Loading...
10-920-031ELECTRICAL NOTES. 1. ALL WORK TO BE IN ACCORDANCE WITH THE N.E.C. AND ALL APPLICABLE RULES, REGULATIONS AND ORDINANCES. 2. ALL WIRE TO BE', COPPER THW, THWN, THHN OR XHHW, #12 MIN. ALL CONDUITS TO BE EITHER RIGID OR EMT AS ALLOWED BY THE CODES. ALL EMTS, FLEX CONDUITS, MC CABLES AND NON — METALLIC CONDUITS MUST HAVE GROUND WIRE AS PER N. E. C.. THIS IS A NON — RESIDENTIAL JOB AND HENCE RQMEX OR SIMILAR WIRING METHODS SHALL NOT BE USED FOR THIS PROJECT. 3. ALUMINUM CONDUCTORS ARE NOT ALLOWED. 4. VERIFY THE STRUCTURAL, CEILING AND OTHER DETAILS THAT MAY AFFECT THE MOUNTING AND PLACEMENT OF LIGHTING FIXTURES. VERIFY THE RECESSED FIXTURES TO ASCERTAIN THAT THEY WILL GO WITH THE CEILING OR WALL DETAILS ALL FIXTURES TO BE MOUNTED IN A NEAT, EYE — PLEASING MANNER AT HEIGHTS AND LOCATIONS THAT ARE SUBJECT TO THE FINAL CONFIRMATION BY THE OWNER OR ARCHITECT IN THE FIELD. 5. PROVIDE DISCONNECTS, FUSES, OVERLOAD PROTECTION AND PROPER CONTROL & POWER WIRING FOR OTHER EQUIPMENT SUCH AS' HVAC, MECHANICAL AND ANY OTHER SPECIAL EQUIPMENT THAT MAY BE USED FOR THIS PROJECT. VERIFY THE ROUGH --IN DETAILS, ACTUAL LOCATIONS, WIRE SIZES AND ANY OTHER DETAILS WITH THE RESPONSIBLE TRADES AND FOLLOW THE ACTUAL INSTALLATION INSTRUCTIONS FOR THE EQUIPMENT BEING INSTALLED. COORDINATE WITH THE OTHER TRADES. 6. ALL DISCONNECTS, FIXTURES, AND OTHER ELECTRICAL COMPONENTS THAT ARE SUBJECT T0, THE OUT SIDE WEATHER ELEMENTS MUST HAVE THE WEATHERPROOF ENCLOSURES. 7. FOR HOMERUNS MOVER 80 FEET, USE ONE SIZE LARGER WIRE. FOR HOMERUNS OVER 135 FEET, USE TWO SIZE LARGER WIRE. 8. PROVIDE PROPER GROUNDING FOR ALL EQUIPMENT, RACEWAYS ETC. AS PER NEC. 9. ALL BREAKERS THAT ARE TO BE USED TO SUPPLY LIGHTING LOADS MUST BE RATED FOR SWITCHING DUTY. PROVIDE LOCK —ON DEVICES FOR THE NIGHT LIGHT CIRCUIT AND OTHER CIRCUITS THAT MAY BE SO DIRECTED BY THE ARCHITECT. NOTE: ELECTRICAL CONTRACTOR TO CONTACT EQUIPMENT MANUFACTURER FOR SPECIFICATION SHEETS FOR PROPER INSTALLATION/ WIRE SIZE AND AMPS. CONTACT ENGINEER IMMEDIATELY IF DIFFERENT THAN SHOWN" ON PLANS. PROVIDE NEW SERVICE WEATHERHEAD FOR OVERHEAD SERVICE GC TO REVIEW AT BID NEW 4 "RGSC 1 4 , . NIR , �• • myffiol 1 EXISTING OVERHEAD SERVICE ENTRANCE LATERAL PROVIDE NEW 600A CT CABINET IN ACCORDANCE WITH LADWP REQUIREMENTS 120 /240V /1 /3W /NEMA 3R PROVIDE NEW METER S �� CAN AND SOCKET TO COMPLY WITH 1" C. LADWP REQUIREMENT NEW 3" RGS CONDUIT WITH 3#500KCMIL CU X1/0 CU— GROUND PER NEC 600A/2P DISC, N3R 600AF K K ■:i K K K # # NEW (BY GC) PANEL — PANEL "A" NEW SUB PANEL ° PANEL "B" PANEL A FLUSH MOUNTED USE / AREA C/B o j 600 AMP 120/240V, A B 1 PH, 3W 600 NIo a/B USE / AREA QmRimm 2 35 YOGURT #2_ RIGHT 4 z 240/60/1 PH YOGURT #1— RIGHT 35 z 1 1950 35 2 240/60/1 PH 3 1724 2 240/60/1 PH 1950 YOGURT #1— LEFT 35 z 5 1794 4 72, YOGURT #2 — LEFT 1794 s 240/60/1 PH 7 YOGURT #6— LEFT,,, 240/60/1 PH 240/60/1 PH �� $ YOGURT #3— RIGHT 35 2 240/60/ 1 y PH ' 1794 35 2 YOGURT #3— LEFT 9 1794 10 240/60/1 PH 11 �r,l ,9 ,.w YOGURT #7— LEFT 1794 240/60/1 PH 240/60/1 PH 1994 12 YOGURT #4-- RIGHT 35 2 13 1950 12 35 2 YOGURT 4— LEFT 13 1794 14 240/60/1 PH 15 SPARE 240/60/1 PH EXTERIOR SIGNAGE 17x4 1s SERVICE LIGHTING #1 201 1� 4200 WALK —IN 'LIGHTING(F) 40 z RTU-r1 NEW SPARE 2Q1 1s WATER HEATER �° z 19 2° 2 3120 SEE MFG SPECS 1$ 4200 20 2 SEE MFG 21 312o ' Zo1 SYRUP — z2 WAFFLE MACHINE 2g/ 1 23 201 WALK —IN REFRIG. 2q1 WALK —IN LIGHTING(R) WALK --IN FREEZER 60o z4 SCALES 20 1 25 195 KITCHEN LIGHTING yj REF. DISPLAY #1 SPARE 1217 2s POS MACHINES 201 27 29 1 COUNTER COOLER z 1 COLD PAN SPARE 302 z8 DINING LIGHTING #1 29/ 1 29 550 SPARE' zo1 SPARE PARTY ROOM RECPT 201 3o DINING LIGHTING 2 Ni 1 35 2 4B0 2° 1 FLYTRAPS SPARE 200 32 TIME CLOCK 20 1 33 200 z5o® z0 1 GENERAL RECEPT. 35 2 600 34 TMB 201 35 YOGURT #8— LEFT 1794 29/ 1 UPLIGHT @ SOFFIT 3s 1200 3s KITCHEN RECEPT. z 1' 12050 3s SPARE 201 SERVICE LIGHTING #2 `� 38 RESTROOM LIGHTING 2 °1 39 SPACE 30 z SUB PANEL B 25646 40 PARTY RM LIGHTING 2 1 41 300 40 SPACE 300 AMP 41 42 TOTAL LOAD PER PHASE 52908 1 53484 153484 VA /120V — 445.7A 42 # -- LIGHTING FACTORED AT 125% * -- HIGHEST MOTOR LOAD FACTORED AT 125% K -- KITCHEN EQUIPMENT FACTORED AT 65% OF -LOAD NOTE: ELECTRICAL CONTRACTOR TO CONTACT EQUIPMENT MANUFACTURER FOR SPECIFICATION SHEETS FOR PROPER INSTALLATION/ WIRE SIZE AND AMPS. CONTACT ENGINEER IMMEDIATELY IF DIFFERENT THAN SHOWN ON PLANS. EXISTING 600A, 120/240V, 1—PH, 3W DISCONNECT SWITCH FOR SERVICE ENTRANCE REMOVE EXISTING TENANT --_ SPACE PANEL FIELD VERIFY EXACT ____ __________ __ _.. -- EXISTING W I R EWAY � - -- --- - -___, - - -T EXISTING r--------- TENANT I PANEL I I � M M Il l 11 M I1 M 1 1 M 1 1 1 I I I I 1 1 If If I I I I I I I i I I i i it 11 1 1 I I I - -- )�� )�� ) )�� )� MCB T I i I T I I 4 I I t L_..,.. —_- - __ __ J L ------- J I 11 I I. I I{ l I I I 1 i L ------ J I - - - -- L ------------- ----------------------------- -- EXISTING METERS ---- ---� � -- _----_____ ___________________� I I I FOR TENANT SPACES REMOVE EXISTING CONDUCTORS c ----- EXISTING GROUND AND ABANDON CONDUIT IN PLACE I PER NEC REQUEST FOR UTILITY TO ABANDON METER SOCKET NEW 4 C. WITH PROPOSED ROUTING AT BLDG COORDINATE WITH BUILDING OWNER PATCH ASPHALT AND RESTORE TO ITS ORIGINAL CONDITION M m K K # # NOTE: GC MUST OBTAIN CUT SHEETS OF YOGURT MACHINES PRIOR TO START OF WORK NOTE: GC TO OBTAIN SHOP DRAWINGS OF WALK —IN AND CONFIRM ELECTRICAL REQUIREMENTS NOTE: GC SHALL OBTAIN AND VERIFY ELEC LOADS OF WATER HEATER AND RTU DURING BID PROCESS NOTE: ALL NEW ELECTRICAL WORK TO BE PERFORMED AFTER CITY AND UTI LITY COMPANY REVIEW AND WRITTEN APPROVAL IS COMPLETE PROVIDE NEW 120/240V PANELS TO BE LOCATED IN REMODELED TENANT SPACE UNDER THIS CONTRACT NEW NEW TENANT TENANT PANEL A PANEL B MLO 3 #21 1#8G) 1 -1/4' C. K K K 11 j , W ., K U K ,.. > ? � F.4 '� 'r 9 CD f Fy�9 n al a PANEL A FLUSH MOUNTED USE /AREA c/B No 1300 AMP 120/24OV, 1 PH, 3W 300 �! A B �o c/B USE j AREA YOGURT #5— RIGHT 35 2 1 1950 35 2 YOGURT #5 --' LEFT 240/60/1 PH 1724 2 240/60/1 PH 3 1794 4 YOGURT #6— RIGHT 35 1994 2;. YOGURT #6— LEFT,,, 6 240/60/1 PH 7 1950 240/60/ 1 y PH ' 1794 YOGURT #7— RIGHT 35 2 9 1950 !'' 35 „ 2 �r,l ,9 ,.w YOGURT #7— LEFT 1794 10 240/60/1 PH 11 240/60/1 PH 1950 12 SPARE X01 13 20 1 SPARE 14 EXTERIOR SIGNAGE 201 1s 201 WALK —IN 'LIGHTING(F) soo° 1s SPARE 2Q1 17 2° 2 WALK —IN REFRIG. 920 1$ WALKIN FREEZER 20 2 19 600 ' 920 — 21 900 201 WALK —IN REFRIG. 22 WALK --IN FREEZER 2 °1 23 201 KITCHEN LIGHTING 300 24 SPARE 20 1 25 - 29 1 COUNTER COOLER 900 26 SPARE zo1 27 201 SPARE' _ 2s PARTY ROOM RECPT 201 a9 35 2 GLYCOL MACHINE z5o0 30 SPARE zo 1 31 - SEE MFG. SPECS z5o® 32 YOGURT #8— RIGHT 35 2 33 35 YOGURT #8— LEFT 1794 34 240/60/1 PH 3s 240/60/1 PH 1950 3s SPARE 20 1 37 `� 2° SPARE SPACE 2° 1 39 — 40 2 RTU — 2 4200 40 SPACE 2 °1 41 SEE MFG SPECS 4200 42 TOTAL LOAD PER PHASE 25316 25646 25646 , W ., K U K ,.. > ? � F.4 '� 'r 9 CD f Fy�9 n al a # — LIGHTING FACTORED AT 125% * — HIGHEST MOTOR LOAD FACTORED AT 125% K — KITCHEN EQUIPMENT FACTORED AT 65% OF LOAD NOTE: IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL EQUIPMENTIi SPECIFICATIONS AND COMPARE WITH ELECTRICAL DRAWINGS. CONTACT PROJECT MANAGER AND ENGINEER IMMEDIATELY 'IF DISCREPANCIES OCCUR. RK-1 Fuses specify "Bussman LPN -rk -1 NOTED #= MECHANICAL EQUIPMENT AT 125 GC TO REVIEW ALL ELECTRICAL SPECIFICATIONS AND EQUIPMENT SHEETS FO'R REQUIRED ELECTRICAL NEEDS. PRIOR TO CONSTRUCTION, CONSULT DESIGNER AND TENANT FOR POSSIBLE SUB PANEL MAY BE NEEDED. NOTES: 1. GROUND PER NEC AND LOCAL CODES. 2. DEBATE CONDUCTOR AS REQUIRED ONE -SINE DIAGRAM (1 -PHASE SERVICE) FOR AMBIENT TEMPERATURE TYPE SHALL COMPLY 3. CONDUIT NO SCALE WITH CODE AND SUITABLE FOR ENVIRONMENT. NOTE: SUBCONTRACTOR TO PROVIDE LOCK OUT AND TAG OUT SYSTEM ONCE BUILDING BECOMES ENERGIZED AND SHALL BE RESPONSIBLE FOR MAINTAINING "SAFE WORK" ENVIRONMENT. NOTE: GENERAL CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY EXISTING CONDITIONS DURING BID PROCESS — COORDINATE WITH LANDLORD SCOPE OF WORK NOTE: GENERAL CONTRACTOR SHALL VERIFY EXISTING ELECTRICALS +������ CONDITIONS DURING BID PROCENta. MENCHIE'S S`v v NAME tq BE'R , �.> :. a � �m VA/ 12 0V -- 214A . # — LIGHTING FACTORED AT 125% * — HIGHEST MOTOR LOAD FACTORED AT 125% K — KITCHEN EQUIPMENT FACTORED AT 65% OF LOAD NOTE: IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL EQUIPMENTIi SPECIFICATIONS AND COMPARE WITH ELECTRICAL DRAWINGS. CONTACT PROJECT MANAGER AND ENGINEER IMMEDIATELY 'IF DISCREPANCIES OCCUR. RK-1 Fuses specify "Bussman LPN -rk -1 NOTED #= MECHANICAL EQUIPMENT AT 125 GC TO REVIEW ALL ELECTRICAL SPECIFICATIONS AND EQUIPMENT SHEETS FO'R REQUIRED ELECTRICAL NEEDS. PRIOR TO CONSTRUCTION, CONSULT DESIGNER AND TENANT FOR POSSIBLE SUB PANEL MAY BE NEEDED. NOTES: 1. GROUND PER NEC AND LOCAL CODES. 2. DEBATE CONDUCTOR AS REQUIRED ONE -SINE DIAGRAM (1 -PHASE SERVICE) FOR AMBIENT TEMPERATURE TYPE SHALL COMPLY 3. CONDUIT NO SCALE WITH CODE AND SUITABLE FOR ENVIRONMENT. NOTE: SUBCONTRACTOR TO PROVIDE LOCK OUT AND TAG OUT SYSTEM ONCE BUILDING BECOMES ENERGIZED AND SHALL BE RESPONSIBLE FOR MAINTAINING "SAFE WORK" ENVIRONMENT. NOTE: GENERAL CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY EXISTING CONDITIONS DURING BID PROCESS — COORDINATE WITH LANDLORD SCOPE OF WORK NOTE: GENERAL CONTRACTOR SHALL VERIFY EXISTING ELECTRICALS +������ CONDITIONS DURING BID PROCENta. MENCHIE'S S`v v NAME tq BE'R , �.> :. a � �m