13-675-007System No. HIV-D -01.34
January 24, 2006
N
in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
Assembly Rating- I and 2 W (See Item 2)
A. Studs -Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
lumber spaced 16 in, (406 mm) OC. Steel studs to be min 3 -1 /2 in. ( 89 ram) wide and spaced max 24 in. (610 mm) OC.
L Rating At Ambient - 4 CFM/Lin Ft
p
The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
L Rating At 400 F -6 CFM/I in Ft
4
sizes of nonmetallic pipes or conduits may be used:
Nominal Joint Width -3/4 In.
C
O
B. Rigid Nonmetallic Conduit-f-I - -Nom 4 in. (102 mm) diani (or smaller) Schedule 40 PVC conduit installed in accordance with
Class 11 Movement Capabilities -17% Compression or Extension
,
(process or supply) piping systems.
1 313 A 3S
U
�
E. Fire Retardant Polypropylene (FRPP) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed
(process or supply) or vented (drain, waste or vent) piping system.
3. Firestop System -The details of the firestop system shall be as follows:
A. Fill, Void or Cavity Materials* --Wrap Strip -Nom 1/8 in. (3.2 mm) thick intumescent material supplied in 2 in. (51 mm) wide
--
0
layer is required. For nom 2 -1/2 in. and 3 in. (62 and 76 mm) diam pipes, two layers are required. For nom 3 -1/2 in. and 4 in. (89 and
102 mm) diam pipes, three layers are required. Wrap strip layers temporarily held in position using aluminum foil tape, steel wire tie,
or equivalent.
3M CONIPArNY -Ultra GS
-__._. - ----- - --
II 11 3A
(13 mrn) long tabs to retain wrap strip layers. Coils of precut 0.016 in. (0.41 mm) thick (28 gauge) galv sheet steel available from wrap
strip manufacturer. As an alternate, collar may be field- fabricated from min 0.016 in. (0.41 mm) thick (28 gauge) galv sheet steel in
accordance with instruction sheet supplied by wrap strip manufacturer. Steel collar, with anchor tabs bent outward 90 deg, wrapped
tightly around wrap strip layers with ruin 1 in. (25 nun) overlap at seam. Anchor tabs to be pressed tightly against wall surfaces, and
collar to be compressed around wrap strip layers using a min 112 in. (13 mm) wide by 0,028 in. (0.71 mm) thick stainless steel band
ZA
zc
�
G,
wall surfaces with 3/16 in. (5 mm) diam steel toggle bolts, or equivalent, in conjunction with min 1 -1/4 in. (32 nun) diam steel fender
A za
,:M
5��
C_ Fill, Void or Cavity Materials* - Caulk, Sealant or Putty (Not Shown) - Min 1/2 in. (13 mm) diam bead of caulk or putty shall be
2C SECTION A -A
31NI COMPANY -CP 25WB +, IC 15WB +, FireDam 150+ caulk, FB -3000 WT sealant or MP +putty
(Note: CP 25 WB +not suitable for use with CPVC pipes. CP 25WB +not suitable for use with CPVC pipes.)
1. F1oorAssembly -Min 4 -1/2 in. (114 nun) thick lightweight or normal weight (100 -150 pef or 1600 -2400 kg/m') concrete.
' 'M
Anchors Strips or with 1/4 in. (6 mm) diam by nun 1 -1/2 in. (38 mm) long steel toggle bolts in conjunction with min 1 -1/4 in. (32 rani)
2. WallAssembly -The I or 2 fire rated gypsum wallboard/steel stud wall assembly shall be constructed of the materials and in the manner
g
3M COMPANY - Ultra RC Pack 2.0, 3.0, 4.0
described in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include then
`
This material was extracted and drawn by 3M Fire Protection Products from the 2001 edition of the UL Fire Resistance Directory. Canada closed only. c UL us
following construction features:
�
Choose option 4 for FAX ON DEMAND
A. Steel Floor And Ceiling Runners -Floor and ceiling runners of wall assembly shall consist of galy steel channels sized to
Features
B. Limitations
accommodate steel studs (Item 213). When U- shaped deflection channel (Item 3A) is used, ceiling runner installed within the
Do not apply 3MT1 FireDamT"" 150+
weather resistant and exhibits
deflection channel with 1 in. (25 min) gap maintained between the top of ceiling runner and top of deflection channel. When deflection
'
temperature is less than 40 "F
channel is not used, ceiling runner secured to concrete floor slab with steel masonry anchors spaced a max o£24 in. (610 mm) OC.
(4 °C) and in conditions when seals
• Excellent adhesion
Al. Light Gauge Rraming *- Slotted Ceiling Runner --As an alternate to the ceiling runner in Item 2A, slotted ceiling runner to
consist of steel with slotted flanges to 213). Slotted
• Compression /extension recovery
spray for 12 to 18 hours, Also do
galv channel sized accommodate steel studs (Item ceiling Tuner secured to
not apply under the following
• Re- enterable /repairable
concrete floor slab with steel masonry anchors spaced max 24 in. (610 nun) OC. When slotted ceiling runner is used, deflection
• Cures upon exposure to
• Building materials that bleed oil,
channel (Item 3A) shall not be used
plasticizers or solvent (e.g.,
• Applied with conventional
METAL -LITE INC -The System
caulking equipment
caulks, green or partially
• Paintabie
SCAFCO STEEL STUD MANUFACTURING CO, SLIPTRACK SYSTEMS INC - SLP -TRK
• Wet or frost - coated surfaces
A2. Light Gauge Framing* -- Clipped Ceiling Runner --As an alternate to the ceiling runner in Items 2A and 2A1, clipped runner
• Areas that are continuously
703.2 713.4
to consist of galy steel channel with clips preformed in track flanges which positively engage the inside flange of the steel studs
ROOF /CEILING
(Item 213). Track sized to accommodate steel studs (Item 2B). Track flanges to be min. 2 -1/2 in. (64 mm). Clipped ceiling runner
BARRIERS
PENETRATION
secured to concrete floor slab with steel masonry anchors spaced max 24 in, (6 10 mm) OC. When clipped ceiling runner is used,
THAN TWO STORIES REFERS TO 714
deflection channel (Item 3A) shall not be used.
SHALL INDICATE
TOTAL STEEL SOLUTIONS L L C - Snap Trak
705.6 (FLOORS)
A3. Light Gauge Framing* - Notched Ceiling Runner --As an alternate to the ceiling runners in Items 2A through 2A2, notched
711.3
ceiling runners to consist of C- shaped galv steel channel with notched return flanges sized to accommodate steel studs
JOINTS- REFERSTO 709.7
(Item 2B). Notched ceiling runner secured to concrete floor slab with steel masonry anchors spaced max 24 in. (6 10 nun) OC.
705.7
704.1.1
When notched ceiling runner is used, deflection channel (Item 3A) shall not be used.
FIRE RESISTANT
DENMAR STEEL INC -Type SCR
714
JOINT SYSTEMS
R Studs - Steel studs to be min 3 -5/8 in. (92 nun) wide. Studs cut 1/2 to 3/4 in. (13 to 19 mm) less in length than assembly height. Studs
Code 70 NEC
THROUGH-
attached to ceiling runner with sheet metal screws a min of 1/2 in. (13 mm) below bottom of deflection channel, when deflection
TO JUSTIFY UNTESTED REQUIREMENTS
channel is used. When deflection channel is not used, steel studs shall not be secured to ceiling runner. When slotted ceiling runner
MATERIALS USED FOR (GENERAL)
(Item 2A 1) is used, steel studs secured to slotted ceiling runner with No. 8 by 1/2 in. (13 nun) long wafer bead steel screws at midheight
INTERNATIONAL
FIRESTOPS F &T
of slot on each side of wall. Stud spacing not to exceed 24 in. (6 10 mm) OC.
Electric Code
REQUIREMENTS
C. Gypsum Board* - Gypsum board sheets installed to a min total thickness of 5/8 in. (16 mm) and 1 -1/4 in. (32 nun) on each side of
RATINGS 714.1 THROUGH 714.1.6.2
wall for a I or 2 fir rated assemblies, respectively, Wall to be constructed as specified in the individual Wall and Partition Design in the
BUILDING CODE
WALL ASSEMBLIES
UL Fire Resistance Directory, except that a nom 3/4 in. (19 mnu) gap shall be maintained between the top of the gypsum board and the
UBC STANDARD 7 -1
( 2003 Edition)
lower surface of the floor, The screws attaching the gypsum board to studs at the top of the wall shall be located 1 in. (25 mm) below
300 21 FIRESTOPPING
EQUIVALENTTO
the bottom of the U- shaped deflection channel (Item 3A) or slotted ceiling runner ner (Item 2AI).
FIRE WALLS AND 714.2 THROUGH 714.2.6.5
The hourly fire rating of the joint system is dependent on the hourly fire rating of the wall.
PARTY WALLS FLOORICEILING AND
3. Joint System --Max separation between bottom of floor and top of wall is 314 in. (19 mm). The joint system is designed to
UBC STANDARD 7 -5
702
DEFINITIONS
accommodate a max 17 percent compression or extension from its installed width. The joint system consists of a deflection charnel
CABO
forming material and a fill material, as follows:
712
PENETRATIONS -
REFERS TO 714
A. Deflection Channel -- (Optional) -A nom 3 -3/4 in. (95 nun) wide by min 2 in. (51 mm) deep mitt 24 ga steel U- shaped channel.
ASTM E 814
PENETRATIONS
Deflection channel secured to concrete floor slab with steel masonry anchors or by welds spaced max 24 in. (6 10 mm) OC. The ceiling
Family Dwelling
runner (Item 2A) is installed within the deflection channel to maintain a I in, (25 min) gap between the top of the ceiling runner and the
7028 NONRATED
ASSEMBLIES
Code
top of the deflection channel. The ceiling runner is not fastened to the deflection channel.
NFPA 5000
713
B. Fill, Void or Cavity Material* - Caulk ---Min 5/8 in. (16 turn) thickness of fill material installed on each side of the wall between the
ak
(2006 EDITION)
top of the gypsum board and bottom of floor, flush with cacti surface of gypsum board.
721'0
3M COMPANY -FU -150+
709.0 FIREBLOCKiNG AND
*Bcaring the UL Classification Mark
8.8
This material was extracted and drawn by 3M Fire Protection Products from the 2001 edition of the UL Fire Resistance Directory. a UI us
FIRESTOPPING
PENETRATIONS
e I70.tt'e i01I P.iOKiUCtS - PrododSupport,hne l-, 9 32$ 1687
ASSEMBLIES
(FiREBLOCKNG IN OTHER
www 3m com /`firestop HEN D 0134 * 1 (hooseop ono
0! 1 option for FAX Ohl QFMAND
%3
709.6
System No. vV L -2147
May 23, 2005
F Rating -1 And 2 IIr (See Item 1)
T Rating --1 And 2 Hr (See Item 1)
SECTION A -A
1. Wall Assembly -The 1 or 2 In: fire rated gypsum board/stud wall assembly shall be constructed of die materials and in the manner specified
in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs -Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
lumber spaced 16 in, (406 mm) OC. Steel studs to be min 3 -1 /2 in. ( 89 ram) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Design, Max diam
of opening is 5 i u. (127 Turn).
The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrants - One nonmetallic pipe or conduit to be centered within opening with a nom 1/4 in, (6 mm) annular space between
pipe or conduit and periphery of opening. Pipe or conduit to be rigidly supported on both sides of the wall assembly. The following types and
sizes of nonmetallic pipes or conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe -Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in
closed (process or supply) or vented (drain, waste or vent) piping system.
B. Rigid Nonmetallic Conduit-f-I - -Nom 4 in. (102 mm) diani (or smaller) Schedule 40 PVC conduit installed in accordance with
Article 347 of the National Electrical Code (NFPA No. 70). '
C. Chlorinated Polyvinyl Chloride (CPVC) Pipe --Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for ruse in closed
(process or supply) piping systems.
D, Acrylonftritle Butadiene Styrene (ABS) Pipe -Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid core or cellular core ABS
pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
E. Fire Retardant Polypropylene (FRPP) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed
(process or supply) or vented (drain, waste or vent) piping system.
3. Firestop System -The details of the firestop system shall be as follows:
A. Fill, Void or Cavity Materials* --Wrap Strip -Nom 1/8 in. (3.2 mm) thick intumescent material supplied in 2 in. (51 mm) wide
strips. Wrap strip tightly wrapped around nonmetallic pipe with continuous layers and butted tightly against both surfaces of the wall.
The nun number of layers required is dependent upon the nom diam of the pipe. For nom 2 in. (51 mm) diam (and smaller) pipes, one
layer is required. For nom 2 -1/2 in. and 3 in. (62 and 76 mm) diam pipes, two layers are required. For nom 3 -1/2 in. and 4 in. (89 and
102 mm) diam pipes, three layers are required. Wrap strip layers temporarily held in position using aluminum foil tape, steel wire tie,
or equivalent.
3M CONIPArNY -Ultra GS
B, Steel Collar --Nom 2 in. (51 nun) deep collar with 1 -1/4 iii. (32 nun) wide by 2 in. (51 mm) long anchor tabs and min 1/2 in,
(13 mrn) long tabs to retain wrap strip layers. Coils of precut 0.016 in. (0.41 mm) thick (28 gauge) galv sheet steel available from wrap
strip manufacturer. As an alternate, collar may be field- fabricated from min 0.016 in. (0.41 mm) thick (28 gauge) galv sheet steel in
accordance with instruction sheet supplied by wrap strip manufacturer. Steel collar, with anchor tabs bent outward 90 deg, wrapped
tightly around wrap strip layers with ruin 1 in. (25 nun) overlap at seam. Anchor tabs to be pressed tightly against wall surfaces, and
collar to be compressed around wrap strip layers using a min 112 in. (13 mm) wide by 0,028 in. (0.71 mm) thick stainless steel band
clamp at the middle of collar: As an alternate to the band clamp, collar for systems with three or more layers of wrap strip may be
fastened together along the overlapping seam with three No. 6 by 3/8 in. (10 mm) long self- tapping steel screws. Collar to be secured to
wall surfaces with 3/16 in. (5 mm) diam steel toggle bolts, or equivalent, in conjunction with min 1 -1/4 in. (32 nun) diam steel fender
washers. Min of two, three or four anchor bolts, symmetrically located, for nom 2 in. (51 mm) diam (and smaller), nom 3 in (76 mrn)
diam (and smaller) and nom 4 in, (102 mm) diam (and smaller), pipes, respectively.
C_ Fill, Void or Cavity Materials* - Caulk, Sealant or Putty (Not Shown) - Min 1/2 in. (13 mm) diam bead of caulk or putty shall be
applied to outer perimeter of collar at its interface with wall surface(s).
31NI COMPANY -CP 25WB +, IC 15WB +, FireDam 150+ caulk, FB -3000 WT sealant or MP +putty
(Note: CP 25 WB +not suitable for use with CPVC pipes. CP 25WB +not suitable for use with CPVC pipes.)
D. Firestop Device* -As an alternate to Items 3A and 3B, firestop device to be installed in accordance with the accompanying
installation instructions. Firestop device to be installed and latched around pipe and secured to both sides of wall with Ultra Fast
Anchors Strips or with 1/4 in. (6 mm) diam by nun 1 -1/2 in. (38 mm) long steel toggle bolts in conjunction with min 1 -1/4 in. (32 rani)
diam steel fender washers. Min of two, three or four anchor straps or anchor bolts symmetrically located, for nom 2 in„ 3 in. and 4 in.
(51 mm, 76 mm and 102 mm) diam pipe respectively.
3M COMPANY - Ultra RC Pack 2.0, 3.0, 4.0
++Bearing the UL Listing Mark
*Bearing the UL Classification Mark
This material was extracted and drawn by 3M Fire Protection Products from the 2001 edition of the UL Fire Resistance Directory. Canada closed only. c UL us
`IhCB "Y'iQtEC(IOall tic 's, Pr, "oduciSbp'pb Line 1 8{U 32$
www.3m.com /firestop W4.2 147 • 0f
Choose option 4 for FAX ON DEMAND
--i
O
C
Cc�
`L7
m
N
O
Q
1/t
CO
O
O
O
C/)
(D
tD
Gi
N
C
all
J L►- A
System No. AVL -319:4)
December 12, 2006
F Ratings - I and 2 Hr (See Item 1)
T Ratings -0 and 1/2 Hr (See Item 1)
� I
3
1A
_�_ 1B
V
SECTION A -A
1, WallAssembly --The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in tie manner described
in the individual U300, U400 or V400 Series Wail and Partition Design in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs -Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3 -1/2 in. (89 mm) wide spaced max 24 in. (610 mm) OC,
B. Gypsum Board* -The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specked in the
individual Design in the UL Fire Resistance Directory. Max diam of opening is 5 in. (127 mm).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. The hourly
T Rating is 0 and 1/2 Hr for i and 2 Hr fire rated assemblies, respectively.
2. Steel Sleeve - (Optional) - Cylindrical sleeve fabricated from min 0.018 in. (0.46 mm) thick (No. 28 gauge) galv sheet steel and having a
min 1 in. (25 mm) lap along the longitudinal seam. Length of sleeve to be equal to or max 2 in. (51 mm) greater than the thickness of wall.
Ends of sleeve to be flush with or extend a max I in. (25 mm) beyond each surface of wall,
3. Cable -Max 4 in. (102 mm) diam cable bundle installed eccentrically or concentrically within opening. Annular space between cable
bundle and periphery of opening or sleeve to be min. 0 in. (0 nun, point contact) to max 1 in. (25 mm). Cable bundle to be rigidly supported
on both sides of wall. The following types and sizes of cables may be used:
A. Max 200 pair No. 22 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) insulation and jacketing material.
B. Max I/C No. 350 kcmil (or smaller) copper conductor cable with cross - linked polyethylene (XLPE) or PVC jacket,
C. Max 71C No. 12 AWG (or smaller) copper conductor power and control cAles with XLPE or PVC insulation with XLPE or PVC
jacket.
D. Max 3/C No. 2/0 AWG (or smaller) copper or aluminum conductor SER cables with XLPE or PVC insulation and jacket.
E. Max 4/C No. 2/0 AWG (or smaller) copper conductor, aluminum clad or steel clad TECK 90 cable with or without PVC jacketed.
F Max 110/125 fiber optic (FO,) cable with PVC insulation and jacket.
G. Max 31C with ground No. 8 AWG (or smaller) copper conductor NM cable with PVC insulation and jacket.
H. Max RG/U coaxial cable with fluorinated ethylene insulation and jacket.
I. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Ilylar jacket and insulation,
J. Through Penetrating Product* --Any cables, Armored Cable+ or Metal Clad Cable-l- currently Classified under the Through
Penetrating Product category.
See Through Penetrating Product (XHLY) category in the Fire Resistance Directory for names of manufacturers.
4. Fill, Void or Cavity Material* - Caulk or Sealant -Min 5/8 in, (16 nun) thickness of caulk applied within annulus, flush with both
surfaces of wall. Min 1/4 in. (6 nun) diam bead of caulk applied to gypsum board/cable bundle interface at point contact location on both
sides ofivall.
3M COMPANY -IC 15WB +, CP 25WB-I- caulk or FB -3000 WT sealant
*Bearing the UL Classification Mark
This material was extracted and drawn by 3M Fire Protection Products from tlne 2006 edition of file UL Fire Resistance Directory. c UL us
OEC1
t Qii. P S,:, .. .
i'0C)IliCt ,
_... .. .. __ . _ _ _.•_ _ ,.; _ _.. Product SaPPtln Line. T $00 32F
w
O
O
O
CV
oz, cartridges and 4,5 gal. pail.
8. Safe Handling Information
Consult Material Safety Data Sheet
prior to handling and
disposing of 3Mrm FireDamTM 150+
Caulk.
Warranty and Limited Remedy, This product will be free from defects in materials and manufacture for a period of ninety (90) days from
date of purchase, 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, User is responsible for determining whether the 3M product is fit for
a particular purpose and suitable for user's application. If this 3M product is defective within the warranty period stated above, your
exclusive remedy and 3M's sole obligation shall be, at 3M's option, to replace the 3M product or refund the purchase price of the 3M product.
CL
0 Limitation of Liabti{i Except where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product,
whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, contract,
negligence or strict liability.
Building and Commercial Services Division
3M Center, Bldg, 223 -2S -24
St. Paul, MN 55144 -1000
Phone 800 -328 -1687
Fax 888 -362 -2737
www3m.com/firestop
WAYNE E. DENIMS
ARCHITECT & PLANNER
FLORIDA REGISTRATION No. 5561
P.O. BOX 143551
CORAL GABLES , FLORIDA 33114
TEL: (305) 661 0711
c!
l
1
3.;i
3r tike q�•pfRiA� "1�,-
Printed in U.S.A. Bolger 7020246
CO 3M 2006 98- 0400 - 4974 -8 Aug. 2006
liq
i.
Product Data
SSIFj��
5. installation Techniques
6. Maintenance
O
Extrusion Rate: 25 -30 g /sec
• No sag formulation
tP* W ��*
4s a7
Consult your 3M Authorized Fire
3MT" FireDamTM 150+ Caulk is
L
Protection Products
stable under normal storage
mDistributor
/Dealer for drawings and
conditions. Shelf life is 12 months
Q_
system details.
from date of manufacture when
8857
ASTM E 84
stored in a clean, dry area with
A. 3MT"' FireDam ""' 150+ Caulk is
Installation Notes:
temperatures between 40'F and
o
• Clean surface of the opening
90 °F (4 °C and 32 °C). Avoid
such as, metallic pipes,
and all penetrating items to
repeated freeze /thaw of 3MT`^
component acrylic latex elastomer
allow proper adhesion of firestop
FireDam " 150+ Caulk while still in
conduits. Controls the spread of
materials.
• Install damming materials as
packaging.
flexible seal. 3M T"` FireDamTM 150+
z
necessary to meet requirements
% Availability
penetrations through floor slabs,
of appropriate system.
walls and other fire -rated building
�5,
• Install the proper amount of
3MT" FireDamT"" 150+ Caulk is
FireDamT"' 150+ Caulk, when
3MT" FireDamT"" 150+ Caulk for
available from 3M Authorized Fire
. -:
appropriate system and rating.
Protection Products Distributors
after exposure to fire.
• Metallic pipes
and Dealers. Caulk is available in
• Construction joints
3MT1" FireDam 150+ Caulk
10.1 oz., 20.0 oz. sausage, 28.0
w
O
O
O
CV
oz, cartridges and 4,5 gal. pail.
8. Safe Handling Information
Consult Material Safety Data Sheet
prior to handling and
disposing of 3Mrm FireDamTM 150+
Caulk.
Warranty and Limited Remedy, This product will be free from defects in materials and manufacture for a period of ninety (90) days from
date of purchase, 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, User is responsible for determining whether the 3M product is fit for
a particular purpose and suitable for user's application. If this 3M product is defective within the warranty period stated above, your
exclusive remedy and 3M's sole obligation shall be, at 3M's option, to replace the 3M product or refund the purchase price of the 3M product.
CL
0 Limitation of Liabti{i Except where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product,
whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, contract,
negligence or strict liability.
Building and Commercial Services Division
3M Center, Bldg, 223 -2S -24
St. Paul, MN 55144 -1000
Phone 800 -328 -1687
Fax 888 -362 -2737
www3m.com/firestop
WAYNE E. DENIMS
ARCHITECT & PLANNER
FLORIDA REGISTRATION No. 5561
P.O. BOX 143551
CORAL GABLES , FLORIDA 33114
TEL: (305) 661 0711
c!
l
1
3.;i
3r tike q�•pfRiA� "1�,-
Printed in U.S.A. Bolger 7020246
CO 3M 2006 98- 0400 - 4974 -8 Aug. 2006
liq
i.
Product Data
SSIFj��
Typical Performance Properties (As Cured)
Slump Resistance (ASTM D 2202): Pass
• Water clean -up
Extrusion Rate: 25 -30 g /sec
• No sag formulation
tP* W ��*
4s a7
• Two colors, sky blue and
Cure Time (77 °F, 25 °C, 50% R.R): 14 -45 days
limestone
(Depends on thickness)
Application Temperature Range
• Resists dirt pick -up after cure
RII, aterials
For Use in Through - Penetration
• No priming required
Firestop Systems and Joint Systems
UV and Ozone Resistance: Good
See UL Fire Resistance Directory
2. Applications
8857
ASTM E 84
A. 3MT"' FireDam ""' 150+ Caulk is
1. Product Description
ideal for sealing construction
706
joints and through - penetrations
3M'"° FireDamT"" 150+ Caulk is a
such as, metallic pipes,
ready to use, gun - grade, one-
conduits, power and
component acrylic latex elastomer
communication cables and
that cures upon exposure to the
conduits. Controls the spread of
atmosphere to form a monolithic
fire, limits the spread of noxious
flexible seal. 3M T"` FireDamTM 150+
gas, smoke and water.
Caulk firestops openings and
Maintains the integrity of fire
penetrations through floor slabs,
rated construction.
walls and other fire -rated building
FLOORS
partitions. and assemblies. 3MT"
Primary firestopping applications:
FireDamT"' 150+ Caulk, when
• Telephone, signal and control
installed properly helps control the
and power cables
spread of fire before, during and
• Metallic conduit
after exposure to fire.
• Metallic pipes
PROVIDING RATINGSAT OINTS -REFER TO 709.7
J
• Construction joints
3MT1" FireDam 150+ Caulk
CONSTRUCTION
Features
B. Limitations
Sealant remains elastomeric,
Do not apply 3MT1 FireDamT"" 150+
weather resistant and exhibits
Caulk when surrounding
excellent adhesion to a full range of
temperature is less than 40 "F
construction substrates.
(4 °C) and in conditions when seals
• Excellent adhesion
may be exposed to rain or water
• Compression /extension recovery
spray for 12 to 18 hours, Also do
of +/ -19% of original joint width
not apply under the following
• Re- enterable /repairable
conditions.
• Cures upon exposure to
• Building materials that bleed oil,
atmosphere
plasticizers or solvent (e.g.,
• Applied with conventional
impregnated wood, oil based
caulking equipment
caulks, green or partially
• Paintabie
vulcanized rubber)
• Wet or frost - coated surfaces
FLOORICEILING OR
• Areas that are continuously
703.2 713.4
damp or immersed in water
4. Performance
3. Specifications
Materials
A. The fire stopping sealant is a
one component, ready to
use, gun grade, acrylic latex
elastomer. The sealant shall
be listed by independent test
agencies such as UL, FM or
Intertek/OPL and be tested to
and pass the criteria of
ASTM E 814 (UL 1479)
Standard Test Method for
Fire Tests of Through -
Penetration Fire Stops and
ASTM E 1966 (UL 2079)
Standard -test Method for
Fire- Resistive Joint Systems.
It shall comply with the
requirements of the NEC
(NFPA 70), BOCAI, ICBO,
SBCCI, IBC and NFPA 101.
Typically Specified Sections
07270 (1988) Firestopping
07840 (1995) Firestopping
A. Typical Physical Properties (As Supplied)
Typical Performance Properties (As Cured)
Slump Resistance (ASTM D 2202): Pass
Hardness (ASTM C 66 Shore A): 45
Extrusion Rate: 25 -30 g /sec
Elongation at Break (ASTM D 412): 150%
Dry to Touch (77'F, 25 °c, 50% R.H.): 30 -60 minutes
Tensile Strength: 85 psi (0.59 MPa)
Cure Time (77 °F, 25 °C, 50% R.R): 14 -45 days
Volume Shrinkage (ASTM C 1241): 28%
(Depends on thickness)
Application Temperature Range
Recovery (ASTM C 736): Pass
Artificial Weathering (ASTM C 732): Pass
(ASTM C 1299): 40° to 122 °F (4° to 5wc)
Low Temp. Flexibility (ASTM C 734): Pass
Color: Blue and Limestone
UV and Ozone Resistance: Good
Specific Gravity: 1.50
Service Temperature Range: -201 to 180 °F ( -28° to 82 °C)
HEVISED AND JOINTS
ASTM E 84
Flame Spread Index: 0
EXPANDED DEFINITIONS
Smoke Developed Index: 0
706
Note: Contact 3M for current sales specification
B. Firestopping Properties
&FIRE BARRIERS
Meets the criteria of ASTM E 814 Standards Test Method for Fire Tests of Through- Penetration Fire Stop and
ASTM E 1966 Standard Test Method for Fire Resistive Joint Sytems. Consult current independent test
laboratories directories for listings.
C. Firestopping Code Requirements
PENETRATED
ICBO Uniform
SBCCI Standard
BOCA Basic /National Building Code
NFPA Life Safety
Building Code
Building Code
(1996 Edition)
Code 101
(1997 Edition)
(1997 Edition)
(1997 Edition)
702
104.2.4
702.0 709.7
6- 2.3.2,4
DEFINITIONS
PLANS MUST SHOW
HEVISED AND JOINTS
PENETRATIONS AND
HOW INTEGRITY iS
EXPANDED DEFINITIONS
MISC. OPENINGS
706
MAINTAINED FOR
FOR PENETRATIONS 711,0
&FIRE BARRIERS
CONSTRUCTION
ASSEMBLIES
AND JOINTS FIRE PARTITIONS
JOINTS
PENETRATED
6.2.42, EXCEPTION
708
202
703.1 711.6
CONSTRUCTION PENETRATIONS -
5 OPENINGS (EXPANSION
OR SEISMIC JOINTS) IN
WOOD FRAME
DEFINITIONS
DOCUMENTS SHALL REFERS TO 714
FLOORS
CONSTRUCTION
INDICATE DETAILS AND
FIREBLOCKING
705.3
MATERIALS FOR 711.7
APPENDIX
WOOD FRAME
PROVIDING RATINGSAT OINTS -REFER TO 709.7
J
A -6 -2.4.2
709
CONSTRUCTION
JOINTS AND
WALL & PARTITION
FIREBLOCKING
PENETRATIONS 713,0
6 -3.6.1
PENETRATION
703 1 1 FLOORICEILING AND
PENETRATIONS AND
PROTECTION
705.3.1.5
PENETRATIONS AND ROORCEILING
MISC. OPENINGS
2.2
CURTAIN WALL GAP
JOINTS SHALL NOT BE ASSEMBLIES
IN FLOORS AND
CURT
CURTAIN WALL GAP
705.4 (GENERAL)
CONCEALED FROM
713.2
SMOKE BARRIERS
PENETRATIONS OF
VIEW BEFORE
INSPECTION CURTAIN WALL GAP
NFPA #221
710
FiRE RATED
FLOORICEILING OR
ASSEMBLIES
703.2 713.4
FIRE WALLS AND
ROOF /CEILING
BUILDINGS FOR MORE PENETRATIONS -
BARRIERS
PENETRATION
705.5 (WALLS)
THAN TWO STORIES REFERS TO 714
PROTECTION
SHALL INDICATE
705.6 (FLOORS)
ALL PENETRATIONS 713.5
711.3
JOINTS- REFERSTO 709.7
SHAFT ALTERNATIVE
705.7
704.1.1
NFPA
FIRE RESISTANT
SUFFICIENT DATA 714.0
714
JOINT SYSTEMS
SHALL BE AVAILABLE PENETRATIONS - ALL
Code 70 NEC
THROUGH-
TO JUSTIFY UNTESTED REQUIREMENTS
PENETRATION
MATERIALS USED FOR (GENERAL)
National
INTERNATIONAL
FIRESTOPS F &T
RESTORATION OF FIRE
Electric Code
REQUIREMENTS
RATINGS 714.1 THROUGH 714.1.6.2
BUILDING CODE
WALL ASSEMBLIES
UBC STANDARD 7 -1
( 2003 Edition)
X070
300 21 FIRESTOPPING
EQUIVALENTTO
FIRE WALLS AND 714.2 THROUGH 714.2.6.5
ASTM E 119
PARTY WALLS FLOORICEILING AND
UBC STANDARD 7 -5
702
DEFINITIONS
707.10 ROORCEILING
ASSEMBLIES
CABO
EQUIVALENT TO
712
PENETRATIONS -
REFERS TO 714
One and Two
ASTM E 814
PENETRATIONS
714.3 THROUGH 714.3.2
Family Dwelling
7028 NONRATED
ASSEMBLIES
Code
NFPA 5000
713
JOINTS - REFERS To
709.7
(1995 Edition)
(2006 EDITION)
FIRE RESISTANT
JOINT SYSTEMS
721'0
709.0 FIREBLOCKiNG AND
602.7
8.8
FiRE SEPARATION DRAFTSTOPPING
FIRESTOPPING
PENETRATIONS
ASSEMBLIES
(FiREBLOCKNG IN OTHER
8.9
709.6
M DEL CODES)
JOINTS
PENETRATIONS -
REFER TO 714
SHEET TITLE:
FIRE STOPPING
SUBMITTAL:
REVISIONS:
SCALE:
DATE: