Loading...
09-1112-039NOTE : ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH CIRCUIT, POSITION AND CONNECTION. ALL PANELS SHALL HAVE UPDATED BRANCH CIRCUITS LABELS. LOAD CALCULATION MAIN 1/2 LOAD CALCULATION MAIN 2/2 PANEL "AC" 47,000 VA ELEVATOR 30,000 VA PANEL "P1" 45,000 VA PANEL "P2" 55,538 VA 92,000 VA 221 AMPS VA 85,538 VA 206 AMPS VA WIRE LEGEND TYPE AQ, G. E. MAINS M.L.O. MOUNTING SURFACE 22,000 A.I.C. BUS RATING 200 AMP LOCATION STORAGE ROOM VOLTAGE 120/24OV- 3PHASE -4WIRE DESCRIPTION WIRE & COND. SIZE 4- #350MCM THWN CU IN 3" CKT. No. �J 4- #350MCM THWN CU + 1 - #2 CU GROUND IN 3" 0 1 - #2 THWN CU GROUND IN 1/2" LOAD (V.A.) O 4 - #3 THWN CU + 1 - #8 CU GROUND IN 1 1/4" �5 4 - #3/0 THWN CU + 1 - #4 CU GROUND IN 2" O 4-#1/0 THWN CU + 1 - #6 CU GROUND IN 2" J EXISTING. VERIFY MINIMUN OF SPACE(HIGH -LEG 4 - #3 THWN CU + 1 - #8 CU GROUND IN 1 1/4" O EXISTING. VERIFY MINIMUN OF #6 -3/4" 10,000 4 - #3/0 THWN CU + 1 - #4 CU GROUND IN 2" O EXISTING. VERIFY MINIMUN OF EXISTING 1,000 4-#1/0 THWN CU + 1 - #6 CU GROUND IN 2" RELOCATED ELEVATOR MACHINE ROOM (EXISTING) PANEL - 120/240 V i 200 A i 3 PH MID I W i 22,000 AIC � (EXISTING) � (DISC SWITCHI i 3� 100 NEW FPL SERVICE L_ ( i _ 3PH, 120/240V, OPEN DELTA I J 4 #350MCM THWN CU IN 3" NEW FPL SERVICE SECOND FLOOR 3PH, 120/240V, OPEN DELTA - 4 #350MCM THWN CU IN 3" i MAIN ELECTRICAL ROOM I NEW NEW o300A 300 NEW GUTTER 8X8 AS REQ. Lj�, NEW GUTTER 8X8 AS REQ. 2 I (EXISTING) i I (EXISTING) i ELECTRICAL ELECTRICAL 4 5 5 6 PANEL - "AC" PANEL - "P1" METER METER _ _ 120/240 V I I 120/240 V 1 1 I(EXISTING)� (EXISTING) F (EXISTING) �(D(ISTING)� i I 200 A i � i 3 PMLO W i i 3 PMLO W NEW N DISC SWITCH DISC SWITCH CBkr CBkr i 3P144 I 3244 i i 200 AMPS i 150 AMPS I I I I I DISC SWITCH DISC SWITCH i 100 i i 200 i ( 3P i i 3P 22,000 AIC� 22,000 AIC� i 3P 3P L -I -J L_ -I -J L_ -J L_ -J I I- MAIN 1/2 MAIN 2/2 1`7 I s 18 I s I I I i L- -- - -- -- - -- i 3 3 I I-------- - - - - -- -------- ____ - - --� COLD WATER -1-- PIPE - (2) 5/8" X 10' DRIVEN GROUND RODS, COPPERCLAD, TO BE SEPARATED 6' -0" MINIMUM #2/0 CU IN 3/4 "C TO BUILDING STEEL FOUNDATION EXISTING ELECTRICAL PANEL SCHEDULE "P1" TYPE AQ, G. E. MAINS M.L.O. MOUNTING SURFACE 22,000 A.I.C. BUS RATING 200 AMP LOCATION STORAGE ROOM VOLTAGE 120/24OV- 3PHASE -4WIRE DESCRIPTION WIRE & COND. SIZE LOAD (V.A.) 74RIP CKT. No. A A B C CKT. No. POL XTRIP LOAD (V.A.) WIRE' & COND. SIZE DESCRIPTION EXISTING EXISTING 1,000 1 20 1 2 1 20 1,000 EXISTING EXISTING EB0004041 SPACE(HIGH -LEG 4 Mechanical Engineers 3 4 AHU -4A #6 -3/4" 10,000 SPACE(HIGH -LEG) 5 6 2 40 5,000 EXISTING EXISTING 1,000 1 20 5 6 1 20 1,000 EXISTING EXISTING AHU -5 #10 -1/2" EXISTING EXISTING 1,000 1 20 7 8 1 20 1,000 EXISTING EXISTING 19 10 SPACE(HIGH -LEG) 9 10 1 4,000 2 X25 13 SPACE(HIGH -LEG) 2 20 2,500 #12 -1/2" CU -6 (NON COIN. LOAD) EXISTING EXISTING 1,000 1 20 11 12 _1,--2 0 1,000 EXISTING EXISTING AHU -2 #10 -1/2" 4,000 2 X25 EXISTING EXISTING 1,000 20 13 14 1 20 1,000 EXISTING EXISTING 19 20 SPACE(HIGH -LEG) AHU -4B #6 -3/4" 15 16 21 22 2 40 SPACE(HIGH -LEG) #8 -3/4" CU -4B (NON COIN.LOAD) EXISTING EXISTING 1,000 1 20 17 18 1 20 1,000 EXISTING EXISTING 25 26 EXISTING EXISTING 1,000 1 2p 19 20 1 20 1,000 EXISTING EXISTING 27 28 SPACE(HIGH -LEG) SPACE(HIGH -LEG) 21 22 SPACE 1 SPACE(HIGH -LEG) 29 30 EXISTING EXISTING 1,000 1 20 23 24 1 20 1,000 EXISTING EXISTING 31 32 EXISTING EXISTING 1,000 1 2p 25 26 1 20 1,000 EXISTING EXISTING 33 34 SPACE(HIGH -LEG) SPACE(HIGH -LEG) 27 28 SPACE SPACE(HIGH -LEG) 35 36 EXISTING EXISTING 1,000 1 20 29 30 1 20 1,000 EXISTING EXISTING 37 38 EXISTING EXISTING 1,000 1 20 31 32 1 20 1,000 EXISTING EXISTING 39 40 SPACE(HIGH -LEG 33 34 41 SPACE(HIGH -LEG) CONTACTOR EXISTING EXISTING 1,000 j-,--2'0 35 36 1 20 400 #12 -1/2" ROOF RECEPT. LOAD CALCULATION PANEL 'P2' CONTINUOUS LOAD AT 125% = 0 VA NON CONTINUOUS LOAD AT 100% = 55,538 VA TOTAL DEMANDED LOAD = 55,538 VA TOTAL DEMAND AMPS = 134 AMPS PER PHASE EXISTING PNL "L" EXISTING 20,000 /100 37 38 1 20 1,000 EXISTING EXISTING 39 40 SPACE(HIGH -LEG) 41 42 CONTACTOR * CONTROLLED BY TIME CLOCK THROUGH LIGHTING LOAD CALCULATION PANEL 'P1' CONTINUOUS LOAD AT 125% = 0 VA X 1.25 = 0 VA NON CONTINUOUS LOAD AT 100% = 0 VA TOTAL DEMANDED LOAD = 45,000 VA TOTAL DEMAND AMPS = 110 AMPS PER PHASE EXISTING ELECTRICAL PANEL SCHEDULE "P271 TYPE AQ, G.E. MAINS : M.L.O. MOUNTING SURFACE 22,000 A.I.C. BUS RATING 200 AMP LOCATION STORAGE ROOM VOLTAGE 120/24OV- 3PHASE -4WIRE DESCRIPTION WIRE & COND. SIZE LOAD (V.A.) POL TRIP CKT. No. A RISER B C CKT. No. POL TRIP LOAD (V.A.) WIRE & COND. SIZE DESCRIPTION AHU -3 #6 -3/4" 10,000 �X601 1 2 2 40 51000 #8 -3/4" CU -3 (NON COIN.LOAD) EB0004041 3 4 Mechanical Engineers AHU -4A #6 -3/4" 10,000 2 60 5 6 2 40 5,000 #8 -3/4" CU -4A (NON COIN.LOAD) 7 g AHU -5 #10 -1/2" 4,000 �Z2 5 2 25 3,000 #10 -1/2" (NONCCOIN.LOAD) 19 10 AHU -6 #10 -1/2" 1 4,000 2 X25 13 14 2 20 2,500 #12 -1/2" CU -6 (NON COIN. LOAD) 15 16 AHU -2 #10 -1/2" 4,000 2 X25 17 18 2' 25 3,000 #10 -1/2" CU -2 (NON COIN.LOAD) 19 20 AHU -4B #6 -3/4" 10,000 2 X60 21 22 2 40 5,000 #8 -3/4" CU -4B (NON COIN.LOAD) 23 24 SPACE 25 26 SPACE SPACE(HIGH -LEG) 27 28 SPACE(HIGH -LEG) SPACE 29 30 SPACE SPACE 31 32 SPACE SPACE(HIGH -LEG) 33 34 SPACE(HIGH -LEG) SPACE 35 36 SPACE SPACE 37 38 3 100 13,538 #3 -1 1/4" PANEL "P3" SPACE(HIGH -LEG) 39 40 SPACE 41 42 CONTACTOR * CONTROLLED BY TIME CLOCK THROUGH LIGHTING LOAD CALCULATION PANEL 'P2' CONTINUOUS LOAD AT 125% = 0 VA NON CONTINUOUS LOAD AT 100% = 55,538 VA TOTAL DEMANDED LOAD = 55,538 VA TOTAL DEMAND AMPS = 134 AMPS PER PHASE NOTE : ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH CIRCUIT, POSITION AND CONNECTION. ALL PANELS SHALL HAVE UPDATED BRANCH CIRCUITS LABELS. CIRCUIT, POSITION AND CONNECTION. ALL PANELS ELECTRICAL RISER AND PANEL SCHEDULES Tel: (305) 661 -0800 Fax: (305) 661 -0811 NOTE : ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH CIRCUIT, POSITION AND CONNECTION. ALL PANELS SHALL HAVE UPDATED BRANCH CIRCUITS, LABELS. BLITSTEIN DESIGN ASSOCIATES Architecture Interior Design 285 Sevilla Avenue Coral Gables, FI 33134 (305) 444 -4433 project name Existing Building Renovation for Continental Fidelity Corporation 5734 Sunset Drive South Miami, Florida project number date 12/07/09 revision drawn by AR, F.G, J.I_, G.R sheet title ELECTRICAL RISER AND PANEL SCHEDULE SCALE: 1/4" = V -0" 4247 SW 71st AVENUE sheet n u m b e r Miami, Florida 33155 Tel: (305) 661 -0800 Fax: (305) 661 -0811 Email: uci @ucieng.com E=3 R.J. Miranda P.E. No. 35579 David A. Belsky P.E. No. 37234 EB0004041 Professional Electrical and Mechanical Engineers