ELECTRICAL NOTES:
12 13 14 15 18 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 U3V7 u 38 il V
A
1) ALL WIRING IS "POWER LIMITED ".
2) ALL WIRING AS APPLICABLE SHALL BE : 14/2, 12/2, 12/4, 18/2 & 18/4 UL FPL CABLE OR THWN.
3) INSTALLATION ADDITIONS SHALL COMPY WITH THE 2004 FBC / MIAMI —DADE COUNTY & LOCAL AHJ CODES
4) INSTALLATION ADDITIONS SHALL COMPLY WITH NFPA 72 2002 ALL APPLICABLE CHAPTERS
5) INSTALLATION ADDITIONS SHALL COMPLY WITH NFPA 101 2003 ALL APPLICABLE CHAPTERS
6) INSTALLATION ADDITIONS SHALL COMPLY WITH THE NEC 2005 ALL APPLICABLE SECTIONS
7) CONDUIT AS REQUIRED SHALL BE 1/2" & 3/4" EMT RACEWAY SIZED FOR MAXIMUM OF 40% WIRE FILL
! FLEXIBLE METALLIC RACEWAY AS REQUIRED SHALL BE 1/2" MINIMUM SIZED FOR MAXIMUM OF 40% WIRE FILL
8) SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS AND THE NEC 2005 ARTICLE 250
9) ALL VISUAL DEVICES SHALL BE MOUNTED @ 80" AFF TO BOTTOM OF VISUAL PER ADA & NFPA 72 2002
10) SYSTEM COMPONENTS SHALL BE UL LISTED, MFR COMPATIBLE AND SUITABLE FOR FIRE SERVICE USE
1 1) COST OF THIS PROJECT IS LESS THAN S 5,000
12) THE FIRE ALARM EVACUATION SIGNAL SHALL BE TEMPORAL PER NFPA 72 2002 & NFPA 101 2003
13) ALL FIRE /SMOKE PARTITION PENETRATION(S) SHALL BE SEALED AS REQUIRED, WITH
LISTED APPROVED FIRESTOP COMPOUND, TO MATCH PENETRATED STRUCTURE(S) FIRE RATING
14) • INITIATING CIRCUITS SHALL BE CLASS B, STYLE B
• ALL NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B — STYLE Y
15) DUCT SMOKE DETECTORS IF APPLICABLE SHALL BE SUPERVISORY ANNUNCIATION ON[_Y,
DUCT DETECTORS SHALL NOT INITIATE GENERAL ALARM
16) MANUAL PULL STATIONS SHALL BE MOUNTED @ 48" AFF
17) FIRE ALARM SYSTEM CONTROL SHALL BE MOUNTED AT FRONT ENTRANCE LOBBY PER PLAN @ 60" AFF
! FIRE ALARM CONTROL SHALL HAVE BUILT —IN ANNUNCIATOR
18) THE FIRE ALARM SYSTEM IS EXISTING AND SHALL BE REMOTE STATION / 24 HOUR STANDBY BATTERY REQUIRED
19) ALL VISUALS SHALL BE SYNCRONIZED @ 1 HZ PER ADA AND NFPA 72
20) THE MAXIMUM NUMBER OF POWERED DEVICES FOR EACH INITIATION CIRCUIT IS: 20
21) THE BUILDING IS NOT FIRE PROTECTION SPRINKLERED
22) ALL HVAC & FAN COIL UNITS GREATER THAN 2,QOOCFM HAVE BEEN PROTECTED.
23) AUDIBLE SIGNAL SHALL BE MINIMUM OF 75 dB OR 15dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR
5dBA ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS
(WHICHEVER IS GREATER), MEASURED 5ft A.F.F. IN THE OCCUPIABLE AREA
CEILING CHARACTERISTICS:
i ALL CEILINGS ARE LESS THAN 10' AND ARE FLAT
PROJECT SOPE OF WORK:
• INSTALL ADDITIONAL FIRE ALARM DEVICES PER MASTER PERMIT SCOPE OF WORK
SYMBOL DESCRIPTION MODEL MANUFACTURER
E FAC
FIRE ALARM CONTROL
MFA -6024
NAPCO
E Esq
FIRE SYSTEM REMOTE ANNUNCIATOR
RP -6000
NAPCO
E.
FAC
NAC BOOSTER POWER SUPPLY
SK -5495
SILENT KNIGHT
OP
PHOTO SMOKE SENSOR
429CT
ESL /GE
E
MANUAL STATION RED — S/A
BG -12
FIRELITE
E\ 0
AUDIBLE VISUAL 24VDC 75CD — RED 1 HZ
P2475 —W
SYSTEM SENSOR
E\ �
�0
VISUAL ONLY 24VDC 75CD — RED 1 HZ
52475 —W
SYSTEM SENSOR
DD
P
DUCT MOUNTED PHOTO SMOKE DETECTOR
DI- 1100ACDC
SYSTEM SENSOR
N\0
AUDIBLE VISUAL 24VDC MULTI —CD — RED 1 HZ
P2R
SYSTEM SENSOR
N\
VISUAL ONLY 24VDC MULTI —CD — RED 1 HZ
SR
SYSTEM SENSOR
cad
A
FIRE A SYSTEM IS
4 U .�
5 d
0
O
v
a
0
rr
j
L L d
z a 0 O 0
E
N NEW E = EXISTING ER = EXISTING RELOCATED WP = WEATHERPROOF
SECTION A -A
1. Wall Assembly -- The 1 or 2 hr fire —rated gypsum wallboard /stud wall assgjnbly shall be constructed of
the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs
in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to
consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2 -1/2 in• wide and
spaced max 24 in. OC. When steel studs are used and the diam of opening exceeds the width of
stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the
vertical studs and screw— attached to the steel studs at each end. The framed opening in the wall
shall be 4 to 6 in. wider and 4 to 6 in. higher than the diam of the penetrating item such that,
when the penetrating item is installed in the opening, a 2 to 3 in. clearance is present between the
penetrating item and the framing on all four sides.
B. Gypsum Board* -- 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type,
thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual
U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 32-1/4 in.
for steel stud walls. Max diam of opening is 14 -1/2 in. for wood stud walls.
The F Rating of the firestop system is equal to the fire rating of the wall assembly.
2. Through— Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or
eccentrically within the firestop system. The annular space shall be min 0 in. to max 2 -1/4 in. Pipe may
be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater
than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall
assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe -- Nom 30 in, diam (or smaller) cast or ductile iron pipe.
C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit.
D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe -- Nom 6 in. diam (or smaller) regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in. thickness of fill material applied within the
annulus, flush with both surfaces of wall. At the point or continuous contact locations between pipe and
wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe wall interface on both surfaces
of wall .
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC -- FS —One Sealant
*Bearing the UL Classification Mark
Reproduced by HILTI, Inc. Courtesy of
FIREST4P SYSTEMS
Underwriters Laboratodes, Inc. I IS
V
WIRING LEGEND
DESCRIPTION
COND
SYMBOL
ELECTRICAL
TYPE
cd
CLASSIFICATION
2 CONDUCTOR 14 AWG FPLR CABLE
Q? p V
1 ( +) RED, 1 ( —) BLACK
a'
0
SIGNAL CIRCUIT
OR
B
FPLR
T_
2 CONDUCTOR 14 AWG THWN
4)
1 ( +) RED, 1 ( —) BLACK
L _0 -- EL
Q R N 3)
-•'� O
INITIATION CIRCUIT
2 CONDUCTOR 18 AWG FPLR CABLE
A
FPLR
AUXILIARY POWER CKT
2 CONDUCTOR 14 AWG FPLR /CMR CABLE
P
FPLR
AUXILIARY POWER CKT
1 ( +) RED, 1 ( —) BLACK
w
cad
WET LOCATION WIRING LEGEND, INCLUDING UNDERGROUND [300.5(B)]
DESCRIPTION
COND
SYMBOL
ELECTRICAL
TYPE
cd
CLASSIFICATION
2 CONDUCTOR 14 AWG VNTC CABLE
Q? p V
1 ( +) RED, 1 ( —) BLACK
a'
0
SIGNAL CIRCUIT
OR
WB
FPL
T_
2 CONDUCTOR 14 AWG THWN
4)
1 ( +) RED, 1 ( —) BLACK
L _0 -- EL
Q R N 3)
-•'� O
INITIATION CIRCUIT
2 CONDUCTOR 18 AWC VNTC SHIELDED CABLE
WA
FPL
AUXILIARY POWER CKT
2 CONDUCTOR 14 AWG VNTC CABLE
WP
FPL
�
0
1 ( +) RED, 1 ( —) BLACK
w
cad
A
FIRE A SYSTEM IS
EXISTING AND SHALL BE
REMOTE STATION
MONITORED PER MDFR
ORDINANCE
FIRE ALARDA SYS17EM TO BE
iNSTALLED 11?1 ACCORDANCE Wri"14
NFPA 71; 70 101-
�t N ..: s i .. �,1.r•�t o
REWORK
DRAWINGS
Z FIRE
❑ ELECTRICAL
DATE: 07 -20 -2009
U U rJ U
U V
System No. C —AJ -1226
F RATING = 3 —HR.
T RATING = 0 —HR.
L Rating At Ambient — Less than 1 CFM /Sq Ft U U
L Rating At 400 F — 4 CFM /Sq Ft ....
U U
A 3
413 F_ 46 1
2
iV
4A
3 �A
SECTION A —A
1. Floor or Wall Assembly Min 4 -1/2 in. thick reinforced lightweight
or normal weight (100 -150 pcf) concrete. Wall may also be constructed
of any UL Classified Concrete Blocks *. Max diam of opening is 32 in.
2. Metallic Sleeve (Optional) Nam 32 in. diam (or smaller) Schedule 40
(or heavier) steel sleeve cast or grouted into floor or wall assembly,
flush with floor or wall surfaces.
3. Through- Penetrant One metallic pipe or conduit to be installed either
concentrically or eccentrically within the firestop system. The annular space
between pipe or conduit and periphery of opening shall be min 0 in.
(point contact) to max 1 -7/8 in. Pipe may be installed with continuous point
contact. Pipe or conduit to be rigidly supported on both sides of floor or wall
assembly. The following types and sizes of metallic pipes or conduits may be used:
A. Steel Pipe Nom 30 in. diarn (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe Norrl 6 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit Nom 6 in. diam (or smaller) steel conduit.
F. Conduit Nam 4 in. diam (or smaller) steel electrical metallic tubing (EMT).
4. Firestop System The firestop system shall consist of the following:
A. Packing Material Min 4 in. thickness of min 4 pcf mineral wool
batt insulation firmly packed into opening as a permanent form.
Packing material to be recessed from top surface of floor or from
both surfaces of wall as required to accommodate the required
thickness of fill material.
B. Fill, Void or Cavity Material* -- Sealant Min 1/4 in, thickness
of fill material applied within the annulus, flush with top surface of
floor or with both surfaces of wall. At the point or continuous
contact locations between pipe and concrete, a min 1/4 in, diam
bead of fill material shall be applied at the concrete /pipe interface
on the top surface of floor and on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC - FS -One Sealant
*Bearing the UL Classification Marking
��II 5 I Fj�o
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
FIREiiOP SYSTEMS c YL Us
80" A.F.F. OR
6" BELOW CEILING —
(WHICHEVER IS LOWER)
STROBE OR
HORN /STROE
PULL STATIO
48" A.F.F.
ADA HEIGHT REQUIREMENTS
NO SCALE
U
e U V
U V
U
U U U
U
C
I
0 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 r 24 25 26 27 28 29 ':,31 32 33 34 35 36 37 38 39
,
F
G
H
J
K
L
M
N
0
0
9
0
S
UNITED
FIRE
COMMUNICATIONS
E F0001087
701 S.W. 27 AVENUE - M33
MIAMI, FLORIDA 33135
PHONE (305) 541 -8375
RON IWSSE, SET
CONTRACTOR
AMSAFE
of MIAMI, Inc
P.Q. Box 550189
Fort Lauderdale, FL
EF0000103
U_
Revisions
No. Date Description
1 08 -18 -09 Fire Review Comments
2 07 -20.09 Fire Review Comments
T
U 4
V
W
0/
Z
1 A -
i