10-892-003NOTES: 1.ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. 72 AND N.E.C. 760 AND WIRING SHALL BE SOLID COPPER, THE CONDUIT SIZE TO BE MINIMUM OF 1/2 ,, . 2. ALL FIRE STOP PENETRATIONS SHALL BE SEALED WITH A U.L. APPROVED FIRE STOP MATERIAL (SEE FIRE STOP DETAIL). 3. ALL WORK TO BE DONE IN ACCORDANCE WITH NEC AND SHALL COMPLY WITH LOCAL RULES AND REGULATIONS 4. THE FIRE ALARM CONTROL PANEL SHALL BE FEED BY A 1/2 EMT CONDUIT WITH (3) #12 CONDUCTORS (3) #12 CU THHN CONDUCTORS (ONE PHASE CONDUCTOR, ONE NEUTRAL CONDUCTOR AND ONE GROUNDING CODUCTOR) SUPPLIED BY A 20 AMP SINGLE POLE DEDICATED BRANCH CIRCUIT BREAKER AT 120 VAC. 5. THE POWER EXPANDER CONTROL PANELS ARE FEED BY A 1/2 EMT CONDUIT WITH (3) #12 CU THHN CONDUCTORS (ONE PHASE CONDUCTOR, ONE NEUTRAL CONDUCTOR AND ONE GROUNDING CODUCTOR) SUPPLIED BY A 20 AMP SINGLE POLE DEDICATED BRANCH CIRCUIT BREAKER AT 120 VAC AND THE BREAKER MUST BE IDENTIFIED "FIRE ALARM CIRCUIT" AS PER NFPA 72 (2002 EDITION) 4.4.1.4.2.2. 6. ALL THE EQUIPMENT SHALL BE UL LISTED FOR FIRE ALARM SERVICES AND COMPATIBLE BETWEEN THEM 7. AL FIRE ALARM DEVICES AND APLIANCES SHALL BE INSTALLED AS PER NFPA 72 (2002 EDITION). 8. THE FIRE ALARM SYSTEM SHALL BE POWER LIMITED AND SHALL BE GROUNDED PER MANUFACTURER SPECIFICATIONS AND NEC ARTICLE 250. 9. THE BACKUP BATTERY CHARGER ARE LOCATED INSIDE THE PANELS OR ADJACENT IN UL LISTED BOXES AND SHALL BE UL LISTED AND THE ONES THAT ARE INSIDE THE PANEL SHALL NOT EXCEED 33 AH. 10. PULL STATIONS SHALL BE INSTALLED IN CONFORMANCE WITH NFPA 72 (2002) EDITION CHAPTER 5.12 AND CHAPTER 11, FIGURE 5(a) OF FLORIDA BUILDING CODE (2007 EDITION) - THE PULL STATIONS SHALL BE INSTALLED AT 48 A.F.F. - THE PULL STATIONS SHALL BE INSTALLED AT LEAST ONE PER FLOOR WITHIN 200' OF ANY POINT IN THE PERMISES 11. SMOKE DETECTORS LOCATION AND SPACING SHALL BE IN CONFORMANCE WITH NFPA 72 (2002 EDITION) CHAPTER 5.5. - CEILING MOUNTED SMOKE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIRFLOW, NOR CLOSER THAN 3' FROM AN AIR SUPPLY DIFFUSER IN ACCORDANCE WITH NFPA 72, (2002 EDITION) CHAPTER 5.7.4.1. - WALL MOUNTED SMOKE DETECTORS SHALL BE MOUNTED 4" MINIMUM FROM CEILING WITH 12" MAXIMUM FROM CEILING, AS PER NFPA 72, (2002 EDITION) CHAPTER 5.7.3.2.1. 12. HEAT DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA72, (2002 EDITION) CHAPTER 5.6.3. 13. SMOKE AND HEAT DETECTORS ARE SPACED ACCORDINGLY IN PEAKED OR SLOPED CEILINGS. 14. HORN /STROBES AND STROBE LIGHTS SHALL BE INSTALLED AT 80" A.F.F. OR 6" BELOW THE CEILING (WHICH EVER IS LOWER) 15. ALL CORRIDOR SPACED STROBE LIGHTS ARE PLACED A MAXIMUM OF 100 FEET APART AND WITHIN 15' FROM THE ENDS OF THE CORRIDOR. 16. ALL VISUALS SHALL BE SYNCHRONIZED AT 1 HZ PER ADA NFPA 72. 17. WHERE AUDIBLE APPLIANCES ARE INSTALLED TO PROVIDE SIGNALS FOR- SLEEPING AREAS, THEY SHALL HAVE A SOUND LEVEL OF AT LEAST 15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5dBA ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 dBA, WHICHEVER IS GREATER, MEASURED AT THE PILLOW LEVEL IN THE OCCUPIABLE AREA. IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR RETRACTABLE PARTITION, IS LOCATED BETWEEN THE NOTIFICATION APPLIANCE AND THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED WITH THE BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW AS PER NFPA 72 7.4.4. 2002 EDITION). 18. THE FIRE ALARM EVACUATION SYSTEM SHALL BE IN CONFORMITY WITH NFPA 72 2002 AND LIFE SAFETY 101 (2006 EDITION)., A GENERAL ALARM SHALL ALERT THE TENANTS THROUGHOUT THE SPACE 19. ALL RACKS SHELVES AND EQUIPMENT IN ANY OF THE AREAS IN THE PERMISES, IF EXISTING SHALL NOT BLOCK ANY OF THE INITIATING AND /OR INDICATING DEVICES AND SHALL BE SHOWN ON THE PLANS. 20. THE DEVICES AND APPLIANCES THAT ARE IN AREAS WHICH THE VOLTAGE, TEMPERATURE AND HUMIDITY VARIATIONS EXCEED THE NORMAL CONDITIONS SHALL HAVE A "WP" LABEL NEXT TO IT. SCOPE OF WORK 1. TO INSTALL A NEW FIRE ALARM SYSTEM THAT SHALL COMPLY WITH LIFE SAFETY 101 (2006 EDITION) AND NFPA 72 (2002 EDITION) FOR AUDIBLE AND VISIBLE DEVICE REQUIREMENTS. 2. THE SCOPE OF WORK BUILDING HAS TWO FLOORS IS NON SPRINKLERED AND HAS A TOTAL AREA OF: 6,480 SQ. FT. THE BUILDING IS AM ASSEMBLY OCCUPANCY WITH OCCUPANT LOAD OF LESS THEN 300 3. THE MAXIMUM LENGTH PER INDICATING CIRCUIT NOT TO EXCEED 700' (SEE CIRCUIT CALCULATIONS). 4. MAXIMUM HEIGHT OF ACOUSTIC CEILING IS 9'8 ". 6. THE FIRE ALARM SYSTEM IS POWER LIMITED AND ALL THE DEVICES ARE UL LISTED AND PERFECT COMPATIBLE WITH THE SYSTEM BEING USED. 7. THE INSTALLATION TO COMPLY F.B.C. 11 -4 -28.3, 2007 EDITION. 8. THE MS- 905OUD FIRE ALARM CONTROL PANEL IT IS AN ADDRESSABLE PANEL WITH A CAPACITY OF 50 DEVICES A SINGLE LINE CIRCUIT SUPORTS UP TO A TOTAL 50 DETECTORS AND MODULES. THE PANEL HAS INCORPORATED AN DIALER TO ITS STRUCTURE. SEQUENCE OF OPERATION: 1. MANUAL PULL STATION -SHALL INITIATE A GENERAL ALARM IN THE BUILDING FOR EVACUATION PURPOSES. IT SHALL BE INSTALLED PER NFPA 72, (2002 EDITION) CHAPTER 5.1.2. AND FLORIDA BUILDING CODE 11.4.28 (2007 EDITION) AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL AND THE LOCATION OF THE ALARMED DEVICE SHALL BE DISPLAYED AT THE PANEL. THE ALARM SHALL SOUND THROUGHOUT THE WHOLE BUILDING AS GENERAL ALARM. 2. SMOKE DETECTOR - SHALL INITIATE A GENERAL ALARM IN THE BUILDING FOR EVACUATION PURPOSES. IT SHALL BE INSTALLED PER NFPA 72, (2002 EDITION) CHAPTER 5.5. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL.THE ALARM SHALL SOUND THROUGHOUT THE WHOLE BUILDING AS GENERAL ALARM. ACTIVATION OF THE INITIATING DEVICES MENTIONED ABOVE, SHALL GENERATE A GENERAL ALARM, ACTIVATING THE AUDIO /VISUAL DEVICES (HORN /STROBES, STROBES) THROUGHOUT THE WHOLE BUILDING 3. HEAT DETECTOR - SHALL INITIATE A GENERAL ALARM IN THE BUILDING FOR EVACUATION PURPOSES. IT SHALL BE INSTALLED PER NFPA 72, (2002 EDITION) CHAPTER 2 -2 -2.. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL. THE ALARM SHALL SOUND THROUGHOUT THE WHOLE BUILDING. ACTIVATION OF THE INITIATING DEVICES MENTIONED ABOVE, SHALL GENERATE A GENERAL ALARM, ACTIVATING THE AUDIO /VISUAL DEVICES (HORN /STROBES, STROBES) THROUGHOUT THE WHOLE BUILDING 4. PANEL POWER -UP AND POWER -DOWN: POWER DOWN: 1. DISCONNECT BATTERY 2. TURN OFF AC POWER PRIMARY & SECONDARY POWER UP: 1. TURN ON AC POWER PRIMARY & SECONDARY 2. RECONNECT BATTERIES ALARM SIGNALS SHALL BE DISPLAYED ON THE FIRE ALARM PANEL AND REMOTE ANNUNCIATOR. TROUBLE AND SUPERVISORY SHALL NOT ACTIVATE AUDIBLE AND VISIBLE DEVICES, BUT THEY SHALL INITIATE A SUPERVISORY TROUBLE CONDITION AT THE FIRE ALARM CONTROL PANEL IN ACCORDANCE WITH NFPA 72, (2002 EDITION) CHAPTER 5.13. AN AUDIBLE SUPERVISORY TF;OUBLE TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL AND THE SUPERVISORY LOCATION SHALL BE DISPLAYED AT THE PANEL AND REMOTE ANNUNCIATOR; THE ALARM AND TROUBLE CONDITION AND SHALL BE REPORTED TO A LISTED CENTRAL STATION FACILITY BY WAY OF DIGITAL COMMUNICATOR. EACH SIGNALING LINE CIRCUIT AND NOTIFICATION APPLIANCE CIRCUIT SHALL BE ELECTRICALLY SUPERVISED FOR OPENS, SHORTS AND GROUND FAULTS. THE OCCURENCE OF ANY FAULT SHALL ACTIVATE THE SYSTEM TROUBLE CIRCUITRY BUT SHALL NOT INTERFERE WITH THE PROPER OPERATION OF ANY CIRCUIT THAT DOES NOT HAVE A FAULT CONDI -� ION. THE 120 -VA POWER FEED FOR THE FIRE ALARM PANELS AND POWER SUPPLIES MUST BE FROM A DEDICATED BRANCH CIRCUIT AND CONNECTIONS SHALL BE MECANICALLY PROTECTED AS PER 4.4.1.4.2.1. NFPA 72 (2002 EDITION). CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZE PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT" AS PER 4.4.1.4.2.2. NFPA 72 (2002 EDITION). THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENETLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT, AS PER NFPA 72 (2002 EDITION). THE FIRE ALARM SYSTEM SHALL BE MONITORED OF - PERMISE B A UL CERTIFICATE /PLACARED CENTRAL STATION FACILITY IN ACCORDANCE WITH NFPA 72 2002 EDITION , CHAPTER 8.2. THE SYSTEM IS A CENTRAL STATION ALARM. TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE ALARM COMMUNICATOR FOR PURPOSES OF MONITORING THE FIRE ALARM SYSTEM. TELEPHONE LINES SHALL BE CONNECTED IN CONFORMANCE WITH NFPA 72, CHAPTER 8.5.3.2.1 (2002 EDITION) UPON COMPLETION OF THE INSTALLATION A "CERTIFICATE OF COMPLETION" SHALL BE PROVIDED TO THE CUSTOMER AND THE LOCAL AUTHORITY HAVING JURISDICTION. A LOG BOOK SHALL REMAIN ON THE PERMISES THAT SHALL INCLUDE DRAWINGS, MANUALS, INSPECTION RECORDS, ETC. BLITSTEIN DESIGN ASSOCIATES Architecture Interior Design 285 Sevilla Avenue Coral Gables, Fl 33134 (305) 444 -4433 Pire291�150I I10IA ?rN -0 A € E- C10U; ;T Y FIRE DE PAR 711.4 ENT FIRE SUPPFF55ION _ VIIWI E 2 HANN E: {T. 1 DATE-: • �^2p [3Y: FIRE ALARM SYSTEM TO BE �I`ISTALLED IN ACCORDANCE MIT i NFPA 72,70; l 01 FIRE ALARM SHALL gE A CENTRAL', STATIG;N! SERVICE. A CERTIFICATE oR PLACARD SHALL BE POSTED AT Flf AL INSPECTION, ASFER NftPA eT ELEVATOR CONTROL THE ACTIVATION OF A SMOKE DETECTOR IN AN ELEVATOR LOBBY AND /OR SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM SHALL, IN ADDITION TO THE ABOVE, ALSO INITIATE THE RECALL OF THE ELEVATOR CARS AS FOLLOWS IN ACCORDANCE WITH NFPA 72, (2002 EDITION) CHAPTER 6.15.3 AND 6.15.4. PHASE I RECALL - ANY ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON SECOND FLOOR AND /OR ANY SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM SHALL INITIATE PHASE I RECALL WHICH WILL BRING THE ELEVATOR CAR TO THE FIRST FLOOR AND LOCK THE DOORS IN THE OPEN POSITION ANY ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON THE FIRST FLOOR SHALL INITIATE PHASE I RECALL ALTERNATE WHICH WILL BRING THE ELEVATOR CAR TO THE SECOND FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. NOTES &SEQUENCE OF OPERATIONS SCALE: N.T.S. project name Existing Building Renovation for: Continental Fidelity Corporation 5734 Sunset Drive South Miarmi; tar project number ,tV. 08/24/10 revision Q 09/1 0/2010 drawn by D.M. sheet title FIRE ALARM PLAN PHASE II RECALL - ACTIVATION OF ANY ELEVATOR MACHINE ROOM SMOKE DETECTOR SHALL ALSO INITIATE ANY EXISTING ELEVATOR WARNING LIGHTS TO ALERT EMERGENCY PERSONNEL THAT THE ELEVATORS SCALE: 1/8" = V -0" ARE NOT SAFE TO USE. >>tt«, �,,sheet number C I IAN •••,� BUCHANAN P.E CONSULTING INC. ° s ELECTRICAL MECHANICAL PLUMBING P �HA NA ENGINEERING W-0 A (%: FAw2 6191 W. ATLANTIC BLVD, SUITE# 2 +L ; MARGATE, FL 33063 - Phi 954 - 590 -3300 Faxe 954- 590 -2232 •'�9 O F 02 Emalb Mepenglneers @aol.coM �,• RAJA BUCHANAN FL P.E # 48916 • �� 0��0' CERTIFICATE OF AUTHORIZATION # 8942 F.