14-850-003I OR 2 HOUR FIRE RATED THROUGH
2 HOUR FIRE RATED THROUGH
lirl
0
'SOS I PENETRATION FIRESTOP FOR
(j, 30,01 PENETRATION FIRESTOP FOR SINGLE
METAL PIPE THROUGH GYPSUM
U
'00
ci MULTIPLE METAL PIPE THROUGH
CONCRETE FLOORS OR WALLS
UL
0 L WALLS USING TREMSTOP WBM.
Vow
0 USING TYRE- SHIELD.
voot
0
F-RATING =1 AND 2 HR.
F-RATING = 2 HR.
WLI 147 T-RATING - 0 AND 1t2 HR.
CAJ-1304 T-RATING = 0 HR.
2
3B
3B
...........
2
1. FLOOR OR WALL ASSEMBLY — 4 THICK CONCRETE, MAX
AREA OF OPENING IS 288 SQ. IN.
2. COPPER PIPE: 4' DIA. (OR SMALLER) REGULAR (OR HEAVIER) COPPER.
STEEL PIPE: So DIA. (OR SMALLER) SCHAO (OR HEAVIER) STEEL
CONDUIT: 40 DIA. (OR SMALLER) EMT OR 60 DIA. (OR SMALLER) STEEL CONDUIT.
COPPER TUBING: 4" DIA.(OR SMALLER) TYPE L(OR HEAVIER) COPPER.
1. 1 OR 2 - HOUR FIRE RATED GYPSUM WALLBOARD /STUD ASSEMBLY
IRON PIPE: W DIA.(OR SMALLER) CAST OR DUCTILE IRON.
MAX NUMBER OF PIPES WITH OPENING IS THREE (3).
2. A) STEEL PIPE - 6" DIAM.(OR SMALLER) SCH. 40 (OR HEAVIER) STEEL
B) CONDUIT - 4" DIAM.(OR SMALLER) EMT OR RIGID STEEL
3 A) FORMING MATERIAL - (NOT SHOWN) - NOM. In THICK POLY
URETHANE BACKER ROD FRICTION FITTED INTO OPENING.
3. TREMSTOPWBM - FILL MAX 3/4w ANNULUS AT A THICKNESS
B) NOM. FYRE-SHIELD THICKNESS INSTALLED WITHIN OPENING.
OF 1 (2 HR. F-RATING) OR 3/4r (I HR. F-RATING).
/V2w
NOTE: FOR WALL APPLY FYRE-SHIELD TO BOTH SURFACES OF WALL.
2 HOUR FIRE RATED THROUGH
I OR 2 HOUR FIRE RATED THROUGH
PENETRATION FIRESTOP FOR SINGLE
fz PENETRATION FIRESTOP FOR
R51 PLASTIC PIPE THROUGH
0 PLASTIC PIPE THROUGH
VUL9 CONCRETE FLOORS OR WALLS
U L GYPSUM WALLS USING
USING BLAZEMASTER CAULK&
FYRE-CAN SLEEVE
e
F-RATING = 2 HR.
F-RATING = 2 HR.
CAJ 2221 T-RATING 1-112 HR.
WL2151 T-RATING =1 HR.
2
4
2
2 .....
...... Id
.......... Q.
3
1. PRE-RATED CONCRETE FLOORS OR BLOCK WALLS = MIN. 4-1W THICKNESS
1. PRE-RATED GYPSUM WALLBOARD/STUD ASSEMBLY.
2. PLASTIC PIPE - A) NOM. 2" DIAM. (OR SMALLER) SCH. 40 PVC PIPE.
2. PLASTIC PIPE - 3" DIA. OR 20 DIA. SCHAO PVC FOR USE
B) NOM. 2' DIAM. (OR SMALLER) CPVC PIPE
IN CLOSED OR VENTED PIPING SYSTEMS.
THE ANNULAR SPACE RANGE SHALL BE MIN MIN 1/4r TO MAX 3V
3. FYRE-CAN SLEEVE/INTUMESCENT DEVICE:
NOTE: FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
NOM. PIPE DIAM. OF ANNULAR
3. FORMING MATERIAL - FOAM BACKER ROD FIRMLY PACKED INTO THE OPENING
DIAM. (IN.) DEVICE SIZE OPENING (IN.) SPACE (IN.)
AS A PERMANENT FORM.
2 TS2 3-112 1/4 TO 7/8
3 TS3 4-3/4 1/2 TO 314
4. BLAZEMASTER CAULK & WALK - MIN 1/20 THICKNESS OF SEALANT APPLIED
WITHIN OPENING, FLUSH TOP SURFACE OF FLOOR OR BOTH SURFACES OF
4. TREMSTOP WBM - MIN. 1/40 THICK SEALANT APPLIED AT
WALL ASSEMBLY
SLEEVE/PIPE AND SLEEVE/WALL INTERFACES.
The above described assembly and
'Y19INHOO(O
THE PRODUCTS USED IN THE ABOVE ASSEMBLY HAVE
products have been tested and are
based on both and anticipated
past
3735 Green Rd.
BEEN TESTED IN ACCORDANCE WITH THE FOLLOWING:
performance criteria. tremco shall
Beachwood, OH, 44122
ASTM E814 (UL1479) STANDARD TEST METHOD
not be liable far any damages, direct
FOR THROUGH PENETRATION FIRESTOPPING.
or consequential, resulting from use
• ASTM E119 (UL 263) STANDARD FOR FIRE TESTS
of this material or design. tremoo
OF BUILDING CONSTRUCTION AND MATERIALS.
shall only be responsible for replacing
DRAWING NOT TO SCALE
material found to be defective.