH STATES TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER COOKING OPERATIONS OCCUR. THE ACTIVATION OF THE EXHAUST FAN SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED METHODS. - - TO SENSOR RETRY IN THE H= DEPOT CONTROL PANEL STEEL SUPPLY FAN .0 , o ; u #12 SELF TAPPING SCREW, TOGGLE BOLT OR THD. ROD 0 CORNERS & 12" O.C. MAXIMUM FOR ALL FAN CURBS AND PLATFORMS, ABOVE WILL PROVIDE A CONNECTION OF FAN CURB TO ROOF THAT WILL WITHSTAND WIND LOADS OF 170 MPH WITH A SAFETY FACTOR OF AT LEAST FOUR. - 'L ROOF CURB DETAIL Pyl �BR��1lto No. 72500 •W O��• STATE OF :_Qj; 4 0 R `'o ''�•,, BONA fil ,%`_,•`. �e 1 w` >r • +n F. j .4 Y,1 a �i r • A. ;A .e r• � JI� ..s 4 d �i Y