12-742-014ELECTRICAL SPECIFICATIONS
GENERAL CONDITIONS:
A. THE REQUIREMENTS AS SET FORTH UNDER GENERAL CONDITIONS,
INSTRUCTIONS TO BIDDERS AND GENERAL REQUIREMENTS ARE A PART OF
THIS CONTRACT.
B. BIDS SHALL BE BASED ON A COMPLETE /FULL SET OF DRAWINGS.
C. CONTRACTOR MUST READ THE ENTIRE SPECIFICATIONS COVERING OTHER
BRANCHES OF WORK AND IS RESPONSIBLE FOR COORDINATION OF THE
WORK WITH WORK PERFORMED BY OTHER TRADES.
SCOPE OF WORK:
A. CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING, BIDS SHALL
SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS. ALL
REQUIREMENTS INCLUDING MODIFICATIONS WHICH ARE REQUIRED TO MEET
THE INTENT OF THE DRAWINGS AND SPECIFICATIONS ARE TO BE OBTAINED
PRIOR TO AND INCLUDED IN BID PRICE. FIELD VERIFY ALL EXISTING
ELECTRICAL AND TELEPHONE EQUIPMENT, LOCATIONS, CONDITIONS ETC,
FAILURE TO VISIT THE SITE SHALL NOT RELIEVE THE CONTRACTOR FROM ANY
RESPONSIBILITY IN THE PERFORMANCE OF THE ELECTRICAL WORK.
B. FURNISH ALL LABOR, MATERIALS, TESTING, EQUIPMENT, INCIDENTALS AND
TOOLS TO PERFORM ELECTRICAL WORK SHOWN, NOTED OR SCHEDULED FOR
A COMPLETE AND FINISHED INSTALLATION.
1. MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING ALL
COMPONENTS THEREOF, SHALL BE NEW AND AS SUCH APPEAR ON
THE UNDERWRITERS LABORATORIES LIST OF APPROVED ITEMS AND
SHALL BE SIZED IN CONFORMITY WITH REQUIREMENTS OF THE
LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND OTHER
APPLICABLE CODES, WHICHEVER ARE MORE STRINGENT.
C. THE WORK IS TO BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
NEC AND ALL APPLICABLE CODES.
D. INCLUDE ANY LABOR AND MATERIALS NOT SPECIFICALLY MENTIONED, BUT
NECESSARY TO PROVIDE A COMPLETE AND FULLY OPERATIVE ELECTRICAL
SYSTEMS.
PERMITS:
A. SECURE AND PAY FOR ALL REQUIRED PERMITS, FEES, ASSESMENTS
AND INSPECTION CERTIFICATES THAT RELATE TO THE ELECTRICAL
CONTRACT.
B. FURNISH APPROVED CERTIFICATE OF FINAL INSPECTION, AND TURN
OVER TO OWNER AT COMPLETION OF PROJECT.
DRAWINGS AND SPECIFICATIONS:
A. THIS ELECTRICAL PLANS ARE DIAGRAMMATIC, NOT SHOWING EVERY
ITEM IN EXACT LOCATION OR DETAIL. MEASUREMENTS AND
LOCATIONS MUST BE FIELD VERIFIED AND COORDINATED WITH
ARCHITECTURAL, PLUMBING, HVAC, FIRE PROTECTION, FIRE ALARM,
STRUCTURAL, AND OTHER BUILDING DRAWINGS.
E, LEAVE A #10 AWG PULL WIRE OR NYLON PULL STRING IN ALL EMPTY CONDUITS.
F. SECURE ALL RACEWAYS TO THE BUILDING STRUCTURE IN A RIGID AND SECURE
MANNER, USING FASTENERS SUCH AS "CADDY CLIPS" OR EQUAL.
G. FLASH AND COUNTERFLASH ALL RACEWAYS WHICH PENETRATE THE ROOF OR USE
PITCH POCKETS. INSURE THAT PENETRATIONS ARE COMPLETELY WEATHERPROOF.
ALL RACEWAY SYSTEMS EXPOSED TO THE WEATHER SHALL BE WEATHERPROOF.
PRIOR APPROVAL BY LANDLORD IS REQUIRED TO ADD ADDITIONAL EQUIPMENT
LOADS TO STRUCTURE OR TO MAKE HOLES IN EXISTING ROOF. NOTIFY
LANDLORD'S ROOFING CONTRACTOR AT LEAST 72 HOURS PRIOR TO ANY
REQUIRED ROOF WORK.
H. REVIEW ANY QUESTION REGARDING INSTALLATION WITH LULULEMON PM,
WIRE:
A. WIRE SHALL BE SINGLE CONDUCTOR COPPER WITH 600 VOLT INSULATION.
MINIMUM WIRE SIZE SHALL BE #14 AWG, ALL WIRE AND CABLE SHALL BE NEW
AND SHALL BE BROUGHT TO THE SITE IN UNBROKEN PACKAGES. ALL WIRING OF
ANY TYPE SHALL BE IN CONDUIT. NO STRANDED WIRE ALLOWED FOR #10 AND
#12 AWG.
MINIMUM WIRE SIZE — 20 AMP BRANCH CIRCUIT SHALL BE AWG LISTED SIZE
PER DISTANCE SHOWN BELOW. DISTANCE SHALL BE MEASURED FROM THE
PANELBOARD CIRCUIT BREAKER TO THE FARTHEST OUTLET.
a. #12 LESS THAN 100 FEET
b. #10 BETWEEN 100 — 150 FEET
c. #8 BETWEEN 150 — 250 FEET
d. #6 OVER 250 FEET
1. GENERAL WIRING SHALL BE THW OR THHN. (ALUMINUM CONDUCTORS
ARE NOT PERMITTED.)
B. WIRE CONNECTORS SHALL BE EQUAL TO SCOTCHLOCK FOR #8 AND SMALLER,
AND EQUAL TO T k B "LOCK —TITE" FOR #6 AND URGER.
C. THE USE OF SHARED NEUTRALS IS ACCEPTABLE FOR LIGHTING AND RECEPTACLE
CIRCUITS OTHER THAN GFCI AND ISOLATED GROUND CIRCUITS IF INSTALLED IN
ACCORDANCE WITH NEC.
D. ALL WIRING TO BE COLOR CODED AS FOLLOWS:
120/208 VOLT SYSTEM
NEUTRAL — WHITE
PHASE A BLACK
PHASE B RED
PHASE C BLUE
GROUND —GREEN
ISOLATED GROUND — GREEN WITH
YELLOW STRIPE.
LIGHTING:
A. INSTALL OWNER PROVIDE LIGHTING FIXTURES AND LAMPS. COORDINATE EXACT
LOCATION AND ALL MOUNTING REQUIREMENTS WITH ARCHITECT, OWNER, AND
MANUFACTURER PRIOR TO ROUGH —IN,
SHOP DRAWINGS:
ifl in
E
B.
LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURAL WITH
A. FOR SUBSTITUTIONS ONLY, SUBMIT FIVE COPIES OF MATERIAL LISTS
12GA WIRE SUPPORT TO OPPOSING CORNERS OF EACH RECESSED LIGHTING
AND SHOP DRAWINGS FOR MAJOR EQUIPMENT TO THE OWNER'S
FIXTURE IN SUSPENDED CEILINGS. INSTALLATION SHALL CONFORM TO THE
CONSTRUCTION MANAGER FOR APPROVAL PRIOR TO ORDERING
PROVISIONS OF THE BUILDING CODE.
EQUIPMENT, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS EARLY
z
0
ENOUGH IN PROJECT TO ALLOW AMPLE TIME FOR OWNER'S REVIEW
WITHOUT CAUSING TIME DELAYS OR CONFLICTS IN THE JOB PROGRESS.
SUBMITTALS SHALL BE IN ACCORDANCE WITH GENERAL CONDITIONS AND
WIRED
GROUND SYSTEM:
THE MANUFACTURERS LISTED ON THE DRAWINGS AND SHALL BEAR THE
STAMP OF THE CONTRACTOR SHOWING THAT HE HAS REVIEWED AND
A.
FURNISH AND INSTALL A COMPLETE WIRED GROUNDING SYSTEM FOR
APPROVED THEM' AND THAT THEY ARE IN CONFORMANCE WITH THE
ELECTRICAL EQUIPMENT AND CIRCUITS AS SHOWN ON THE DRAWINGS AND
CONTRACT DRAWINGS, LACK OF SUCH CONTRACTOR'S APPROVAL WILL
DESCRIBED GENERALLY BELOW.
BE CAUSE FOR REJECTION WITHOUT REVIEW BY THE OWNER.
B.
ALL GROUNDING CONDUCTORS SHALL BE GREEN, WHERE EXPOSED IN PANEL,
w
0
SWITCHBOARD, OUTLET, BOXES, ETC.
B. WHERE TRADE NAMES, BRANDS OF MANUFACTURERS OF EQUIPMENT OR
MATERIALS ARE SHOWN ON THE DRAWINGS OR SPECIFICATIONS THE
EXACT EQUIPMENT SHALL BE USED ON THE PROJECT. THE USE OF
C.
ALL ENCLOSURES AND NON— CURRENT CARRYING METALS TO BE GROUNDED.
ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO
CONDUIT SYSTEM TO BE ELECTRICALLY CONTINUOUS. ALL LOCK NUTS MUST CUT
REMOVAL /REPLACEMENT AT THE REQUEST OF THE OWNER'S
THROUGH ENAMELED OR PAINTED SURFACES ON ENCLOSURES. WHERE
CONSTRUCTION MANAGER (AT THE ELECTRICAL CONTRACTORS EXPENSE).
ENCLOSURES AND NON— CURRENT CARRYING METALS ARE ISOLATED FROM THE
CONDUIT SYSTEM, USE BONDING JUMPERS WITH APPROVED CLAMPS.
CONDUITS:
A. CONDUIT SHALL BE STANDARD STEEL RIGID, IMC OR EMT (THIN WALL)
ACCORDING TO LOCAL CODE AND LANDLORD REQUIREMENTS. CONDUIT
SHALL BE CONCEALED IN FINISHED AREAS, EXCEPT AS OTHERWISE
APPROVED BY ARCHITECT. USE RIGID CONDUIT IN ALL OPEN CEILING
CONDITIONS. RUN CONDUIT IN STRAIGHT LINES (PARALLEL OR
PERPENDICULAR) TO DEMISING WALLS ALONG EXISTING STRUCTURE OR
DECK WHERE POSSIBLE. PAINT TO MATCH. EMT CONNECTIONS SHALL
BE COMPRESSION OR SET SCREW TYPE.
B. FLEXIBLE CONDUIT OR TYPE MC CABLE SHALL BE USED FOR FINAL
CONNECTIONS TO LIGHT FIXTURES, MOTORS AND VIBRATING EQUIPMENT
ONLY; AND WHERE SO USED TO BE GROUNDED WITH A SEPARATE
FULL SIZED GREEN GROUNDING CONDUCTOR. FINAL TYPE MC /FLEX
CONNECTIONS SHALL BE LIMITED TO 6' -0" IN LENGTH. (ARRANGE
CIRCUITS SO AS TO AVOID THE USE OF JUNCTION BOXES ABOVE
DRYWALL CEILING AREAS, JUNCTION BOXES LOCATED ABOVE LAY —IN
CEILINGS ARE ACCEPTABLE.) PAINT TO MATCH.
1. MINIMUM SIZES OF CONDUITS SHALL BE 3/4" FOR
STANDARD CONDUIT, AND 1/2" FOR FLEX CONDUIT (1/2"
STANDARD CONDUIT AND 3/8" BX CABLE MAY BE USED
AS SPECIFIED ABOVE, IF ACCEPTABLE WITH LANDLORD AND
LOCAL CODES, ELECTRICAL CONTRACTOR SHALL FIELD
COORDINATE WITH LANDLORD do INSPECTION AGENCIES
PRIOR TO INSTALLATION). ELECTRIC METALLIC TUBING
(EMT) SHALL BE GALVANIZED OR ELECTRO— GALVANIZED.
FITTINGS SHALL BE SET SCREW OR COMPRESSION TYPE,
FITTING SHALL BE AS MANUFACTURED BY REGEL, STEEL
CITY, RACO, T is B, EFCOR OR EQUAL. EMT SHALL BE
USED FOR FEEDERS AND BRANCH CIRCUITS RUN ABOVE
SUSPENDED CEILINGS OR CONCEALED IN INTERIOR
PARTITIONS.
2. PAINTING OF ELECTRICAL CONDUITS, ETC., IF REQUIRED, WILL BE
BY GENERAL CONTRACTOR.
C. THE USE OF ROMEX, AC CABLE IS NOT PERMITTED UNLESS NOTED
OTHERWISE AND APPROVED BY THE ENGINEER.
D. MAXIMUM CONDUIT HANGER SPACING SHALL BE 8' -0" FOR 3/4" THRU 1
1/4" AND 10' -0" FOR 1 1/2" THRU 4" CONDUITS. DO NOT SUPPORT
CONDUIT FROM THE CEILING SYSTEM.
w
v
a
n
D. RUN A SEPARATE GROUNDING CONDUCTOR IN EACH CONDUIT, #12 MINIMUM, OR
AS SHOWN ON DRAWINGS. FOR PANEL FEEDERS BOND THE GROUNDING
CONDUCTOR TO THE CONDUIT, WHERE ENTERING AND LEAVING THE CONDUIT. ALL
GROUND CLAMPS SHALL BE PENN —UNION OR EQUAL, SIMILAR TO "GPL" TYPE.
CONDUIT GROUND BUSHINGS SHALL BE THOMAS do BETTS OR EQUAL, SIMILAR TO
#3800 SERIES WITH NYLON INSULATED THROAT.
E. ALL DEVICES SHALL BE BONDED TO THE CONDUIT SYSTEM. USE A BONDING
JUMPER BETWEEN THE OUTLET BOX AND THE DEVICE GROUNDING TERMINAL,
METAL —TO —METAL CONTACT BETWEEN THE DEVICE YOKE AND THE OUTLET BOX IS
NOT ACCEPTABLE AS A BOND FOR EITHER SURFACE MOUNTED BOXES OR FLUSH
TYPE BOXES. ALL JUNCTION BOXES, OUTLET BOXES AND PULL BOXES SHALL BE
BONDED TO THE CONDUIT SYSTEM, ALL FLEXIBLE CONDUIT SHALL BE JUMPERED
WITH A GROUND CONDUCTOR,
WIRE DEVICES:
A. COLOR OF WIRING DEVICES AND COVERPLATES SHALL BE SELECTED BY ARCHITECT.
(SEE PLAN NOTES FOR ADDITIONAL INFORMATION).
1. RECEPTACLES SHALL BE 20 AMP, 3 —WIRE GROUNDING TYPE EQUAL TO
HUBBELL 5362.
2. SWITCHES SHALL BE 20 AMP SPECIFICATION GRADE, RATED AT 120 OR
347 VOLT, AS REQUIRED.
3. SPECIAL DEVICES SHALL BE A SPECIFICATION GRADE.
4. EQUAL BY ARROW —HART, GENERAL ELECTRIC, BRYANT, PASS It
SEYMOUR, OR SIERRA.
PANELBOARDS AND SAFETY SWITCHES:
A. PROVIDE BRANCH CIRCUIT PANELS WHICH SHALL BE OF THE BOLTED
CIRCUIT BREAKER TYPE WITH SOLID COPPER BUSSING FULL SIZED
NEUTRAL, 25% GROUND BUSSING, OVERALL HINGED /LOCKABLE DOOR,
AND TYPEWRITTEN DIRECTORY INSIDE DOOR. ALL SERVICE ENTRANCE
EQUIPMENT SHALL BEAR THE MANUFACTURER'S LABEL WHICH SHALL
STATE THAT THE EQUIPMENT IS RATED FOR SERVICE ENTRANCE
APPLICATION IN ACCORDANCE WITH N.E.C. LOAD BALANCE ALL ELECTRICAL
PHASES AT PANELS AND SWITCHBOARDS. TWO AND THREE POLE
BREAKERS SHALL BE COMMON TRIP TYPE. WHEN USED AS SWITCHES IN
120V. AND 277V. LIGHTING CIRCUITS, FURNISH TYPE "SWD" BREAKERS IN
ACCORDANCE WITH NEC. SQUARE D OR EQUAL BY SIEMENS ITE, CUTLER
HAMMER, OR GENERAL ELECTRIC (OR APPROVED EQUAL).
B. PROVIDE SAFETY AND DISCONNECT SWITCHES, FUSED OR NONFUSED,
AS CALLED FOR ON DRAWINGS AND AS REQUIRED BY CODE. (FUSES
AS MANUFACTURED BY BUSSMAN, CHASE SHAWMUT, ECONOMY FUSE
CO., OR LITTLE FUSE CO. ARE ACCEPTABLE). DISCONNECT SWITCHES
THAT ARE INSTALLED AT AIR CONDITIONING EQUIPMENT, HEAT PUMPS,
ETC SHALL BE FUSED IN ACCORDANCE WITH THE EQUIPMENT'S NAME
PLATE REQUIREMENTS PER NEC. SWITCHES SHALL BE HEAVY DUTY,
QUICK MAKE /QUICK BREAK TYPE, FUSIBLE OR NON— FUSIBLE,
WEATHERPROOF AS INDICATED ON THE DRAWINGS, OR AS REQUIRED
BY LOCAL CODES. LOAD AND HORSEPOWER RATED AS MANUFACTURED
BY SQUARE D. SIEMENS ITE, CUTLER HAMMER, OR GENERAL ELECTRIC
(OR APPROVED EQUAL).
C. MANUAL MOTOR STARTERS WITH OVERLOAD PROTECTION MAY BE USED
FOR FRACTIONAL HORSEPOWER MOTORS THAT DO NOT REQUIRE
AUXILIARY CONTROL. SINGLE PHASE STARTERS SHALL BE SQUARE D OR
EQUAL. THREE PHASE STARTERS SHALL BE PROVIDED WITH OVERLOAD
DEVICE IN EACH PHASE MATCHED TO MOTOR NAMEPLATE RATING.
MAGNETIC MOTOR STARTERS (MINIMUM SIZE #1) SHALL BE USED FOR
ALL SINGLE PHASE AND THREE PHASE MOTORS RATED ABOVE 1/2 HP
OR THAT REQUIRE AUXILIARY CONTROL, PROVIDE CONTROL DEVICES
(CONTACTS, TRANSFORMERS, ETC.) IN STARTERS AS REQUIRED FOR
INTERLOCKS, COORDINATE WITH MECHANICAL AND /OR TEMPERATURE
CONTROL CONTRACTORS, COMBINATION STARTERS, WHEN USED, SHALL
CONTAIN FUSIBLE SWITCHES.
BOXES:
A. OUTLET BOXES AND COVERS SHALL BE GALVANIZED, ONE —PIECE
PRESSED STEEL KNOCKOUT.
B. JUNCTION, PULL BOXES AND COVERS SHALL BE GALVANIZED STEEL,
CODE GAUGE SIZE.
C. INSTALL BOXES RIGIDLY ON BUILDING STRUCTURE AND SUPPORT
INDEPENDENTLY OF THE CONDUIT SYSTEM. ALSO PROVIDE
SUITABLE /PROPER BOX EXTENSIONS TO EXTEND BOXES TO FINISHED
FACES OF WALLS ETC. ALL OUTLET BOXES TO HAVE SUITABLE
BLOCKING BEHIND THEM TO MINIMIZE THE DEFLECTION THAT OCCURS
WHEN PUGGING /UNPLUGGING INTO THESE DEVICES.
D. WHERE A 277 VOLT LIGHT SWITCH IS GANGED WITH A 120 VOLT
RECEPTACLE PROVIDE A SUITABLE DIVIDER OR SEPARATE JUNCTION
BOXES IN ACCORDANCE WITH NEC AND LOCAL CODES.
SERVICES:
A. PROVIDE TEMPORARY SERVICE FROM LANDLORD'S DESIGNATED
LOCATION AND PROVIDE LIGHTING, POWER AND WIRING AS REQUIRED
TO FACILITATE APPLICABLE TEMPORARY NEEDS, AND FURNISH
EXTENSION CORDS, ANY TEMPORARY WIRING, FUSES, ETC., SHALL BE
REMOVED UPON COMPLETION OF THE PROJECT. PROVIDE GROUND
FAULT PROTECTION AS REQUIRED BY LOCAL CODES,
B. PROVIDE ELECTRICAL SERVICE AS SHOWN ON THE DRAWINGS, FIELD
VERIFY EXACT REQUIREMENTS PRIOR TO BIDS. ALL WORK NOT
SPECIFICALLY NOTED AS BEING BY THE LANDLORD OR POWER
COMPANY SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR,
CLOSELY COORDINATE ENTIRE INSTALLATION WITH LANDLORD AND
POWER COMPANY AS REQUIRED. (PROVIDE EQUIPMENT THAT IS
COMPATIBLE WITH AVAILABLE FAULT CURRENT LEVELS, PROVIDE
"CABLE LIMITERS" IF NECESSARY FOR SYSTEM COORDINATION).
FIELD VERIFY EXACT TYPE, SIZE, LOCATION, REQUIREMENTS,
FTC, OF EXISTING POWER AND TELEPHONE FACILITIES PRIOR TO
BIDDING PROJECT.
C. MAKE PROVISIONS FOR NEW TELEPHONE SERVICE AS REQUIRED, AND
AS INDICATED ON THE DRAWINGS.
D. CONDUIT SYSTEM FOR TELEPHONE DISTRIBUTION WITHIN TENANT'S
PREMISES SHALL BE PROVIDED AS REQUIRED FOR A COMPLETE
TELEPHONE SYSTEM. OUTLET BOXES SHALL BE 4" SQUARE
MINIMUM WITH SINGLE DEVICE COVER AND TELEPHONE PLATE,
FIELD COORDINATE WITH TENANTS CONSTRUCTION MANAGER
TO AVOID CONFLICTS.
STEP —DOWN TRANSFORMER:
A. PROVIDE DRY —TYPE TRANSFORMER AS MANUFACTURED BY SQUARE "D" ,
HEAVY DUTY, ACME, GENERAL ELECTRIC, SIEMENS ITE OR OTHER
EQUIVALENT MANUFACTURERS, OF THE ENCLOSED VENTILATED TYPE WITH
KVA AND VOLTAGE RATINGS AS CALLED FOR ON THE DRAWINGS WITH
COILS DESIGNED FOR 150 DEGREE C RISE ABOVE A 40 DEGREE C
AMBIENT WITH 100% OF RATED LOAD CONNECTED TO THE SECONDARY,
CLASS 220 DEGREE C INSULATION AND A MINIMUM OF SIX STANDARD
FULL CAPACITY TAPS (TWO ABOVE AND FOUR BELOW NORMAL). SOUND
LEVEL /DECIBELS SHALL BE IN ACCORDANCE WITH "NEMA" STANDARDS,
AND INSTALLATION SHALL INCLUDE "KORFOUND" OR EQUAL
VIBRATION — DAMPENING MOUNTS AND FLEXIBLE STEEL CONDUIT FOR
PRIMARY AND SECONDARY CONNECTIONS TO MINIMIZE SOUND
TRANSMISSION. MOUNT TRANSFORMER ON SEPARATE VIBRATION
ISOLATORS. THESE ARE ADDITIONAL VIBRATION ISOLATORS AND ARE
USED IN CONJUNCTION WITH ANY INTEGRAL FACTORY INSTALLED
VIBRATION ISOLATORS.
FIRE ALARM SYSTEM:
PROVIDE THE FOLLOWING NEW EQUIPMENT, COMPATIBLE WITH, OR OF
THE SAME MANUFACTURER AS, THE EXISTING FIRE ALARM CONTROL
PANEL AND SYSTEM, AT LOCATIONS INDICATED ON THE DRAWINGS, AS
REQUIRED BY BUILDING CODES, THE LANDLORD, OR ALL THREE, AND
CONNECT TO THE EXISTING FIRE ALARM CONTROL PANEL:
A. ADDITIONAL INITIATING DEVICES, INDICATING APPLIANCES, AND
INTERCONNECTING CIRCUITS,
B. ADDITIONAL ZONE MODULES REQUIRED BY NEW ZONING.
C. NEW AMPLIFIERS AND OTHER EQUIPMENT THAT MAY BE REQUIRED TO
INCORPORATE THE NEW INITIATING DEVICES AND INDICATING
APPLIANCES INTO THE EXISTING SYSTEM.
D. A NEW ZONE MAP, INCLUDING ALL EXISTING ZONES AND ALL NEW
ZONES, FRAMED, MOUNTED UNDER GLASS, AND INSTALLED ADJACENT
TO THE FIRE ALARM CONTROL PANEL, HORN /STROBES SHALL MEET
ALL REQUIREMENTS OF THE AMERICANS WITH DISABILITIES ACT.
E. PROVIDE ALL REQUIRED PROGRAMMING.
F. PROVIDE TESTING OF SYSTEM AS REQUIRED.
G. PROVIDE SHOP DRAWINGS WITH EQUIPMENT CUTSHEEfS, WIRING
DIAGRAMS, POINT —TO —POINT FIRE ALARM CABLING PLAN, VOLTAGE
CALCULATIONS, AND BATTERY CALCULATIONS FOR THE MAIN FIRE
ALARM CONTROL PANEL.
W V Y Y V W Y Y Y Y
••• Y i • • • • Y Y
• Y • • V Y WW••W
• • Y Y r Y • • •
••• ••• Y • • •••t Y Y •
••• • • • •
• Y • • Y • V t • Y
LIGHTING CONTACTOR AND TIMER SWITCHES: • • • i i • • M
• Y • • • r Y
• • • 16• • VV7 ••W
A. CONTACTORS FOR CONTROL OF LIGHTING AND SIGNS SHALL BE
SQUARE "D ", CLASS 8903, TYPE "L ", ELECTRICALLY HELD.
EQUIVALENT PRODUCTS BY OTHER MANUFACTURERS ARE PERMITTED.: "Ou `*": •`•!• :`••0
•••• v r u r
• Y • V Y v
• Y • • • Y Y
•rV• • ••••• • VUU V YWV• r
B. ELECTRONIC DIGITAL TIME SWITCHES SHALL BE USED FOR CONTROL
OF SHOW WINDOW LIGHTING, SIGNS, AND IF REQUIRED /DESIRED
OTHER LIGHTING. THE ELECTRONIC DIGITAL TIMER SHALL BE
PROVIDED WITH A 7 —DAY FORMAT, 365 DAY ADVANCED HOLIDAY
SCHEDULE, CAPABLE OF DIFFERENT SETTINGS EACH DAY OF THE
WEEK, AND HAVE AN ASTRONOMIC FEATURE.
INSTALLATION:
A. ALL ELECTRIC WORK SHALL BE INSTALLED SO AS TO BE READILY
ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING AND REPAIRING.
HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS
CHANNELS, RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK
AND SHALL BE FASTENED TO BUILDING STEEL, CONCRETE OR MASONRY,
BUT NOT PIPING OR DUCTWORK. ALL CONDUIT SHALL BE CONCEALED
WHEREVER POSSIBLE. EXPOSED CONDUITS SHALL BE IN STRAIGHT
LINES PARALLEL WITH OR AT RIGHT ANGLES TO COLUMN LINES OR
BEAMS AND SEPARATED AT LEAST 3 INCHES FROM WATER LINES
WHEREVER THEY RUN ALONGSIDE OR ACROSS SUCH LINES. ALL
CONDUCTORS SHALL BE IN CONDUIT, DUCTS OR OTHER CODE
APPROVED RACEWAYS.
B. ALL LINE AND LOW VOLTAGE POWER AND CONTROL WIRING (EXCEPT
HVAC, DATA, TELEPHONE AND VIDEO /TV LOW VOLTAGE WIRING)
INCLUDING CONNECTIONS TO MOTORS, DAMPERS, INTERLOCKING, ETC.,
SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. ALL LINE
VOLTAGE WIRING, CONDUIT, AND FINAL CONNECTIONS FROM THE
POWER SOURCE THRU THE STARTER /DISCONNECT ETC. TO THE
MOTOR OR EQUIPMENT IS THE RESPONSIBILITY OR THE ELECTRICAL
CONTRACTOR. ALL HVAC RELATED LOW VOLTAGE CONTROL WIRING,
CONDUIT AND FINAL CONNECTIONS ARE THE RESPONSIBILITY OF THE
MECHANICAL /TEMPERATURE CONTROL CONTRACTOR, UNLESS
OTHERWISE NOTED ON THE PLANS. ALL DATA, TELEPHONE AND
VIDEO /TV LOW VOLTAGE WIRING AND CONNECTIONS ARE THE
RESPONSIBILITY OF THE OWNER'S VENDORS.
C. THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING, CHASING OR
CHANNELING AND PATCHING REQUIRED FOR ANY WORK UNDER THE
ELECTRICAL DIVISION, ANY CUTTING SHALL HAVE PRIOR APPROVAL
OF THE LANDLORD. SLEEVES SHALL EXTEND AT LEAST TWO (2 ")
INCHES ABOVE FINISHED FLOOR AND ALL SLEEVES, OPENINGS,
ETC., THROUGH FIRE RATED WALLS AND FLOORS SHALL BE FIRE
SEALED WITH CALCIUM SILICATE, SILICONE "RTV" FOAM, "3M"
FIRE RATED SEALANTS OR EQUAL BY HILTI AFTER CONDUIT /CABLES
INSTALLATION SO AS TO RETAIN THE FIRE RATING,
D. THE ELECTRICAL CONTRACTORS, INSOFAR AS THE WORK IS
CONCERNED, SHALL AT ALL TIMES KEEP THE PREMISES IN A NEAT
AND ORDERLY CONDITION AND, AT THE COMPLETION OF THE WORK,
SHALL PROPERLY CLEAN UP AND CART AWAY ANY DEBRIS AND
EXCESS MATERIAL.
E. THE FOLLOWING EQUIPMENT SHALL BE IDENTIFIED WITH ENGRAVED
BAKELITE NAMEPLATES AS TO NAME AND /OR FUNCTION:
DISTRIBUTION PANELS, LIGHTING PANELS, MOTOR STARTERS AND
DISCONNECT SWITCHES. NAMEPLATES TO BE APPROXIMATELY 1" X
2" IN SIZE AND BE FASTENED WITH POP RIVETS OR SCREWS.
F. THE LOCATION OF OUTLETS AND EQUIPMENT SHOWN ON THE
DRAWINGS ARE APPROXIMATE AND THE ARCHITECT /TENANT
CONSTRUCTION MANAGER SHALL HAVE THE RIGHT TO RELOCATE ANY
OUTLETS OR FIXTURES BEFORE THEY ARE INSTALLED WITHOUT
ADDITIONAL COST. IN THE EVENT OF ANY CONFLICTS WITH EXISTING
OR NEW FIXTURE LAYOUT GENERAL CONTRACTOR TO CONTACT
LULULEMON PROJECT MANAGER.
G. ELECTRICAL CONTRACTOR SHALL RECORD ALL FIELD CHANGES IN
THE WORK AS THE JOB PROGRESSES, AND TURN THIS "AS BUILT"
INFORMATION OVER TO THE OWNER AT THE COMPLETION OF THE
PROJECT.
H. ELECTRICAL CONTRACTOR SHALL PROTECT ALL FIXTURES /EQUIPMENT
AGAINST DAMAGE FROM LEAKS, ABUSE, ETC., AND PAY COST OF
REPAIR OR REPLACEMENT OF FIXTURES OR EQUIPMENT MADE
NECESSARY BY FAILURE TO PROVIDE SUITABLE SAFEGUARDS OR
PROTECTION.
I. ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL ELECTRICAL
CONNECTIONS AS REQUIRED FOR A COMPLETE AND OPERATING
SYSTEM. AFTER ALL EQUIPMENT HAS BEEN INSPECTED AND
APPROVED, THOROUGHLY CLEAN ALL EQUIPMENT PROVIDED UNDER
THIS WORK JUST PRIOR TO COMPLETION OF PROJECT.
J. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ANY /ALL
NECESSARY ELECTRICAL DEMOLITION WORK THAT IS REQUIRED TO
FACILITATE THE NEW INSTALLATION, FIELD COORDINATE PRIOR TO
BIDS. REMOVE AND /OR MODIFY EQUIPMENT, ETC. AS REQUIRED
FOR A COMPLETE INSTALLATION. ANY EQUIPMENT OR DEVICE
REMAINING IN USE AFTER PART OF THE EQUIPMENT OR DEVICES
HAVE BEEN REMOVED ARE TO BE RECONNECTED TO EXISTING OR NEW
CIRCUITS AND LEFT IN WORKING ORDER. FEEDERS TO PANELS AND
WIRING TO OTHER EQUIPMENT TO BE ROUTED CONCEALED IN
FINISHED AREAS. COORDINATE ANY DISRUPTION OF ELECTRICAL
OR TELEPHONE SERVICES WITH LANDLORD AND TENANT
CONSTRUCTION MANAGER TO AVOID CONFLICTS.
GUARANTEE:
A. MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE GUARANTEED
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE.
DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED
AT THE ELECTRICAL CONTRACTOR'S EXPENSE,
B. FOR THE SAME PERIOD, ELECTRICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE TO PREMISES CAUSED BY DEFECTS
IN WORKMANSHIP OR IN THE WORK OR EQUIPMENT FURNISHED
AND /OR INSTALLED BY THE ELECTRICAL CONTRACTOR.
FI NALLY:
A. IT IS THE INTENT THAT THE FOREGOING WORK SHALL BE COMPLETE
IN EVERY RESPECT AND THAT ANY MATERIAL OR WORK NOT
SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS, BUT
NECESSARY TO FULLY COMPLETE THE WORK SHALL BE FURNISHED.
B. PROVIDE AND INSTALL TYPED PANEL SCHEDULES FOR ALL PANEL
BOARDS. PROVIDE AND INSTALL BLACK PLASTIC, WHITE ENGRAVED
NAMEPLATES ON EXTERIOR OF ALL PANELBOARDS. PROVIDE ONE
COMPLETE SET OF STAMPED PLANS TO BE CONTAINED IN A PVC
TUBE MOUNTED ON PHONE BOARD.
9WAHENDERSON
ENGINEERSM_
5325 LENEXA DRIVE
LENEXA, KS 66214
TEL 913 742 5000 FAX 913 742 5001
www.hei- eng.cem
1250000999
FL. CEIEIlFMli lO]lllYlAYIIIM11b A68 7606
1mRRogl//Il///l3
(� r, m (-
ifl in
E
Nu �
•
:Y
z
0
H
a
rr
U
w
0
0
0
z
up
STATE OF
i
DAVID MKE %J
G
LICE S 611x1
V J
0
Uz
Li
Ld
Cr)
Q
o
<0
F___
O
U
0U ILLI
� °
U
w
W� L_j
U)
V J z
�`�
�...J I� j
U
�0
Elf
U
W
w
ISSUE FOR DD —LLL XX —XX —XX
ISSUE FOR DD —LLD XX —XX —XX
ISSUE FOR CD --LLL XX —XX —XX
ISSUE FOR CD —LLD XX —XX —XX
ISSUE FOR PERMIT 09-12 -12
ISSUE FOR OID XX —XX —XX
Scale:
Doti: 12/ 12
Drawn ANS
Ch.ck.ol By: DME
J96 Numloor 17991
Drawing:
E61
i
t