09-1112R-003NEW ELECTRICAL PANEL SCHEDULE wP3w
TYPE : AQ, G. E. MAINS M. L.O.
MOUNTING : SURFACE 22,000 A.I.C. BUS RATING 100 AMP
LOCATION : STORAGE ROOM VO LTAG E 120/24OV-3PHASE-4WIRE
CU IN 3"
WIRE &
COND. SIZE
LOAD
(V.A.)_
PO
7�TRIP
4-#350MCM THWN
CU + 1-#2 CU GROUND
IN 3"
CKT.
No.
1 - #2 THWN CU GROUND IN 1/2-
WIRE &
COND. SIZE
DESCRIPTION
DESCRIPTION
4-#3 THWN CU +
1 - #8 CU GROUND IN
1
1/4-
1
4-#3/0 THWN CU
+ 1 - #4 CU GROUND
IN
2-
EXISTING
4-#1/0 THWN CU
+ 1-#6 CU GROUND
IN
2-
SPACE(HIGH-LEG)
EXISTING. VERIFY MINIMUN
OF
3
4
4-#3 THWN CU +
1 - #8 CU GROUND IN
1
1/4-
EXISTING. VERIFY MINIMUN
OF
EXISTING
EXISTING
4-#3/0 THWN CU
+ 1 - #4 CU GROUND
IN
2-
1 2Q
EXISTING. VERIFY MINIMUN
OF
EXISTING
4-#1/0 THWN CU
RECEPTACLES
IN
2-
1,000
1 20
7
8
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
9
10
SPACE(HIGH-LEG)
RECEPTACLES
EXISTING
EXISTING
1,000
1 20
11
12
1 20
1,000
EXISTING
EXISTING
RECEPTACLES
EXISTING
EXISTING
1,000
1 20
13
14
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
15
16
OEM=
SPACE(HIGH-LEG)
DRINKING FOUNTAIN-���M
EXISTING
EXISTING
1,000
_!,--2'0
17
18
1j-20
1,000
EXISTING
EXISTING
EXISTING
EXISTING
1,000
1 20
19
20
1 20
1,000
ROOF RECEPT.
EXISTING
SPACE(HIGH-LEG)
MM
21
22
SPACE(HIGH-LEG)
EXISTING
MM
1,000
1 20
mm=
24
j,---2'0
1,000
-FIRE -DAMPER
EXISTING
EXISTING
EXISTING
1,000
1 20
25
26
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
27
28
SPACE(HIGH-LEG)
EXISTING
EXISTING
1,000
_!,,--2-0
29
30
LOAD CALCULATION PANEL 'P3'
CONTINUOUS LOAD AT 125% = 6,030 X 1.25 = 7,538 VA
NON CONTINUOUS LOAD AT 100% = 6,000 VA
TOTAL DEMANDED LOAD = 13,538 VA
TOTAL DEMAND AMPS = 57 AMPS PER PHASE
NOTE : ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH CIRCUIT, POSITION AND CONNECTION.
ALL PANELS SHALL HAVE UPDATED BRANCH CIRCUITS LABELS.
LOAD CALCULATION MAIN 1/2
PANEL "AC- 47,000 VA
PANEL " Pl" 45,000 VA
• 14I .0
LOAD CALCULATION MAIN 2/2
ELEVATOR 30,000 VA
PANEL "P2" 60,038 VA
H11106NIAWNEWT, 1- 11 ■9
61711:40111MAIM,
J
RELOCATED
NEW EXISTIN
ELEVATOR MACHINE ROOM
(G)
PANEL - "P3" PANEL -'P2'
120/240 V 120/240 V
100 A 200 A B LITSTEIN
3 PH, 4 W 3 PH, 4 W
MLO MLO
- -�,_ DESIGN
22,000 AIC
22,000 AIC { { (EXISTING)
ASSOCIATES
DISC SWITCH
3M
100 Architecture
NEW FPL SERVICE
-J
3PH, 120/24OV, OPEN DELTA Interior Design
41350MCM THWN CU IN 3-
285 Sevilla Avenue
NEW FPL SERVICE SECOND FLOOR Coral Gables, FI 33134
3PH, 120/240V, OPEN DELTA
4#350MCM THWN CU IN 3' (305) 444-4433
MAIN ELECTRICAL ROOM
NEW NEW
EXISTING GUTTER
-J (EXISTING) (EXISTING)
ELECTRICAL ELECTRICAL
4 5 5 6
METER METER PANEL - "AC" PANEL - "P1"
<
120/240 V 120/240 V
-1 (EXISTING) WIN Gil !-(151-ffN-G)-�
(EXISTING) EX 200 A
3 PH, 4 PH, 4 W
W 3
NEW NEW MLO MLO
DISC SWITCHI DISC SWITCH CBkr CBkr
200 AMPS 150 AMPS
3P1M 32M
L DISC SWITCH L DISC
3P 3P IG 22,000 A]
C-j
3PAM 3PAM
L L J L J L J
300 300
MAIN 1/2 MAIN 2/2 F
-J
3
L-Elp
FIRST FLOOR
J2/0 CU IN 3/4-C-4
J2/0 CU IN 3/4-C
COLD WATER
PIPE
(2) 5/8- X 10' DRIVEN GROUND
RODS, COPPERCLAD, TO BE
SEPARATED 6'-0" MINIMUM
#2/0 CU IN 3/4-C TO BUILDING
STEEL FOUNDATION
EXISTING ELECTRICAL PANEL SCHEDULE wMw
4-#350MCM THWN
CU IN 3"
WIRE &
COND. SIZE
LOAD
(V.A.)_
PO
7�TRIP
4-#350MCM THWN
CU + 1-#2 CU GROUND
IN 3"
CKT.
No.
1 - #2 THWN CU GROUND IN 1/2-
LOAD
(V.A.)
WIRE &
COND. SIZE
DESCRIPTION
4-#3 THWN CU +
1 - #8 CU GROUND IN
1
1/4-
1
4-#3/0 THWN CU
+ 1 - #4 CU GROUND
IN
2-
EXISTING
4-#1/0 THWN CU
+ 1-#6 CU GROUND
IN
2-
SPACE(HIGH-LEG)
EXISTING. VERIFY MINIMUN
OF
3
4
4-#3 THWN CU +
1 - #8 CU GROUND IN
1
1/4-
EXISTING. VERIFY MINIMUN
OF
EXISTING
EXISTING
4-#3/0 THWN CU
+ 1 - #4 CU GROUND
IN
2-
1 2Q
EXISTING. VERIFY MINIMUN
OF
EXISTING
4-#1/0 THWN CU
+ 1-#6 CU GROUND
IN
2-
J
RELOCATED
NEW EXISTIN
ELEVATOR MACHINE ROOM
(G)
PANEL - "P3" PANEL -'P2'
120/240 V 120/240 V
100 A 200 A B LITSTEIN
3 PH, 4 W 3 PH, 4 W
MLO MLO
- -�,_ DESIGN
22,000 AIC
22,000 AIC { { (EXISTING)
ASSOCIATES
DISC SWITCH
3M
100 Architecture
NEW FPL SERVICE
-J
3PH, 120/24OV, OPEN DELTA Interior Design
41350MCM THWN CU IN 3-
285 Sevilla Avenue
NEW FPL SERVICE SECOND FLOOR Coral Gables, FI 33134
3PH, 120/240V, OPEN DELTA
4#350MCM THWN CU IN 3' (305) 444-4433
MAIN ELECTRICAL ROOM
NEW NEW
EXISTING GUTTER
-J (EXISTING) (EXISTING)
ELECTRICAL ELECTRICAL
4 5 5 6
METER METER PANEL - "AC" PANEL - "P1"
<
120/240 V 120/240 V
-1 (EXISTING) WIN Gil !-(151-ffN-G)-�
(EXISTING) EX 200 A
3 PH, 4 PH, 4 W
W 3
NEW NEW MLO MLO
DISC SWITCHI DISC SWITCH CBkr CBkr
200 AMPS 150 AMPS
3P1M 32M
L DISC SWITCH L DISC
3P 3P IG 22,000 A]
C-j
3PAM 3PAM
L L J L J L J
300 300
MAIN 1/2 MAIN 2/2 F
-J
3
L-Elp
FIRST FLOOR
J2/0 CU IN 3/4-C-4
J2/0 CU IN 3/4-C
COLD WATER
PIPE
(2) 5/8- X 10' DRIVEN GROUND
RODS, COPPERCLAD, TO BE
SEPARATED 6'-0" MINIMUM
#2/0 CU IN 3/4-C TO BUILDING
STEEL FOUNDATION
EXISTING ELECTRICAL PANEL SCHEDULE wMw
TYPE AQ, G.E. MAINS : M.L.O.
MOUNTING SURFACE 22,000 A.I.C. BUS RATING : 200 AMP
LOCATION STORAGE ROOM VOLTAGE : 120/24OV-3PHASE-4WIRE
DESCRIPTION
WIRE &
COND. SIZE
LOAD
(V.A.)_
PO
7�TRIP
C
No-
A B
C
CKT.
No.
POL
7TRIP
LOAD
(V.A.)
WIRE &
COND. SIZE
DESCRIPTION
EXISTING
EXISTING
1,000
1 20
1
2
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
3
4
SPACE(HIGH-LEG)
EXISTING
EXISTING
1,000
1 20
5
6
1 2Q
1,000
EXISTING
EXISTING
EXISTING
EXISTING
1,000
1 20
7
8
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
9
10
SPACE(HIGH-LEG)
EXISTING
EXISTING
1,000
1 20
11
12
1 20
1,000
EXISTING
EXISTING
EXISTING
EXISTING
1,000
1 20
13
14
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
15
16
SPACE(HIGH-LEG)
EXISTING
EXISTING
1,000
_!,--2'0
17
18
1j-20
1,000
EXISTING
EXISTING
EXISTING
EXISTING
1,000
1 20
19
20
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
21
22
SPACE(HIGH-LEG)
EXISTING
EXISTING
1,000
1 20
23
24
j,---2'0
1,000
EXISTING
EXISTING
EXISTING
EXISTING
1,000
1 20
25
26
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
27
28
SPACE(HIGH-LEG)
EXISTING
EXISTING
1,000
_!,,--2-0
29
30
j,--2'0
1,000
EXISTING
EXISTING
EXISTING
EXISTING
1,000
1 20
31
32
1 20
1,000
EXISTING
EXISTING
SPACE(HIGH-LEG)
33
34
SPACE(HIGH-LEG)
EXISTING
EXISTING
1,000
1 20
35
36
2,--2--'0-
400
#12-1/2"
ROOF RECEPT.
EXISTING PNL"L"
1
EXISTING
20,000
3
/100
37
38
_1, 20
1,000
EXISTING
EXISTING
39
40
SPACE(HIGH-LEG)
41
42 1
CONTROLLED BY
TIME CLOCK
THROUGH
LIGHTING
CONTACTOR
LOAD CALCULATION PANEL 'Pl'
CONTINUOUS LOAD AT 125% = OVAX 1.25 =OVA
NON CONTINUOUS LOAD AT 100% = 0 VA
TOTAL DEMANDED LOAD = 45,000 VA
TOTAL DEMAND AMPS = 110 AMPS PER PHASE
NOTE : ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH
CIRCUIT, POSITION AND CONNECTION,
ALL PANELS SHALL HAVE UPDATED
BRANCH CIRCUITS
LABELS.
ELECTRICAL
RISER
AND
PANEL
SCHEDULES
MR
NOTE:
PROVIDE SIGNS ON ALL ELECTRICAL PANELS
"CAUTION: B Phase has 190 Volts to Ground"
NOTE : ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH CIRCUIT, POSITION AND CONNECTION.
ALL PANELS SHALL HAVE UPDATED BRANCH CIRCUITS LABELS.
61),
t JECT NO; 0911-093
tt'
7%
I Ttt�.'
J" ilenglineenng
From Vision to Reality
4247 SW 71st AVENUE
Miami, Florida 33155
Tel, (305) 661-0800
Fax: (305) 661-0811
Emall: uci@ucieng.com
R.J. Miranda P.E. No. 35579
David A. Belsky P.E. No. 37234
EBOD04041
Professional Electrical and
Mechanical Engineers
project name
Existing Building
Renovation for
Continental
Fidelity
Corporation
5734 Sunset Drive
South Miami, Florida
project number
date
12/07/09
r e v i s i o n
11 REV. 5-25-10
REV. . ■�!lI�
iii REV. 10-18-10
drawn by
AR, FG, J.L, G.R
sheet title
ELECTRICAL RISER
AND PANEL
SCHEDULE
SCALE: 1/4n = 11-011
sheet number