13-406R-013ITH MIN. OF TMETAL SCREWS SELF TAPPING SCREW, TOGGLE BOLT OR ROD 0 CORNERS MINIMUM OF 4 PER PITCH ABOVE WILL PROVIDE A CONNECTION OF PAN TO ROOF THAT WILL WITHSTAND WIND OF 170 MPH WITH A SAFETY FACTOR OF AST FOUR. . f- MUA DUCT ROOF SUPPORT DETAIL COMBUSTIBLE MATERIAL 1 " NONCOMBUSTIBLE SPACER 1" MINERAL WOOL BAT 22 GAUGE SHEET METAL BOTH SIDES, MEETS AND EXCEEDS NFPA #96 DETAIL 3" REDUCTION METHOD D 3/8 "0 ALL THREADED ROD FASTENED TO TOP CORE OF EXISTING BAR JOIST W/ BEAM CLAMPS AND TO 1 5 /8" UNISTRUT OR 2 "X2 "Xq" ANGLE IRON W/ 3/8"0 BOLTS , WASHERS AND NUTS. BAR JOIST 3/8 "0 ALL - THREAD ROD TO 12 GA. HANGER WITH WASHERS AND NUTS, TOP k BOTTOM. STOP OF HOOD HOOD HANGING DETAIL N.T.S. f! r•!•! •• Y W M f f r f r r s r •• r• s u f U.L. FILE MH 18803 HOOD SCHEDULE ;... ....; y- •••! . • C ! • f 1 HOOD # MFG. MODEL # LENGTH TYPE DUCT AREA OF EXHAUST VELOCITY THRU LIGHTS 1 MATERIAL WGT UTLITY CABINET —f SWITCHES Y 1 " NONCOMBUSTIBLE SPACER 1" MINERAL WOOL BAT 22 GAUGE SHEET METAL BOTH SIDES, MEETS AND EXCEEDS NFPA #96 DETAIL 3" REDUCTION METHOD D 3/8 "0 ALL THREADED ROD FASTENED TO TOP CORE OF EXISTING BAR JOIST W/ BEAM CLAMPS AND TO 1 5 /8" UNISTRUT OR 2 "X2 "Xq" ANGLE IRON W/ 3/8"0 BOLTS , WASHERS AND NUTS. BAR JOIST 3/8 "0 ALL - THREAD ROD TO 12 GA. HANGER WITH WASHERS AND NUTS, TOP k BOTTOM. STOP OF HOOD HOOD HANGING DETAIL N.T.S. f! r•!•! •• Y W M f f r f r r s r •• r• s u f U.L. FILE MH 18803 HOOD SCHEDULE ;... ....; y- •••! . • C ! • f 1 HOOD # MFG. MODEL # LENGTH TYPE EXHAUST COLLAR AREA OF EXHAUST VELOCITY THRU LIGHTS FILTERS MATERIAL WGT UTLITY CABINET —f SWITCHES Y SIZE S.P. CFM QTY. TYPE QTY H X W TYPE SIZE LOCATION HOOD LIGHT 1/4" 1443 13.3 SQFT 108 FPM 70 LBS FILTERS EXHAUST FILTERS 7' -8" 16" 1 HOOD DEPOT SIMA - 1446025416 10' -0" TYPE 1 HOOD 32" x 18" 5/8" 6000 28.77 SQFT 209 FPM 6 INCANDESCENT (12) 20" X 20" S/S KASON 430 S/S 650 LBS 15" REMOTE REMOTE REMOTE 1 24" x 10" 1/4" 1173 7.3 SQFT 161 FPM 40 L =SQ .FT. DUCT AREA L X W / 144 -- SQ.FT. 2 Z�L DUCT VELOCITY = CFM DIVIDED BY DUCT AREA =FPM EXPOSED WILL WITHSTAND CABINET CABINET 2 HOOD DEPOT NDF- 0724525114 6' -0" TYPE 1 HOOD 11 " x 11" 5/8" 1380 8.22 SQFT 168 FPM 2 INCANDESCENT (2) 20" X 16„ (2) 20 X 20 S/S KASON 430 S/S 300 LBS 15" REMOTE REMOTE CABINET REMOTE 7X19 -A #12 SELF TAPPING SCREW, TOGGLE . A1N EXHAUST 'Ise EXHAUST FAN 1 CONTINUOUSLY WELDED LIQUID EXPOSED S/S CABLE m C CABINET MUA PLENUM SCHEDULE PLENUM # HOOD # LENGTH WIDTH SUPPLY COLLAR AREA OF MUA PERF VELOCITY THRU MUA PERF WGT SIZE S.P. I CFM 1A #1 10' -0" 16" (2) 24" x 10" 1/4" 1443 13.3 SQFT 108 FPM 70 LBS 1B #1 10' -0" 16" (2) 24" x 10" 1/4" 1443 13.3 SQFT 108 FPM 70 LBS 1 C #1 7' -8" 16" 24" x 10" 1/4" 1107 10.2 SQFT 108 FPM 50 LBS 1D #1 7' -8" 16" 1 24" x 10" 1/4"— 1107 10.2 SQFT 108 FPM 50 LBS 2 #2 6' -3" 14" 1 24" x 10" 1/4" 1173 7.3 SQFT 161 FPM 40 L HVAC DESIGN CRITERIA HOOD # YES NO FIRE DAMPER 7390 X SMOKE DAMPER VOLTAGE X FIRE RATED CEILING TOTAL AIR VOLUME X DUCT SMOKE DETECTOR JENCO X FIRE RATED ENCLOSURE 1.125" X AIR BALANCE SCHEDULE HOOD # EX CFM SUPPLY CFM AIR EXHAUSTED FROM HOODS 7390 S.P. AIR SUPPLIED TO HOODS VOLTAGE 6273 AMPS TOTAL AIR VOLUME 1 7390 6273 FAN SCHEDULE HOOD # FANS MFG. MODEL # CFM S.P. HP VOLTAGE RPM AMPS WGT #1 EF -1 JENCO CM -24 6000 1.125" 2.0 208V/30 865 6.8 340 LBS #2 EF -2 JENCO TXB -15 1380 1 .85" 1/2 208V/30 1 1168 2.4 1 95 LBS #1&2 SF -1 JENCO KSF -18 1 6273 1 1/2" 3.0 208V/30 1 819 10.6 310 LBS I L 2 0 31 5 /8-T 17" '4' • f • f • • • r • f • •t!. • CONTROL—OPTIONS HOOD SWITCH LIGHT SWITCH GEMEBLL MOTES: A. ELECTRICAL INSTALLER IS REQUIRED TO PRWAE AND INSTALL APPROVED MEANS OF EXHAUST FAN FIRE SYSTEM MICRO SWITCH CONTACTS WHEN IF ANEL IS REMOTE MOUNTED, OR FIRE SYSTEM IS FIELD MOUNTED THEN MICRO SWITCH WIRES MUST BE FIELD WIRED. FIELD WIRING — — — FACTORY WIRING MOUNTED AND MOUNTED AND FAN TO BE SECURED � 35 "SQ DISCONNECT SECURED WITH MIN. OF 41 7/9- .. 31 39 SQ WIRED IN PANEL WIRED FOR 12" X 19" X G' TYPE I HINGED ELECTRICAL ENCLOSURE 2 X14 SHEETMETAL SCREWS B. ALL OUTPUTS FROM TERMINAL FAN i� HOOD 1 ICBD SWI HOOD 2 CM-24 EXHAUST FAN DETAIL TXB -15 EXHAUST FAN DETAIL KSF -18 SUPPLY FAN DETAIL- BLOCKS ARE 120V ONLY N.T.S. N.T.S. N.T.S. GREASE DUCT VELOCITY SCHEDULE GREASE DUCT VELOCITY SCHEDULE W NC NO (N RMALLY CLOSED) TO BE USED FOR OF DUCT AREA =LXW / 144 =SQ .FT. DUCT AREA L X W / 144 -- SQ.FT. 2 Z�L DUCT VELOCITY = CFM DIVIDED BY DUCT AREA =FPM DUCT VELOCITY = CFM DIVIDED BY DUCT AREA =FPM THE FOLLOWING ARRANGEMENT WILL PROVIDE A CONNECTION OF FAN TO ROOF CURB THAT WILL WITHSTAND WIND LOADS OF 170 MPH WITH A SAFETY FACTOR OF AT LEAST FOUR, DUCT AREA = 32 X 18 / 144= 4.00 SQ.FT. DUCT AREA = 11 X 11 / 144= 0.84 SQ.F. DUCT VELOCITY = 6000 / 4.00 = 1500 FPM DUCT VELOCITY = 1380 / 0.84 = _ 1642 FPM ALUMINUM RING HORNS, STROBES, SHUNT TRIPS. ETC. 7X19 -A #12 SELF TAPPING SCREW, TOGGLE . A1N EXHAUST 'Ise EXHAUST FAN 1 CONTINUOUSLY WELDED LIQUID S/S CABLE m C m cGM� TYPICAL OF SELF TAPPING SCREW, TOGGLE - SEE NOTE 3: r EXHAUST CIRCUIT CONTACTO 3 PHASE ¢ R+ PER NFPA #96 TIGHT ROOF CURB 2o9V -23ov 3 PHASE TO BE O.C. MAXIMUM FOR ALL FAN CURBS AND NC ANY ROOFTOP --- .r CRIMPE PLATFORMS, ABOVE WILL PROVIDE A O.C. AIRPIN CLIP FAN NC m 209V -230V 3 PHASE 20.0 AMP BREAKER _ SEF O/L Az Lt TO 7.! A ]T3 EXHAUST FAN ATTACHED TO PLATFORM /CURB CONNECTION OF FAN CURB TO ROOF THAT ° 3 r ,SEE MOTE I o WILL WITHSTAND WIND LOADS OF 170 MPH #12 SELF TAPPING SCREW, TOGGLE BOLT OR (1) 3 6 m WITH 22 GA. X 1" GALVANIZED STEEL METAL NO m ° ° WITH A SAFETY FACTOR OF AT LEAST FOUR. WILL WITHSTAND WIND LOADS OF 170 MPH o 'o THD. ROD 0 CORNERS k 12" O.C. MAXIMUM Al N EXHAUST STRAPS AND #10 X 1" SHEETMETAL SCREWS, EXHAUST FAN {)<2 • WITH m 4 m EXHAUST CIRCUIT CONTACTO 3 PHASE t R FOR ALL FAN CURBS AND PLATFORMS, ABOVE 209V -230V 3 PHASE 3 STRAPS PER SIDE (6 TOTAL) WILL PROVIDE � 4 T• Mon swrrcH ' L 1/2 HP 2.4 AMPS WILL PROVIDE A CONNECTION OF FAN CURB TO V A CONNENCTION OF FAN CURB TO ROOF THAT 12 GA GALVO 20iV -230V 3 PHASE _ SET o/L IT" �1 J}� ROOF THAT WILL WITHSTAND WIND LOADS OF (N.T.S) A WILL WITHSTAND WIND LOADS OF 170 MPH 5 `����� P� �; ••0EN•N� —FROM Hoop SWITCH CLEVIS PI 170 MPH WITH A SAFETY FACTOR OF AT LEAST 20.0 AMP BREAKER . • o WITH A SAFETY FACTOR OF AT LEAST FOUR. m 5 m FOUR. o o ATTACHED TO CURB W/ 14 (3) #14 SHEETMETAL WO" SWITCH SCREWS W/ RUBBER FAN HURRICANE STRAPPING DETAIL 1 5 A) 4/ HOW LAWS L L L WASHERS N SUPPLY v• —� SUPPLY FAN #1 U J 16 H �?. SY 7-EM TO LIGHT SUPPLY CIRCUIT 3 PHASE Ie • T3 —r MISTAL! [- e PLATFORM DETAILx� 17 rr„ �C'%�T ^cCAMCk r�. swlrcH 209V -230V 3 PHASE - -� SET o/L T2 N. T. S. 3.0 HP 10.6AMPS �- �......� ..�....��, m N I� FAN BASE �- -- 20.0 AMP BREAKER L1 TO I1.OA t TI SECURED WITH MIN. OF 0 D m N m 2 #14 SHEETMETAL: SCREWS D CONTROL—OPTIONS HOOD SWITCH LIGHT SWITCH GEMEBLL MOTES: A. ELECTRICAL INSTALLER IS REQUIRED TO PRWAE AND INSTALL APPROVED MEANS OF EXHAUST FAN FIRE SYSTEM MICRO SWITCH CONTACTS WHEN IF ANEL IS REMOTE MOUNTED, OR FIRE SYSTEM IS FIELD MOUNTED THEN MICRO SWITCH WIRES MUST BE FIELD WIRED. FIELD WIRING — — — FACTORY WIRING MOUNTED AND MOUNTED AND FAN TO BE SECURED DISCONNECT SECURED WITH MIN. OF SYSTEM IS SET WIRED IN PANEL WIRED IN PANEL WIRED FOR 12" X 19" X G' TYPE I HINGED ELECTRICAL ENCLOSURE 2 X14 SHEETMETAL SCREWS B. ALL OUTPUTS FROM TERMINAL FAN i� FIBE_SY�B� ICBD SWI TCM EXHAUST FAN CONTINUES TO RUN UNDER Y OR N .NO Y OR N -NO BLOCKS ARE 120V ONLY 1LUE so 1RGVN No FIRE CONDITION EVEN WITH HOOD SWITCH OFF NOTE W NC NO (N RMALLY CLOSED) TO BE USED FOR OF 18 GAUGE GALVANIZED STEEL APPLIANCE CONTACTORS. I FIRE CONTINUOUSLY WELDED LIQUID NO (N RMALLY OPEN) TO BE USED FOR TIGHT ROOF CURB HORNS, STROBES, SHUNT TRIPS. ETC. 18 GAUGE GALVANIZED STEEL #12 SELF TAPPING SCREW, TOGGLE . A1N EXHAUST 'Ise EXHAUST FAN 1 CONTINUOUSLY WELDED LIQUID F I m C m cGM� #12 SELF TAPPING SCREW, TOGGLE - SEE NOTE 3: r EXHAUST CIRCUIT CONTACTO 3 PHASE ¢ R+ PER NFPA #96 TIGHT ROOF CURB 2o9V -23ov 3 PHASE J l(j) O.C. MAXIMUM FOR ALL FAN CURBS AND NC � --- 2.0 HP 7.5 AMPS PLATFORMS, ABOVE WILL PROVIDE A O.C. MAXIMUM FOR ALL FAN CURBS AND m NC m 209V -230V 3 PHASE 20.0 AMP BREAKER _ SEF O/L Az Lt TO 7.! A ]T3 CONNECTION OF FAN CURB TO ROOF THAT 3 r ,SEE MOTE I C WILL WITHSTAND WIND LOADS OF 170 MPH G (1) 3 6 m F- NO m WITH A SAFETY FACTOR OF AT LEAST FOUR. WILL WITHSTAND WIND LOADS OF 170 MPH NO (1) WELDED LIQUID TIGHT Al N EXHAUST EXHAUST FAN {)<2 WITH m 4 m EXHAUST CIRCUIT CONTACTO 3 PHASE t R 209V -230V 3 PHASE � 4 T• Mon swrrcH �-_ L 1/2 HP 2.4 AMPS V 20iV -230V 3 PHASE _ SET o/L IT" �1 J}� (N.T.S) A 5 `����� P� �; ••0EN•N� —FROM Hoop SWITCH 20.0 AMP BREAKER — A2 Lt TO z.B A + m 5 m 14 (� WO" SWITCH mT W 1 5 A) 4/ HOW LAWS L L L I N SUPPLY v• —� SUPPLY FAN #1 U J 16 Taw LIGHT SUPPLY CIRCUIT 3 PHASE Ie • T3 —r 209V -230V 3 PHASE 17 — swlrcH 209V -230V 3 PHASE - -� SET o/L T2 3.0 HP 10.6AMPS -S C m N I� TG MLGT GROUND -- • �- -- 20.0 AMP BREAKER L1 TO I1.OA t TI 0 D m N m D ® N m (D N _NEUTML _NEUTRAL CONTROL CIRCUIT L HOT 120V 1PHASE INPUT POWER T y 15 AMP BREAKER I L —' ^DEPOT GROUND TO II G (1) HOOD PANEL a) G -- GROUND TEMPERATURE SENSOR 11 I m CD n r"- RELAY MOUNTED WITH AUTO ON TEMP SETPOINT D COIL- ® COM2 NO I I _— 1 2 ADJUSTABLE FROM INSIDE THE CONTROL BOX. F cOIL+ FIRE RELAYI ® N 02 Z 3 COM1 NOt NC I HOOD DEPOT I 4 S G TEMPERATURE - SENSOR? — J 5 COIL- T CB + SENSOR 7 E COM2 NO COIL- FIRE RELAY DBIL+ RELAY2 NO2 DUCT SENSOR FIELD 9 P COM1 N01 ® NC MOUNTED AND WIRED 10 11 TSS2 IN -9004 JOD NAME HUNS ANn DL-jNS DATE DRAWN n DWG. N0, SIDE MOTE: 07/24/1 MAC J2EAt FCN1TS2 INSIDE DASHED LINE REPRESENTS ACTUAL CONTROL PANEL ENCLOSURE. MOOD TEE s� FD EVERYTHING OUTSIDE OF LINE IS WIRED FROM OUTSIDE OF CONTROL PANEL. BRUN H'1 p/0 1) DEPPOT FF�(G54)35 oiG�fs DUCT TEMPERATURE SENSOR TEMPERATURE SENSOR TO BE PLACED IN THE GREASE EXHAUST DUCT TO ACTIVATE THE EXHAUST HOOD SYSTEM PER FLORIDA MECHANICAL CODE 507.2.1.1 OPERATION. WHICH STATES TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER COOKING OPERATIONS OCCUR. THE ACTIVATION OF THE EXHAUST FAN SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED METHODS. TEMPERATURE SENSOR — — — J TO SENSOR RELAY IN THE HOOD DEPOT CONTROL PANEL 16 GAUGE GALVANIZED STEEL .� No. 72500 cr +�• * • %0 STATE OF =�= • • 4. so R llllll11111111 EXHAUST FAN ON THREE SIDES FAN BASE i FAN TO BE SECURED SECURED WITH MIN. OF TO CURB WITH PRE- 16 16 GAUGE GALVANIZED STEEL 2 X14 SHEETMETAL SCREWS FAN i� ENGINEERED HINGES CURB BASE CAP CONTINUOUSLY ON ALL FOUR SIDES WELDED LIQUID TIGHT TO EXHAUST DUCT TO SUPPORT FAN IN CASE OF 18 GAUGE GALVANIZED STEEL FIRE CONTINUOUSLY WELDED LIQUID TIGHT ROOF CURB 18 GAUGE GALVANIZED STEEL #12 SELF TAPPING SCREW, TOGGLE GREASE CONTAINER CONTINUOUSLY WELDED LIQUID BOLT OR THD. ROD ® CORNERS do 12" #12 SELF TAPPING SCREW, TOGGLE PER NFPA #96 TIGHT ROOF CURB O.C. MAXIMUM FOR ALL FAN CURBS AND BOLT OR THD- ROD 0 CORNERS do 12" PLATFORMS, ABOVE WILL PROVIDE A O.C. MAXIMUM FOR ALL FAN CURBS AND CONNECTION OF FAN CURB TO ROOF THAT PLATFORMS, ABOVE WILL PROVIDE A 16 GAUGE GALVANIZED STEEL WILL WITHSTAND WIND LOADS OF 170 MPH CONNECTION OF FAN CURB TO ROOF THAT EXHAUST DUCT CONTINUOUSLY WITH A SAFETY FACTOR OF AT LEAST FOUR. WILL WITHSTAND WIND LOADS OF 170 MPH WELDED LIQUID TIGHT WITH A SAFETY FACTOR OF AT LEAST FOUR. ROOF CURB DETAIL ROOF CURB DETAIL `Illllulrlllll� 8 R (N.T.S) (N.T.S) `����� P� �; ••0EN•N� ��•` DUCT TEMPERATURE SENSOR TEMPERATURE SENSOR TO BE PLACED IN THE GREASE EXHAUST DUCT TO ACTIVATE THE EXHAUST HOOD SYSTEM PER FLORIDA MECHANICAL CODE 507.2.1.1 OPERATION. WHICH STATES TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER COOKING OPERATIONS OCCUR. THE ACTIVATION OF THE EXHAUST FAN SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED METHODS. TEMPERATURE SENSOR — — — J TO SENSOR RELAY IN THE HOOD DEPOT CONTROL PANEL 16 GAUGE GALVANIZED STEEL .� No. 72500 cr +�• * • %0 STATE OF =�= • • 4. so R llllll11111111