10-920-0300 T L0 00 Z) J V) z w CL 0 I- 0 w n_ ELECTRICAL NO I t5a 1. ALL WORK TO BE IN ACCORDANCE WITH THE N.E.C. AND ALL APPLICABLE RULES, REGULATIONS AND ORDINANCES. 2. ALL WIRE TO BE COPPER THW, THWN, THHN OR XHHW, #12 MIN. ALL CONDUITS TO BE EITHER RIGID OR EMT AS ALLOWED BY THE CODES. ALL EMTS, FLEX CONDUITS, MC CABLES AND NON— METALLIC CONDUITS MUST HAVE GROUND WIRE AS PER N. E. C.. THIS IS A NON— RESIDENTIAL JOB AND HENCE ROMEX OR SIMILAR WIRING METHODS SHALL NOT BE USED FOR THIS PROJECT. 3. ALUMINUM CONDUCTORS ARE NOT ALLOWED. 4. VERIFY THE STRUCTURAL, CEILING AND OTHER DETAILS THAT MAY AFFECT THE MOUNTING' AND PLACEMENT OF LIGHTING FIXTURES. VERIFY THE RECESSED FIXTURES. TO ASCERTAIN THAT THEY WILL GO WITH THE CEILING OR WALL DETAILS ALL FIXTURES TO BE MOUNTED IN A NEAT, EYE — PLEASING, MANNER AT HEIGHTS AND LOCATIONS THAT ARE SUBJECT TO THE FINAL CONFIRMATION BY THE OWNER OR ARCHITECT IN THE FIELD. 5. PROVIDE DISCONNECTS, FUSES, OVERLOAD PROTECTION AND PROPER CONTROL & POWER WIRING FOR OTHER EQUIPMENT SUCH AS HVAC, MECHANICAL AND ANY OTHER SPECIAL EQUIPMENT THAT MAY BE USED FOR THIS PROJECT VERIFY THE ROUGH —IN DETAILS, ACTUAL LOCATIONS, WIRE SIZES AND ANY OTHER DETAILS WITH THE RESPONSIBLE TRADES AND FOLLOW THE ACTUAL INSTALLATION INSTRUCTIONS FOR THE EQUIPMENT BEING INSTALLED. 'COORDINATE WITH THE OTHER TRADES. 6. ALL DISCONNECTS, FIXTURES, AND OTHER ELECTRICAL COMPONENTS THAT ARE SUBJECT TO THE OUT SIDE WEATHER ELEMENTS MUST HAVE THE WEATHERPROOF ENCLOSURES. 7. FOR HOMERUNS OVER 80 FEET, USE ONE SIZE LARGER WIRE. FOR HOMERUNS OVER 135 FEET, USE TWO SIZE LARGER WIRE. 8. PROVIDE PROPER GROUNDING FOR ALL EQUIPMENT, RACEWAYS ETC. AS PER NEC. 9. ALL BREAKERS THAT ARE TO BE USED TO SUPPLY LIGHTING LOADS MUST BE RATED FOR SWITCHING DUTY. PROVIDE LOCK —ON DEVICES FOR THE NIGHT LIGHT CIRCUIT AND OTHER CIRCUITS THAT MAY BE SO DIRECTED BY THE ARCHITECT. NOTE: ALL NEW ELECTRICAL WORK TO BE PERFORMED AFTER CITY AND UTILITY COMPANY REVIEW AND WRITTEN APPROVAL IS COMPLETE K 11 I< f: .- .�. -•AI �w►1r1 A IVGYY GLGIi l I \IVnL 1 ra.L L PANEL A SURFACE MOUNTED 400 AMP 120 24OV, 30, USE AREA C/B NO A B C 4W 400AMC6 AIC 10,000 No C/B USE / AREA YOGURT #1 — RIGHT 20 3 1 LIGHTING 4,620 1.25 5,775 V2O YOGURT #4 — RIGHT 1.25 iao0 2 240V /3PH 3 8,530 MECH EQUIPMENT 28,040 240V /3PH 28,040 1800 4 1.25 5 KITCHEN EQUIPMENT 1800 0.65 59,904 TOTAL (VA) 1800 8 YOGURT #1 — LEFT 20 3 7 2040 20 3 7 20 31 YOGURT #4 - LEFT N 2040 2040 s 240V /3PH 9 2°4° 2040 10 240V /3PH 2040 2040 11 2040 s 20 1 2040 2040 12 YOGURT #2 — RIGHT 73. 13 .201 20 2 20 3 YOGURT #5 - RIGHT I 1800 14 24OV /3PH 15 1960 so0 240V/1 PH 240V /3PH PARTY ROOM LTG 1a o 1B 17 17 1200 1800 2 °1 WALK —IN REF EVAP 20 1 1800 .18 YOGURT #2 —LEFT 73 3 19 WALK —IN FREEZER YOGURT #7 — LEFT 3 20 3 YOGURT #5 — LEFT 20040 20 240V /3PH 21 RECEPT 2040 22 240V /3PH 12 2040 22 23 23 2040 2040 20 1 2040 24 1200 24 40 2 EXIST RTU -1 YOGURT #3 — RIGHT 20 3 2s 1 S 25 4200 26 240V /3PH 27 SPACE SYRUP MACHINES 27 240V/1 PH 16 4200 28 1 201 2a 28 1800 100 2 PANEL C 201 7020 30 YOGURT #3 — LEFT 20 3 31 30 201 240V/1 PH SPACE B40 32 240V /3PH 33 201 _ 32 40 2 EXIST RTU -2 SPACE 4200 34 33 21 2040 _ 240V/ 1 P H 4200 38 SPARE SPACE ., 7-31 GLYCOL MACHINE SPACE 900 37 36 22 3300 38 SPACE SPACE 39 37 - 240V /3PH 38 3300 40 SPACE SPACE 41 39 — 24 SPARE = 3300 42 TOTAL LOAD PER PHASE 34310 30820 33640 34310 VA /120V = 286 A 201 NOTE: PROVIDE FEED —THRU LUGS TO FEED PANEL b PROVIDE PLACARDS --- FOR SERVICES AS SHOWN, MODIFY DESCRIPTIONS TO REFLECT ACTUAL INSTALLATION LOAD SUMMARY LOAD DESCRIPTION CONNECTED D A DEMAND AOR LOAD (VA) LIGHTING 4,620 1.25 5,775 EXTERIOR SIGN LTG 1,200 1.25 1,500 GENERAL POWER 8,530 1.0 8,530 MECH EQUIPMENT 28,040 1.0 28,040 LARGEST MECH EQUIP 9,900 1.25 12,276 KITCHEN EQUIPMENT 92,160 0.65 59,904 TOTAL (VA) 144,450 1300 116,025 116,025 VA / (240V X 1.73) = 279 -AMPS SERVICE 2 OF 2 120/240V, 3 -PH, 4W 400 AMPS SERVICE 1 OF 2 IS LOCATED IMMEDIATELY TO THE RIGHT l � PROVIDE NEW 120/240V PANELS TO BE LOCATED IN REMODELED TENANT SPACE UNDER THIS CONTRACT 0 SERVICE 1 OF 2 120/24OV, 1 -PH, 3W 400 AMPS SERVICE 2 OF 2 IS LOCATED IMMEDIATELY TO THE LEFT PROVIDE NEW SERVICE '- WEATHERHEAD FOR OVERHEAD SERVICE GC TO REVIEW AT BID PROVIDE NEW 320A FEED -THRU- METER IN ACCORDANCE WITH FLP REQUIREMENTS 120 /24OV/3/4W /NEMA 3R NEW 400A/24OV /3P 3F SERVICE ENTRANCE RATED DISCONNECT SWITCH, NEMA 3R ENCLOSURE FUSE AT 400A, FRN LOCATE NEAR EXISTING SERVICE DISCONNECT SO THEY ARE GROUP MOUNTED K K � K < H r /1T1"•1I'1AI nAAlrl 0 IVGYY GELD I lm%l nL 1 v%1mL.L. + PANEL B SURFACE MOUNTED 1400 AMP 120 240V, 30, 4W MLO AIC 10,000 CIR USE / AREA C/o NO A B C NO C/B USE /AREA 3" C. WITH 20 3 i USE / AREA 11500KCMIL, 2 G 73, NEW NEW NEW TENANT TENANT TENANT PANEL C PANEL A PANEL B MLO MCB - - MLO -- 1-1/4" C. WITH 3" C. WITH 2#2, 1 #8G 1500G KCMIL, KITCHEN RECEPTS 1800 l � PROVIDE NEW 120/240V PANELS TO BE LOCATED IN REMODELED TENANT SPACE UNDER THIS CONTRACT 0 SERVICE 1 OF 2 120/24OV, 1 -PH, 3W 400 AMPS SERVICE 2 OF 2 IS LOCATED IMMEDIATELY TO THE LEFT PROVIDE NEW SERVICE '- WEATHERHEAD FOR OVERHEAD SERVICE GC TO REVIEW AT BID PROVIDE NEW 320A FEED -THRU- METER IN ACCORDANCE WITH FLP REQUIREMENTS 120 /24OV/3/4W /NEMA 3R NEW 400A/24OV /3P 3F SERVICE ENTRANCE RATED DISCONNECT SWITCH, NEMA 3R ENCLOSURE FUSE AT 400A, FRN LOCATE NEAR EXISTING SERVICE DISCONNECT SO THEY ARE GROUP MOUNTED K K � K < H r /1T1"•1I'1AI nAAlrl 0 IVGYY GELD I lm%l nL 1 v%1mL.L. + PANEL B SURFACE MOUNTED 1400 AMP 120 240V, 30, 4W MLO AIC 10,000 CIR USE / AREA C/o NO A B C NO C/B USE /AREA YOGURT #6 — RIGHT 20 3 i AIC 10,000 USE / AREA c/B 73, YOGURT #8 — RIGHT H a 7A j, {: 1800 2 240V /3PH 3 USE 1800 KITCHEN /RR LTG 240V /3PH 201 1800 4 5 1800 201 KITCHEN RECEPTS 1800 8 1300 DINING LIGHTING 20 3 YOGURT #8 - LEFT N YOGURT #6 - LEFT 20 3 7 2040 s 240V /3PH 9 500 2°4° a 240V /3PH 2040 10 11 2040 s 20 1 2040 12 YOGURT #7 - RIGHT V20 13 1800 .201 20 2 WALK —IN REFRIG 14 240V /3PH 15 RECEPT 1960 so0 240V/1 PH s PARTY ROOM LTG 16 2 °1 17 1200 2 °1 WALK —IN REF EVAP 20 1 RECEPT 1s _20/ V2 WALK —IN FREEZER YOGURT #7 — LEFT 3 19 2040 B0 20 240V /3PH 21 RECEPT 2960 240V/1 PH 12 RECEPT - POS 22 0 21 23 2040 20 1 WALK —IN FRZ EVAP 20 1 1200 24 320 3o 2 WATER HEATER SPACE 1 S 25 200 2500 26 SPACE SYRUP MACHINES 27 16 SPARE 240V/1 PH 1 201 2500 28 SPACE 29 18 201 SCALES SPACE - 30 201 19 SPACE SPACE 1650 31 201 _ 32 SPACE SPACE 33 21 _ 34 201 COUNTER COOLER SPARE SPACE SPACE 35 900 - 36 22 SPACE SPACE 37 23 _ 38 SPACE SPACE - ROOF 39 15900 24 SPARE = 40 15900 SPACE VA /120V = 116 A SPACE TOTAL LOAD PER PHASE 201 41 13880 42 113880 _ PANEL CHEDULE/LOAD CALCULATION LEGEND• # — LIGHTING (CONTINUOUS LOAD) AT 1257. * — LARGEST MOTOR AT 125% K — KITCHEN EQUIPMENT (MORE THEN 6) AT 65% PER NEC 220.56 -*-- — EXISTING OVERHEAD SERVICE ENTRANCE LATERAL EXISTING 400A, 120 24OV, 1 -PH, 3W NEW 4" DISCONNECT SWITCH RGS C FOR SERVICE ENTRANCE - -_ -_ EXISTING WIREWAY 1 II li- li I M1 I I I I I M 11 M I I M I I M 1 1 M I �� I I 1 I I I I I I I I I I _ I I I I I I I I I I I I I I I J L 1 1 1 I I I � I I I- I I TA I NEW 3" RGS C. I I I L- J L - -J L- J L WITH 3 #500KCMIL + L , -- I V— EXISTING c 1/0 CU -� GERUND TO EXISTING TENANT PANELS ROUND = NO CHANGE -- PER NEC NOTES: 1. GROUND PER NEC AND LOCAL CODES. 2. DERATE CONDUCTOR AS REQUIRED FOR AMBIENT TEMPERATURE 3. CONDUIT TYPE SHALL COMPLY WITH CODE AND SUITABLE FOR ENVIRONMENT. ONE -SINE NO SCALE DIAGRAM (3 -PHASE SERVICE) # # # # # # IVGYY PANEL C RECESSED MOUNTED 100 AMP 120/24OV, 1�, 3W MLO AIC 10,000 USE / AREA c/B No A C `3111 a 7A j, {: No c/B USE /AREA KITCHEN /RR LTG 201 1 z 201 KITCHEN RECEPTS 1300 DINING LIGHTING 201 3 201 RECEPT —MUSIC 500 a SERVICE AREA LTG 201 5 s 20 1 RECEPT — TIME CL soo SERVICE AREA LTG .201 7 201 RECEPT — TMB so0 s PARTY ROOM LTG 2 °1 9 10 20 1 RECEPT — DINING 1200 WALK —IN LIGHTING 2D1 11 300 201 RECEPT - REF DISP 12 RECEPT - POS 0 21 13 14 20 1 COLD PAN 320 RECEPT 20 1 S 200 20 1 SYRUP MACHINES 600 16 SPARE 1 201 17 18 201 SCALES 200 EXTERIOR SIGN 201 19 1650 201 WAFFLE MACHINE 20 201 21 201 COUNTER COOLER SPARE 900 22 SPARE 201 23 201 RECEPT - ROOF 200 24 SPARE 201 25 26 201 SPARE _ SPARE 201 27 201 SPARE _ 28 201 29 30 201 SPARE SPARE _ SPACE 31 SPACE _ 32 33 - 34 SPACE SPACE - 35 - SPACE SPACE - 3s 37 - 3s SPACE SPACE - 39 - SPACE SPACE - 40 41 42 SPACE SPACE TOTAL LOAD PER PHASE 7690 7020 7690 VA /120V = 64 A NOTE: GC MUST OBTAIN CUT SHEETS OF YOGURT MACHINES PRIOR TO START OF WORK NOTE: ELECTRICAL CONTRACTOR TO CONTACT EQUIPMENT MANUFACTURER FOR SPECIFICATION SHEETS FOR PROPER INSTALLATION/ WIRE SIZE AND AMPS. CONTACT ENGINEER IMMEDIATELY IF DIFFERENT THAN SHOWN ON PLANS. NOTE: IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL EQUIPMENT SPECIFICATIONS AND COMPARE WITH ELECTRICAL DRAWINGS. CONTACT PROJECT MANAGER AND ENGINEER IMMEDIATELY IF DISCREPANCIES OCCUR. RK -1 Fuses specify L'Bussman LPN -rk -1 NOTE: GC TO OBTAIN SHOP DRAWINGS OF WALK —IN AND CONFIRM ELECTRICAL REQUIREMENTS NOTE: GC SHALL OBTAIN AND VERIFY ELEC LOADS OF WATER HEATER AND RTU DURING BID PROCESS NOTE: GENERAL CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY EXISTING CONDITIONS DURING BID PROCESS — COORDINATE WITH LANDLORD SCOPE OF WORK NOTE: = MECHANICAL EQUIPMENT AT 125% GC TO REVIEW ALL ELECTRICAL SPECIFICATIONS AND EQUIPMENT SHEETS FOR REQUIRED ELECTRICAL NEEDS. PRIOR TO CONSTRUCTION, CONSULT DESIGNER AND TENANT FOR POSSIBLE SUB PANEL MAY BE NEEDED. NOTE: TYPED PANEL LABELS WILL BE PROVIDED FOR ALL PANELS. PANELS AND DISCONNECTS WILL BE LABELED WITH PHENOLIC PLASTIC PLATES. NOTE: SUBCONTRACTOR TO PROVIDE LOCK OUT AND TAG OUT SYSTEM ONCE BUILDING BECOMES ENERGIZED AND SHALL BE RESPONSIBLE FOR MAINTAINING "SAFE WORK" ENVIRONMENT. NOTE: GENERAL CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY EXISTING CONDITIONS DURING BID PROCESS — COORDINATE WITH LANDLORD SCOPE OF WORK NOTE: GENERAL CONTRACTOR SHALL FIELD VERIFY EXISTING ELECTRICAL CONDITIONS DURING BID PROCESS N^ < �- v w w z W p o J X �p _ja_ rn z w >- z m " r Q <z 1 cn,CO-) ) o _r V o Q z rn d- cn -J z U Q mot- Q <C 00 J wr` cn Z d Q n }oX:2 0 :2 I i