09-1112R-006
GENERAL MECHANICAL NOTES 1- SCOPE OF WORK WORK SHALL INCLUDE ALL LABOR, EQUIPMENT AND PERFORMING ALL OPERATIONS IN CONNECTION WITH THE FURNISHING OF ALL AIR CONDITIONING, HEATING AND VENTILATION WORK AS SHOWN ON DRAWINGS. HEREIN SPECIFIED AND /OR EQUAL EQUIPMENT FOR APPROVAL. 2- AIR CONDITIONING SYSTEM OF SPLIT TYPE. SHALL CONSIST OF CONDENSING UNIT AND AIR HANDLING UNIT AS INDICATED ON DRAWINGS. SYSTEM SHALL BE PROVIDED COMPLETE WITH FRAMES AND ENCLOSURES, WIRING, NECESSARY CONTROLS REFRIGERANT CHARGE AND OIL CHARGE, STRIP HEATER, INTERCONNECTING PIPES AND FILTER BOX. REFRIGERANT LINES SHALL BE OF COPPER OF THE PRECHARGED, PRE - INSULATED TYPE FURNISHED AND SIZED BY SUPPLIER OF EQUIPMENT.PROVIDE SMOKE DETECTORS TO SHUT OFF UNIT. 3- CONDENSATE WATER PIPING. CONDENSATE PIPING SHALL BE OF PVC SCHED. 40, EXCEPT INSIDE A/C PLENUM SPACES WHERE COPPER PIPING SHALL BE INSTALLED. 4- OUTSIDE AIR INTAKE SHALL BE AT 10' MINIMUM DISTANCE FROM ANY EXHAUST VENT. 5- DUCTWORK PROVIDE VOLUME DAMPERS, TURNING VANES, ETC., IN DUCTWORK FOR PROPER AIR FLOW AND BALANCE. PROVIDE VOLUME DAMPER WITH LOCKING QUADRANT AT ALL FLEXIBLE DUCT CONNECTIONS WITH SUPPLY DUCTWORK. PROVIDE MULTIPLE VANE EXTRACTORS WITH CONTROL RODS ACCESSIBLE FROM THE REGISTER AT ALL OUTLETS CONNECTED CLOSER THAN TWO DUCT DIAMETERS TO MAIN SUPPLY DUCT, AND WHERE SHOWN ON DRAWINGS. FLEXIBLE DUCTS SHALL BE THE INSULATED TYPE, SUPPORTED AND INSTALLED TO AVOID SAGS AND KINKS. ALL FLEXIBLE DUCTS SHALL BE SIMILAR IN LENGTH TO AVOID DISSIMILAR PRESSURE DROPS. FLEXIBLE DUCTS SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS. SEAL ALL FLEXIBLE DUCTS TO SUPPLY DUCTS AND DIFFUSERS WITH DUCT TAPE AND MASTIC. EXCEPT AS SPECIFIED OTHERWISE, NEW AIR CONDITIONING SUPPLY, AND AIR DUCTWORK SHALL BE CLASS 1 GLASS FIBER DUCT BOARD CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH THE LATEST SMACNA FIBROUS DUCT CONSTRUCTION STANDARDS. PROVIDE R =4.6 INSULATION PER FLORIDA ENERGY CODE. METAL DUCTS SHALL BE IN ACCORDANCE WITH LATEST ISSUE OF THE LOW VELOCITY DUCT CONS- TRUCTION STANDARDS, PUBLISHED BY THE "SHEET METAL AND AIR CONDITIONED CONTRACTORS NATIONAL ASSOCIATION, INC." AND THE LATEST PUBLICATION OF GUIDE & DATA BOOK OF THE AMERICAN SOCIETY OF HEATING, VENTILATING AND AIR CONDITIONING ENGINEERS. 6- CONTRACTOR SHALL PROVIDE POSITIVE MEANS FOR BALANCING EACH INDIVIDUAL AIR CONDITIONING SUPPLY AIR OUTLET, AS PER SCHEDULES AND DRAWING, SYSTEMS SHALL BE BALANCED AGAINST THE ACTUAL INSTALLED STATIC PRESSURE. 7- BEFORE SUBMITTING FINAL PROPOSAL, THE CONTRACTOR SHALL EXAMINE THE SITE OF THE PROPOSED WORK TO DETERMINE THE EXISTING CONDITIONS THAT MAY AFFECT HIS WORK AS HE WILL BE RESPONSIBLE FOR ANY ASSUMPTIONS MADE BY HIM IN REGARDS THERETO. 8- ANY APPARATUS, APPLIANCE, MATERIALS, WORK OR INCIDENTAL ACCESSORIES OR MINOR DETAILS NOT SHOWN BUT NECESSARY TO MAKE THE INSTALLATION COMPLETE AND FUNCTIONAL IN ALL RESPECTS AND READY FOR OPERATION, EVEN IF NOT PARTICULARLY SPECIFIED, SHALL BE PROVIDED BY THE CONTRACTOR WITHOUT ANY ADDITIONAL EXPENSE FOR THE OWNER, AS PART OF MEANS AND METHOD OF INSTALLATION. 9- VIBRATION ISOLATION PROVIDE SUPPORTS OR MOUNTS FOR ALL EQUIPMENT LOCATED WITHIN THE BUILDING STRUCTURE POWERED BY ONE HORSEPOWER OR LARGER MOTOR. FLEXIBLE PIPING CONNECTIONS SHALL BE PROVIDED FOR ALL PIPING CONNECTED TO EQUIPMENT MOUNTED OR SUPPORTED BY VIBRATION ISOLATORS. 10- ALL WORK SHALL BE FIELD CHECKED BEFORE INSTALLATION AND COORDINATED WITH ALL OTHER TRADES. 11- ALL MECHANICAL EQUIPMENT INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE CONSTRUCTED TO WITHSTAND A WIND PRESSURE OF 60 PSF (120 MPH WINDS) FROM ANY DIRECTION. 12- ALL SIZES SHOWN FOR LINED AND UNLINED DUCTS ARE CLEAR INSIDE DUCT DIMENSIONS. 13- COORDINATE LOCATION OF DUCTWORK WITH OTHER TRADES, PARTICULARLY WHERE DUCTS RUN THROUGH STRUCTURAL 14- ALL CONTROL WIRING SHALL BE THE RESPONSIBILITY OF THE MECHANICAL SUBCONTRACTOR MECHANICAL SUB CONTRACTOR TO FURNISH ALL MOTORS, STARTERS, AND RELAYS, ETC. 15- A/C CONTRACTOR IS RESPONSIBLE FOR OBTAINING HIS OWN PERMIT AND PAYING ALL PERMIT FEES. 16- CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR ALL COSTS INCURRED RESULTING FROM SUBSTITUTION OF EQUIPMENT AS WELL AS THE PERFORMANCE OF SUCH EQUIPMENT. ALL TESTS SHALL BE PERFORMED AS REQUIRED DURING THE DIFFERENT STAGES OF WORK AND A FINAL 24 HOURS MINIMUM RUNNING TEST SHALL BE DONE AFTER ALL OTHER TESTS AND BALANCING OPERATIONS HAVE BEEN DONE. PROVIDE A BALANCING INDEPENDENT TEST & BALANCE REPORT TO ENGINEER FOR REVIEW. 17- TESTS 18- PROVIDE ALL NECESSARY INSTRUCTIONS TO THE OWNER IN THE OPERATION OF THE MECHANICAL SYSTEMS. 19- PROVIDE EQUIPMENT OPERATION AND MAINTENANCE MANUALS. MANUALS SHALL BE SUBMITTED TO THE ARCHITECT FOR ACCEPTANCE. 20- SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT AND /OR ENGINEER BEFORE PROCEEDING WITH PURCHASE OR INSTALLATION OF THE EQUIPMENT AND MATERIALS. 21- GUARANTEE CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE COVERING ALL WORMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE. FAN NO. CFM SP. HP. VOLTS /PHASE TEF -1( *) 60 0.25 80 WATTS 115/60/14 ( *)EF -1 INTERLOCK WITH LIGHT SWITCH HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR X COMMENTS FIRE DAMPER(S) SUPPLY AIR X SMOKE DAMPER(S) RECTANGULAR DIFUSER WITH OPPOSED BLADE DAMPER. 24x24 MODULAR. X FIRE RATED ENCLOSURE X TITUS, 250 AA FIRE RATED ROOF /FLOOR CEILING ASSEMBLY 59,500 X FIRE STOPPING X OPPOSED BLADE DAMPER. SMOKE CONTROL 13,000 X t �t SUPPLY/ RETURN AIR DIFFUSER SCHEDULE DIFFUSER # USE TYPE MAAMODEL No R COMMENTS FC -6 rr CU -6 750/110 SUPPLY AIR CEILING DIFFUSER TITUS, TMS RECTANGULAR DIFUSER WITH OPPOSED BLADE DAMPER. 24x24 MODULAR. 1600 /SEE SCHEDULE SUPPLY AIR CEILING DIFFUSER TITUS, 250 AA RECTANGULAR DIFUSER WITH OPPOSED BLADE DAMPER. 59,500 SUPPLY AIR WALL REGISTER TITUS, 300 FS OPPOSED BLADE DAMPER. 72,700 13,000 41,500 RETURN AIR CEILING GRILLE TITUS, 50F EGG CRATE RETURN AIR REGISTER WITH ADJUSTABLE AND OPPOSED BLADE DAMPER. 10.0 5 RETURN AIR CEILING GRILLE TITUS, PAR PERFORATED, 24x24 MODULAR. AHU /CU SCHEDULE m UNIT NUMBER AHU -1 CU -1 FC -2 CU -2 FC -3, 4A, 4B CU -3, 4A, 4B FC -5 CU -5 FC -6 rr CU -6 750/110 FC -7 „ CU -7 m 1000 /100 SUPPLY CFM/ O/A CFM 3000/530 600/30 1600 /SEE SCHEDULE 650/110 TOTAL CAPACITY, BTU /HR. 92,000 18,000 59,500 29,000 29,000 29,000 SENSIBLE CAPACITY, BTU /HR. 72,700 13,000 41,500 20,500 20,500 20,500 HEATER CAPACITY (K.W.) 10.0 5 10.0 8.0 8.0 8.0 AIR TEMP. CONDENSER 95 'F 95 'F 95 'F 95 'F 95 'F 95 'F AIR TEMP. ENT. EVAP., DB /WB 80'/67 80'/67 80'/67 80' /6T 80' /6T 80'/6T VOLTAGE, PHASE 230/34/60 230/14/60 230/14/60 230/14/60 230/14/60 230/14/60 BLOWER HP 1.5 1/8 1.0 1/2 1/2 1/2 COMPRESSOR RLA /LRA 25/164 6.4/38.6 27.6/158 11.1/63 11.1/63 11.1/63 CONDENSER FAN HP -FLA 0.5 -3.1 1/8 -0.7 1/4 -1.3 1/8 -0.7 1/8 -0.7 1/8 -0.7 MCA /MOP 34.4/45 9/15 36/60 15/25 15/25 15/25 CONDENSING UNIT MODEL TTA090D300A 4TTB3018D1000A 4TTB306OD1000A 4TTB3030D1000A 4TT1330301000A 4TrB3030D1000A A.H.U. MODEL TWE090D300A 18HX 4TEE3F65B1000B 4TEE3F31B1000B 4TEE3F31B1000B 4TEE31731B100013 MANUFACTURER TRANE TRANE /FIRST CO. TRANE TRANE TRANS TRANE UNIT TYPE "' SPLIT, DX SPLIT, DX SPLIT, DX SPLIT, DX SPLIT, DX SPLIT, DX SEER /EER - -/11.2 13.0/ -- 13.25/ -- 13.25/ -- 13.25/ -- 13.25/- - AHU WEIGHT (LBS.) 323 88 218 134 134 134 AHU DIMENSIONS (HxWxD) 52.5x41.5x25.5 11x37.25x21 65x28.5x23.5 44.5x2423.5 44.5x2423.5 44.5x2423.5 COND.UNIT WEIGHT (LBS.) 298 110 251 195 195 195 NOTE: PROVIDE RAWAL VALVE AND SUCTION ACCUMULATOR FOR AHU /CU -3, 4A AND AB OUTDOOR AIR CALCULATIONS AS PER F.B.C. 2007. ASHRAE TABLE 6.1 ADDENDUM 62N -2001 LINEAR SUPPLY AIR DIFFUSER SCHEDULE DIFFUSER # MANUFACTURER MODEL # SLOTS SLOTS CFM COMMENTS SYSTEM DESIGNATION GF RETAIL AREA 2215 15 WIDTH PER FOOT __ �--� (A } TITUS ML -38 4 3/4" 25 CFM /FT PROVIDE W/ PLENUM MODEL MP -38 OUTDOOR AIR CALCULATIONS AS PER F.B.C. 2007. ASHRAE TABLE 6.1 ADDENDUM 62N -2001 AREA DESIGNATION FLOOR AREA (FT2) PERSONS/ 1000 FT2 TOTAL PERSONS CFM / PERSON CFM / FT2 CFM REQUIRED CFM PROVIDED SYSTEM DESIGNATION GF RETAIL AREA 2215 15 33 16 __ 528 530 AHU -1(N) 2F CORRIDOR /BOH 2335 -- _- -- 0.06 140 140 AHU -5(R), 6(N) 110 CFM EA 2F PRIVATE OFFICE 90 7 1 20 __ 20 20 2F STUDIO A 1080 30 32 20 __ 64.0 640 AHU -4A, 4B(N) 320 CFM EA 2F STUDIO B 660 30 19 20 __ 380 380 AHU -3(N) GF B.O.H. 250 _- -- -- 0.12 30 100 AHU -7(R) ENTRY STAIRS 173 -- -- -- 0.06 11 10 30 AHU -2(N) FAI FAI HVAC LEGEND SYMBOL DESCRIPTION I SYMBOL DESCRIPTION X DESIGNATION FOR SUPPLY DIFFUSER LETTER AND CFM SCALE: 1/40 = 1' -01, RETURN AIR GRILLE XXX revision ,. d 10 18 1 C}_ REV. r. g PXXq DESIGNATION FOR RETURN REGISTER NUMBER ® CEILING DIFFUSER EN &%y rl AND CFM 1 -0800 J •• M=3�X AIR HANDLING UNIT g�f • � a7 r � ( 4 • it NEW FIBERBOARD DUCTWORK © THERMOSTAT jx ..: t F :`r'•_ R.J. Miranda P.E. No. 35579 ELBOW WITH TURNING VANES ---� FIRE DAMPER /SMOKE DAMPER FD /SD WITH ACCESS PANEL EB0004041 s . ; - -+ FD FIRE DAMPER From Vision to Reality Mechanical Engineers REDUCERS AS INDICATED .% SUPPLY REGISTER OR GRILLE (VERTICAL MOUNT SIDEWALL) VD R/A RETURN /EXHAUST REGISTER OR STANDARD BRANCH TAKE -OFF -�- GRILLE (VERTICAL MOUNT SIDEWALL) O.A. LOUVER 6M FLEXIBLE DUCTWORK W /COLLAR ® EF -# EXHAUST FAN (CEILING TYPE) WITH VOLUME DAMPER BLITSTEIN DES11GN hitecture Interi 285 Sevilla Avenue Coral Gables, Fl 33134 (305) 444 -4433 project name Existing Building Renovation for. Continental Fidelity Corporation 5734 Sunset Drive South Miami, Florida project number 4 •bt k� b ; F' 4 date 'fr SCALE: 1/40 = 1' -01, 12/07/09 PROJECT N0; 0911 -093 revision ,. d 10 18 1 C}_ REV. r. g 4247 SW 71st AVENUE 11 /01 /10 Bb.C. Miami, Florida 33155 EN &%y rl 1 -0800 J •• M=3�X Fax; (305 ) 661 0811 g�f • � a7 r � ( 4 • it rt,J, ! ., ri r 1; tr - Email: ud @ucieng.com :'�•' ����'� jx ..: t F :`r'•_ R.J. Miranda P.E. No. 35579 �y, David A. Belsky P.E. W 37234 V e udengineering EB0004041 s . ; Professional Electrical and From Vision to Reality Mechanical Engineers BLITSTEIN DES11GN hitecture Interi 285 Sevilla Avenue Coral Gables, Fl 33134 (305) 444 -4433 project name Existing Building Renovation for. Continental Fidelity Corporation 5734 Sunset Drive South Miami, Florida project number 4 •bt k� b ; F' 4 date 'fr SCALE: 1/40 = 1' -01, 12/07/09 revision ,. d 10 18 1 C}_ REV. r. g 10/26/10 REV. 11 /01 /10 Bb.C. trawn by sheet title SCHEDULES AND NOTES 'fr SCALE: 1/40 = 1' -01, sheet number M=3�X jx - ---------- i'