Loading...
11-50-013ELECTRICAL LEGEND SYMBOL DESCRIPTION S TOGGLE SWITCH, QUIET TYPE. 20A. 125/277. MH= 48 "AFF SD DIMMER SWITCH. QUIET TYPE. 20A. 125/277. MH= 48"AFF S3 3 -WAY SWITCH, SAME AS ABOVE S31) 3 -WAY DIMMER SWITCH, SAME AS ABOVE DUPLEX RECEPTACLE GROUNDING TYPE, 20A, MH =18' AFF DUPLEX RECEPTACLE. SAME AS ABOVE, MH =42" AFF cD MH= 42 "AFF SPECIAL PURPOSE RECEPTACLE, RATING TO MATCH CB AS E NOTED, MINIMUM 20A 240V IP LION T' JUNCTION BOX FLUSH MOUNTED TELEPHONE AND DATA JACK OUTLET. TYPE AS SELECTED BY OYMER, 3/4' EC "AFF . WITH PULL STRING TO TELEPHONE BOARD LION, MH= 18 ® CABLE/TV JACK OUTLET, TYPE AS SELECTED BY OWNER, 3/4" EC WITH PULL STRING TO TELEPHONE BOARD UON. MH= 18'AFF ® 120V EXHAUST FAN TIED TO BATHROOM CIRCUIT coo .-� FUSED DISCONNECT SWITCH RATED 250V. INDICATING 2 POLES. 60A SWITCH, 50 AMP FUSES, NEMA -1. "3R' INDICATES NEMA -3R 60 POLES, SWITCH SIZE AND FUSES SIZED AS NOTED ON PLANS. PANELBOARD, DESCRIP11ON PER PANEL SCHEDULE _r- HOMERUN TO PANEL, TICKS INDICATE PHASE AND NEUTRAL NO TICKS INDICATE PHASE AND NEUTRAL CIRCUIT c) CONDUIT RUN CONCEALED IN CEILINGS, WALLS OR SLAB -- CONDUIT RUN UNDERGROUND •� FLEXIBLE CONDUIT GFI GROUND FAULTINTERRUPTOR WP WEATHER PROOF, NEMA 3R VP VAPOR PROOF Q 120V LIGHTING FIXTURE SURFACE/RECESSED MOUNTED. 10OW MAX VERIFY WITH ARCH /OWNER FOR FINAL LIGHT TYPE SELECTION ®P CLG. J-BOX W/FIXTURE, SUPPORT AS PER NEC, FOR FUTURE co PENDANT OR FAN/LTG FIXTURE, 20OW MAX. SEE NOTES. Q 120V SCONCE UGHTING FIXTURE, BRACKET MOUNTED • FAN AND LIGHT SELECTED BY INTERIOR DESIGNER /ARCHITECT, LL 30OW MAX SMOKE DETECTOR �✓ 120V GARBAGE DISPOSAL INDIVIDUALLY SWITCHED ELECTRICAL PLAN ELECTRICAL NOTES: 1. SCOPE OF WORK IS INTERIOR REMODELING OF AREA AS SHOWN ON THESE DWGS. EXISTING SERVICE AND PANEL ARE ADEQUATE FOR THIS REMODELING TO REMAIN. 2. IONIZATION TYPE SMOKE DETECTOR WITH BATTERY BACK -UP WIRED TO UNSWITCHED ARC -FAULT 120V CIRCUIT. INTERLOCKED TO ACTIVATE IN ALARM ANNUNCIATION. EXTERIOR 3. ALL LIGHTlNG SHALL BE RATED FOR EXTERIOR LOCATION. 4. BEFORE COMMENCING WORK CONTRACTOR SHALL COORDINATE WITH ARCH /OWNER AND SELECTED MANUFACTURER FAN/LTG VENDOR FOR CLG. J -BOX AND PENDANT FIXTURE SUPPORTS AS PER NEC 370,410, 422. FAN W/UGHT 20OW MAX. 5, CONTRACTOR SHALL PROVIDE 60A -2P DISCONNECTS FOR AHU'S AND 60A -2P -3R DISCONNECTS FOR CU'S AS SHOWN ON PLANS. BEFORE COMMENCING WORK CONTRACTOR SHALL VERIFY EQUIPMENT NAMEPLATE FOR EXACT FUSES AND SIZES. 6. CONTRACTOR TO COORDINATE AND VERIFY LIGHTING TYPE AND MODELS, AND CEILING ARCH/OWNER. 7. UNLESS OTHERWISE NOTED CONTRACTOR SHALL PROVIDE 8. ALL NEW OUTLETS SHALL COMPLY WITH NEC 2008 ART 406.11 TAMPER RESISTANT AS SPECIFIED IN ART 210.52. UNLESS OTHERWISE NOTED ALL CKT NUMBERS REFER TO PANEL "A" (TYP) chkplot: 01/17/2011 PP,OlCr NMfF, (10) 112 Cot rrA_r ror sJA�.'_ v'9 -Y &L PI.WW 9016 Af rrF, rrl-r rt'FM F'r'og -Mt o WW i d Ally Wok', t7AS 111112011 SCAI.F ♦`° gTr1® oo r a e P n .- ,- cD U E ii T' Z . co c t� LL coo .-� a c) Z •� ., co W uj LL Lu ,r Z p "� _c Z c L1t —T U C) 00 co �t ak ca as Z o to Q 0o c? — o E Q H a�i U t7AS 111112011 SCAI.F ♦`° gTr1® • « �°« a e P Q i g « ��M 35 P = P °! •r4 ate I e ✓n� 6