11-50-018mo MECHANICAL NOTES: PART -1 - GENERAL 1.1 GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE CONTRACT AND SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND TRADES SHALL APPLY AND BE PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFICATIONS AND THE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION OF THE MECHANICAL SYSTEMS. "PROVIDE" MEANS "FURNISH AND INSTALL". A.2 COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF NFPA, ASHRAE. ASME, ASPS. ASTM, OSHA, HRS, HEALTH AGENCIES, AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL CODES AND PERTAINING REGULATIONS ESSTABUSHED BY RULING AUTHORITIES HAVING JURISDICTION. CONTRACTOR SHALL ALSO MEET REQUIREMENTS OF OTHER RECOGNIZED STANDARDS WHERE SUCH REQUIREMENTS ARE MORE STRINGENT THAN THOSE CITED ABOVE. :P 1.3 WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN THEIR RESPECTIVE DISCIPLINES. WORK SHALL BE DONE IN A FIRST CLASS MANNER, FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT /ENGINEER. CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIALS REQUIRED FOR COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO CONNECTIONS TO RELATED WORK SUCH AS CONNECTION TO EXISTING SYSTEMS, EXCAVATIONS AND BACKFIWNG, DEWATERING OF EXCAVATED TRENCHES. 1.4 MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN MANUFACTURE. BEARING THE UNDERWRITER'S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE ACCEPTABLE AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON PLANS. SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED BY CONTRACTOR AS REQUIRED FOR COMPLETION OF THE WORK AT NO ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND COORDINATION OF DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING SHIPMENT OR INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO FACTORY FINISH, REPLACED WHERE NOT ACCEPTABLE. 1.5 PERMITS & INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF COMPLETE MECHANICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 1.6 EXISTING CONDITIONS: BEFORE BIDDING CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIAL OR LABOR. ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 1.7 UTILITY COMPANIES: BEFORE SUBMITTING BID CONTRACTOR SHALL CHECK WITH WATER, SEWER, GAS, ELECTRICAL, TELEPHONE, CABLE TV AND OTHER UTILITY COMPANIES SUPPLYING SERVICE TO THIS INSTALLATION TO DETERMINE INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COSTS TO BE INCLUDED IN THE BID. EXCEPT WHERE UTILITY REQUIREMENTS CHANGE AFTER SUBMITTAL, NO EXTRA PAYMENT WILL BE MADE TO THE CONTRACTOR FOR SUCH ITEMS. 1.8 PLANS: DRAWINGS ARE GENERALLY DIAGRAMMATIC, INTENDED TO SHOW APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. 1.9 INTERFERENCE: CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES SO THAT INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL, STRUCTURAL MEMBERS WILL BE AVOIDED. 1.10SHOP DRAWINGS: PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION, SUBMIT FOR REVIEW PROPERLY IDENTIFIED AND BOUND SHOP DRAWINGS AND MANUFACTURER'S LITERATURE GIVING SPECIFICATIONS, DETAILS, COMPLIANCE. UL APPROVAL, MATERIALS. FINISHES, ACCESSORIES AND INSTALLATION DIRECTIONS WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. FACTORY CERTIFIED PRINTS SHALL BE FURNISHED FOR ALL MAJOR ITEMS OF EQUIPMENT AND SPECIFIED. SUBMISSION OF EQUIPMENT FOR APPROVAL SHALL BE MADE COMPLETE AND ALL AT THE SAME TIME. 1.11SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUAUTY, APPEARANCE, PERFORMANCE AND DIMENSION. CONTRACTOR SHALL BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING. REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT/ENGINEER. DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN. CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK FOR OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY OF SUBSTITUTIONS; ARCHITECT/ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT/ENGINEER EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR SUBSTITUTIONS SHALL BE PAID BY CONTRACTOR. 1.12GUARANTEES: AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE ARCHITECT /OWNER. ENTIRE MECHANICAL WORK. INCLUDING PARTS AND LABOR, SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION AND WORKMANSHIP. WHERE APPLICABLE, LONGER GUARANTEES FOR CERTAIN COMPONENTS SHALL APPLY AS REQUIRED AND NOT BE REDUCED IN ANY WAY. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE TO THE OWNER AND SHALL INCLUDE REPLACEMENTS AND /OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 1.13RECORD DRAWINGS: MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES. USE COLORED PENS TO MARK CHANGES AT THE TIME OF EXECUTION AND DELIVER THE SET TO ARCHITECT/ENGINEER UPON COMPLETION. CONTRACTOR SHALL STAMP "AS BUILT ON PRINTS AND PLANS, DATE AND SIGN IN INK. PART 2 - PRODUCTS 2.1 EQUIPMENT: CONTRACTOR SHALL PROVIDE FOR A COMPLETE HVAC SYSTEM AS SPECIFIED ON PLANS INCLUDING BUT NOT LIMITED TO HVAC EQUIPMENT OF THE CAPACITIES SHOWN, DUCTWORK AND AIR DISTRIBUTION, FLUID SYSTEMS, REFRIGERANT AND RELATED SYSTEM UNES, TEMPERATURE AND HUMIDITY CONTROLS, FILTERS, MOTOR STARTERS, RELAYS, CONTACTORS AND ANY OTHER COMPONENTS REQUIRED. SUBMIT SHOP DRAWINGS FOR EQUIPMENT NOTED ABOVE AS REQUIRED. A. AIR HANDLING AND CONDENSING UNIT. INSTALLED ON APPROVED BASES WITH VIBRATION ISOLATORS, CONDENSATE DRAIN PAN WITH DUAL CONDENSATE DRAINS, AND STRUCTURAL SUPPORT AS NOTED ON PLANS. CONDENSING UNIT SHALL BE MOUNTED ON SUPPORT FRAME RECOMMENDED BY MANUFACTURER AND APPROVED BY RULING AUTHORITIES. B. HVAC EQUIPMENT SHALL PROVIDED WITH NON- CYCLING RELAY. BIRD SCREEN, RAIN HOOD, AND MANUAL OUTSIDE AIR DAMPERS AS REQUIRED. 2.2 FILTERS: THROWAWAY TYPE LOCATED IN AIR HANDLER OR AT RETURN AIR GRILL UNLESS OTHERWISE NOTED. FURNISH ONE (1) SPARE SET TO OWNER. 2.3 REFRIGERANT PIPING: "K" COPPER WITH WROUGHT COPPER SOLDER FITTINGS. INSULATE ALL REFRIGERANT SUCTION LINES WITHIN BUILDING SPACES WITH 3/4" ARMAFLEX OR APPROVED EQUAL. UNLESS OTHERWISE NOTED. 2.4 CONDENSATE DRAIN: "M" TYPE COPPER; PVC MAY BE USED FOR OTHER THAN AIR PLENUM INSTALLATIONS WHERE ALLOWED BY RULING AUTHORITIES. CONNECT PIPING FROM UNIT THROUGH A 3- INCH VENTED TRAP TO DRYWELL OR AS NOTED ON DRAWINGS. INSULATE CONDENSATE RUNS WITHIN ATTIC AND OTHER NON - CONDITIONED SPACES. 2.5 THERMOSTATS: HEAT /OFF /COOL AND FAN /AUTO /ON SWITCHES, TYPE AS REQUIRED PER SELECTED HVAC EQUIPMENT MANUFACTURER AND FULLY COMPATIBLE WITH HVAC SYSTEM COMPONENTS USED. MANUFACTURERS SHALL BE HONEYWELL, BARBER - COLEMAN OR APPROVED EQUAL MOUNT 5' -6" ABOVE FLOOR UNLESS OTHERWISE NOTED. 2.6 AIR DISTRIBUTION ACCESSORIES: TITUS, AIR GUIDE, METAL -AIRE, OR APPROVED EQUAL DIFFUSERS SHALL BE ELECTROSTATICALLY PAINTED ALUMINUM AND SHALL BE SUPPUED WITH MATCHING METAL MOUNTING BOOTS, COMPLETELY INSULATED. UNLESS OTHERWISE NOTED, SUPPLY REGISTERS SHALL BE INSTALLED WITH OPPOSITE BLADE DAMPERS. PROVIDE ADDITIONAL CONTROLS, CONNECTORS, PLENUM BOXES, ROUND TO SQUARE NECK CONNECTORS AND ADDITIONAL COMPONENTS REQUIRED FOR COMPLETE INSTALLATION. 2.7 DUCTWORK: PROVIDED IN ACCORDANCE WITH LATEST EDITION OF SMACNA "LOW VELOCITY DUCT CONSTRUCTION STANDARDS% ASHRAE, ASTM, NFPA, AND APPLICABLE PROVISIONS OF THE MECHANICAL CODE. A. GALVANIZED SHEET METAL• SUPPLY AND RETURN DUCTWORK. EXHAUST AND OUTSIDE AIR. DUCTWORK ABOVE ROOF SHALL BE WEATHERPROOFED AND PAINTED. INSULATION SHALL BE 1- 1/2" THICK RIGID ON INTERIOR. INSTALLED IN AN APPROVED MANNER. B. NON - METAWC DUCT. WHERE PREVIOUSLY APPROVED BY ARCHITECT /OWNER AND RULING AUTHORITIES, AIR CONDITIONING UNIT SUPPLY AND RETURN AIR DUCTS MAY BE UL APPROVED 1 -1/2" THICK FIBROUS GLASS DUCT BOARD TYPE 475. STAPLE AND TAPE ALL SEAMS AND SECTIONS AND APPLY TAPE WITH ROBIN -AIRE HEAT GUN SET AT 400- DEGREE F., INSTALLED PER MANUFACTURER'S INSTRUCTIONS. C. FLEXIBLE DUCT. FACTORY INSULATED 1 -1/2" MINIMUM FLEXIBLE DUCTWORK. CLASS 1 AIR DUCT, UL 181 APPROVED, SIMILAR TO OWENS- CORNING MODEL NO. INL -25, CERTIFIED CERTAFLEX OR APPROVED EQUAL DUCTWORK SHALL HAVE RESILIENT CORE OF CONTINUOUS INNER AIR BARRIER, JACKETED WITH A REINFORCED VAPOR JACKET. FIRE HAZARD CLASSIFICATION SHALL HAVE A FLAME SPREAD OF 25, SMOKE RATING OF 50, IN ACCORDANCE WITH ASTM C518 -70, ASTM E -84, AND UL 723 STANDARDS. 2.8 DUCTWORK INSTALLATION: A. DUCTWORK SIZES SHOWN ARE INSIDE DIMENSIONS. B. EXHAUST AND OUTSIDE AIR INTAKES SHALL BE GALVANIZED METAL IN ACCORDANCE WITH SMACNA STANDARDS, SCREENED WITH A CORROSION- RESISTANT MATERIAL NOT LARGER THAN 1/2" MESH. OUTDOOR AIR INTAKE SHALL BE A MINIMUM OF TEN (10) FEET FROM EXHAUSTS, FLUES, PLUMBING VENTS AND OTHER SOURCES OF EXHAUST. C. LONGITUDINAL SEAMS SHALL BE PITTSBURGH LOCK OR APPROVED EQUAL. LATERAL SEAMS SHALL BE SUP DRIVE OR STANDING. SUP SEAMS AND SHEET METAL SCREWS NOT PERMITTED. D. JOINTS AND SEAMS SHALL BE SEALED WITH FOSTER 30 -02 DUCT SEALANT APPLIED ABOVE 32 DEGREES FAHRENHEIT. E. DUCTS SHALL BE INDEPENDENTLY SUPPORTED TO PREVENT SAGGING, KINKING AND OTHER PHYSICAL DAMAGE. WHERE PREVIOUSLY APPROVED BY ENGINEER, USE OF FLEXIBLE DUCTS SHALL BE RESTRICTED ONLY FOR INDIVIDUAL BRANCH LENGTHS, MAXIMUM 10 FEET LONG. 2.9 DUCT INSULATION: A. AIR CONDITIONING DUCTS SHALL BE EXTERNALLY INSULATED WITH R -6 2 -INCH BY 1 -1/2" LB FIBROUS GLASS FLEXIBLE BLANKET WITH UL APPROVED FIRE RESISTING ALUMINUM FOIL VAPOR SEAL FACING. B. ROUND DUCTS SHALL BE WRAPPED WITH R -6 2 -INCH BY 3/4 LB BLANKET AS NOTED ABOVE. JOINTS SHALL BE SEALED WITH FIRE RESISTING MASTIC AND 3 -INCH WIDE FOIL BACKED TAPE. 2.10 AIR CONDITIONING SUPPLY DUCT ELBOWS SHALL BE PROVIDED WITH APPROVED TURNING VANES. RECTANGULAR ELBOWS EQUAL TO OR GREATER THAN 45- DEGREES SHALL HAVE DOUBLE THICKNESS TURNING VANES. ROUND ELBOWS INSIDE RADIUS SHALL BE NOT LESS THAN 1.5 TIMES THE WIDTH OF THE DUCT. 2.11 BRANCH TAKE -OFFS AND SUPPLY AIR REGISTERS SHALL BE PROVIDED WITH INDIVIDUAL ADJUSTABLE AIR SPUTTER MANUAL VOLUME BALANCING DAMPERS. ALL ADJUSTING AND CONTROL HARDWARE SHALL BE ACCESSIBLE. 2.12 PROVIDE CLAMPED FLEXIBLE CONNECTIONS BETWEEN DUCT AND FAN, DUCT AND MOTOR EQUIPMENT. DUCT AND COLLARS, AND DUCT AND SIMILAR EQUIPMENT THAT COULD TRANSMIT AND CAUSE VIBRATION AND NOISE. PART 3 - EXECUTION 3.1 TEST do BALANCE: CONTRACTOR SHALL PROVIDE AND PAY FOR AN NEBB OR AABC CERTIFIED INDEPENDENT CONTRACTOR REGULARLY AND EXCLUSIVELY ENGAGED IN THIS WORK TO ADJUST, TEST AND BALANCE ALL SYSTEMS AS SHOWN ON PLANS. TEST SHALL INCLUDE BUT NOT BE LIMITED TO START -UP AND TEST SYSTEM OPERATION IN ALL MODES IN CONJUNCTION WITH OTHER DISCIPLINES. CLEANING OF UNIT INSIDE AND OUT, POLISH ALL CHROME AND ENAMEL FINISHES, REFRIGERANT CHANGE AND PROPER CONTROLS OPERATION, LUBRICATION, ELECTRICAL SYSTEM TESTING FOR RELATED COMPONENTS, AND BALANCING OF CFM QUANTITIES. PROVIDE ANY ADDITIONAL MANUAL VOLUME DAMPERS OR DUCT ACCESSORIES AS REQUIRED TO ADJUST THE SYSTEM AS PER PLANS. AFTER COMPLETION, PROVIDE THREE (3) CERTIFIED COPIES OF REPORT, INCLUDING WORKSHEET AND SUBSTANTIATING DATA, TO ARCHITECT /OWNER AND ONE (1) CERTIFIED COPY TO ENGINEER. 3.2 VIBRATION ISOLATION: HVAC AND RELATED SYSTEMS COMPONENTS SHALL BE PROVIDED WITH VIBRATION ISOLATION DEVICES AS PER MANUFACTURER'S RECOMMENDATIONS. 3.3. ALL EXTERNAL EQUIPMENT COMPONENTS SHALL BE FACTORY FINISH PAINTED FOR WEATHER PROTECTION AND IN ACCORDANCE WITH ARCHITECTURAL PLANS. 3.4 CONTRACTOR SHALL MAKE ALL NECESSARY EXCAVATIONS, CUTTING AND REPATCHING AS NECESSARY FOR THE PROPER EXECUTION OF THIS WORK. 3.5 VOLUME CONTROL DAMPERS SHALL BE PROVIDED WHERE INDICATED AND SHALL BE EQUIPPED WITH LOCKING ADJUSTMENTS, READILY ACCESSIBLE. 3.6 CONTRACTOR SHALL GUARANTEE THAT ALL PIPE AND DUCTWORK SHALL OPERATE FREE OF VIBRATIONS, RATTLES, PULSATIONS OR OBJECTIONABLE NOISES. 3.7 ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND PROVIDED BY THIS CONTRACTOR. EQUIPMENT REMOVAL FROM THE JOB SITE AND /OR DISPOSAL SHALL BE THE RESPONSIBIUTY OF THE CONTRACTOR. COORDINATE WITH OWNER BEFORE COMMENCING WORK. 3.8 HVAC SYSTEM COMPONENTS AND EQUIPMENT SHALL BE CLEARLY AND PERMANENTLY IDENTIFIED. WITH EQUIPMENT NUMBER, 2" HIGH LETTERS ON SIDES OF THE UNIT AS APPLICABLE AND IN ACCORDANCE WITH OWNER'S REQUIREMENTS. 3.9 EQUIPMENT SHALL BE SUPPORTED FROM STRUCTURAL MEMBERS. NO WEIGHT SHALL BE PLACED ON THE ROOFING MATERIALS, INSULATION. CEILING GRID, ROOF DECKING OR SIMILAR COMPONENTS. 3.10 BEFORE COMMENCING WORK CONTRACTOR SHALL COORDINATE WITH OWNER EXTENT OF WORK WITHIN AND OUTSIDE BUILDING SPACE TO DETERMINE PROVISIONS REQUIRED. MECHANICAL REMODELING AND DEMOLITION NOTES: PART 1 - GENERAL 1.1 ALL WORK AND MATERIALS SHALL BE NEW AND PROVIDED BY THIS CONTRACTOR UNLESS OTHERWISE NOTED AS EXISTING TO REMAIN OR BE RELOCATED. WORK SHALL ALSO INCLUDE THE REMOVAL AND DISPOSAL OF MATERIALS FROM THE SITE AND THOROUGH CLEANING OF THE PREMISES UPON COMPLETION OF THE WORK AS DIRECTED BY ARCHITECT /OWNER. 1.2 WORK SHALL INCLUDE PROVISIONS OF ALL MATERIALS, CUTTING. EXTENSIONS. CONNECTIONS, PATCHING, PAINTING, REPAIRING, ADAPTING AND OTHER WORK INCIDENTAL THERETO, TOGETHER WITH SUCH TEMPORARY CONNECTIONS AS MAY BE REQUIRED. 1.3 ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON PLANS AND /OR SPECIFICATIONS BUT CONSIDERED NECESSARY FOR COMPLETION OF THE WORK IN THE PROPER MANNER SHALL BE PROVIDED BY THIS CONTRACTOR WITHOUT ADDITIONAL CHARGE. 1.4 WHERE PRESENT WORK IS DAMAGED IN THE EXECUTION OF THIS WORK IN THE PROPER MANNER SHALL BE PROVIDED BY THIS CONTRACT, OR WHERE OPENINGS ARE LEFT DUE TO THE REMOVAL OF PIPES, EQUIPMENT OR APPARATUS, THE SAME SHALL BE REPAIRED OR CLOSED UP TO CORRESPOND IN MATERIAL., QUALITY, SHAPE AND FINISHWITH THAT OF SIMILAR AND ADJOINING WORK, UNLESS OTHERWISE CALLED FOR. WHERE DAMAGE IS UNREPAIRABLE, NEW ITEMS OR EQUIPMENT SHALL BE PROVIDED. PROVIDE ALL NECESSARY WATERPROOFING, FIRE STOPPING AND SEALING OF PENETRATIONS LEFT FROM REMOVED EQUIPMENT OR PRODUCED BY THIS WORK. 1.5 INTERRUPTION OF EXISTING SERVICES AND /OR OPERATION OF FACIUTIES SHALL BE KEPT TO A MINIMUM. CONTRACTOR SHALL FURNISH ALL MATERIALS REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTION OF EXISTING SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES, AND THE WORK OF MAKING FINAL CONNECTIONS TO THE NEW WORK SHALL BE DONE ONLY AT SUCH TIMES PERMITTED AND SCHEDULED IN ADVANCE BY THE ARCHITECT /OWNER WITHOUT ADDITIONAL COST. CARE MUST BE USED IN REMOVING SERVICES TO AREAS BEING DEMOLISHED SO THAT SERVICES TO OTHER AREAS WHICH MIGHT BE SERVED THROUGH THESE AREAS WILL NOT BE INTERRUPTED. PART 2 - MECHANICAL 2.4 EXISTING COMPONENTS TO BE REUSED SHALL BE REFURBISHED TO "AS NEW CONDITION; WHERE DAMAGE AND/OR OPERATIONAL RESTRICTIONS CANNOT JUSTIFY REUSE OF EXISTING COMPONENTS, REPLACE SUC COMPONENTS WITH EQUAL NEW EQUIPMENT. A. EXISTING DUCTWORK TO BE REUSED SHALL BE THOROUGHLY CLEANED INSIDE AND OUT. REPLACE WHERE MOISTURE CONDENSATION AND /OR PHYSICAL DAMAGE IS DEEMED UNACCEPTABLE. B. DIFFUSERS AND REGISTERS SHALL BE REMOVED, CLEANED, AND PAINTED AS REQUIRED BEFORE BEING REINSTALLED. C. MOTORS AND VENTILATION FANS SHALL BE CLEANED; AIR CONDITIONING UNITS SHALL HAVE COIL, FAN SECTION AND PLENUM SECTIONS CLEANED; HEATERS AND COMPRESSORS SHALL BE CHECKED AND REPAIRED AS REQUIRED; FILTERS IN A/C UNIT INCLUDING OUTSIDE AIR SYSTEM SHALL BE REPLACED. 2.5 TEST AND BALANCE OF EXISTING AIR CONDITIONING UNITS SHALL INCLUDE CHECKING AND CORRECTION AS REQUIRED OF THE FOLLOWING COMPONENTS: A. GENERAL- CLEAN THE AIR HANDUNG UNIT AND OUTSIDE CONDENSING COIL LUBRICATE ALL MOVING PARTS AS REQUIRED AND RECOMMENDED BY MANUFACTURER. CHECK CONDITION OF BELTS, ADJUST TENSION, AND REPLACE AS REQUIRED. CHECK REFRIGERANT OPERATING PRESSURES; VERIFY PROPER CHARGE AND CERTIFY THERE ARE NO LEAKS. B. AIR SIDE: CHECK EVAPORATOR SUPERHEAT. CHECK CONDITION OF THE EXISTING DUCTWORK EXISTING MAIN TRUNK AND CLEAN AS REQUIRED. VERIFY TEMPERATURE AT THE RETURN AND SUPPLY AIR SYSTEMS MEETS DESIGN CRITERIA. CHECK OUTSIDE AIR IS BALANCED ACCORDINGLY. REPLACE EXISTING FILTERS AND RECOMMEND FILTER MAINTENANCE SCHEDULE. C. CONTROLS: CHECK VOLTAGE AND AMPERAGE TO ALL MOTORS, HEATERS AND RELATED ELECTRICAL COMPONENTS TO ASSURE SATISFACTORY OPERATION. CHECK OPERATION OF THE COMPRESSOR CONTACTOR. START CAPACITOR AND RELAYS. INSPECT THERMOSTAT AND OBSERVE ITS OPERATION. CHECK OPERATION OF ALL SAFETY CONTROLS. CHECK ALL WIRING AND CONNECTIONS INSIDE THE UNIT. D. CONDENSATE: VERIFY PANS AND DRAIN UNES ARE OPEN AND FREE OF ALGAE, RUST AND SIMILAR OBSTRUCTIONS, AND THAT DRYWELL IS OPERATING PROPERLY. CLEAN SYSTEM AS REQUIRED. m MAIN DUCT AIR FLOW DO NOT KINK FLEX. DUCT (SEE PLANS FOR SIZE) IDLE p r r •- FLEX DUCT CEIUNG DIFFUSER MA 00 DIFFUSER ROUND DUCT CONNECTION DETAIL N.T.S. CONCRETE SLAB. QR NG STRUC;. :." : .� 5' MAX. WASHER 2" EXPANSION NAIL AX AG: 24 GA. HANGER STRAP 1/2" PER FT °FLEXIBLE DUCT OF SUPPORT 1 -1/2" BAND CLAMP NOTE SUPPORT SYSTEM SHALL NOT DAMAGE DUCT OR CAUSE OUT OF ROUND SHAPE FLEXIBLE DUCT SUPPORT DETAIL N.T.S 1 �i'r m, NEOPRENE NTH • •- •OD .■ m NOTES: 1. PROVIDE BACKDRAFT DAMPER WITH BIRDSCREEN FOR TOILET EXHAUST 2. FLASH AND SEAL WALL AND ROOF CAP CEILING CAP DETAILS NTS If 11111111 chkplot: 01/17/2011 m PmVI I MA Z ,c to � v v W w W 06 !Z � 4J 'E c Z v W 0 ay c n d" < C) � -@ ° J rn FE # 9a3 .. �, CD co C) .N o - E co 0 ate e- . s. � o a e s o °�► m.:s , n d" < 5M FE # 9a3 ate e- . s. � o a e s o °�► m.:s ,