13-675-007System No. HIV-D -01.34 January 24, 2006 N in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following Assembly Rating- I and 2 W (See Item 2) A. Studs -Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in, (406 mm) OC. Steel studs to be min 3 -1 /2 in. ( 89 ram) wide and spaced max 24 in. (610 mm) OC. L Rating At Ambient - 4 CFM/Lin Ft p The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. L Rating At 400 F -6 CFM/I in Ft 4 sizes of nonmetallic pipes or conduits may be used: Nominal Joint Width -3/4 In. C O B. Rigid Nonmetallic Conduit-f-I - -Nom 4 in. (102 mm) diani (or smaller) Schedule 40 PVC conduit installed in accordance with Class 11 Movement Capabilities -17% Compression or Extension , (process or supply) piping systems. 1 313 A 3S U � E. Fire Retardant Polypropylene (FRPP) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. 3. Firestop System -The details of the firestop system shall be as follows: A. Fill, Void or Cavity Materials* --Wrap Strip -Nom 1/8 in. (3.2 mm) thick intumescent material supplied in 2 in. (51 mm) wide -- 0 layer is required. For nom 2 -1/2 in. and 3 in. (62 and 76 mm) diam pipes, two layers are required. For nom 3 -1/2 in. and 4 in. (89 and 102 mm) diam pipes, three layers are required. Wrap strip layers temporarily held in position using aluminum foil tape, steel wire tie, or equivalent. 3M CONIPArNY -Ultra GS -__._. - ----- - -- II 11 3A (13 mrn) long tabs to retain wrap strip layers. Coils of precut 0.016 in. (0.41 mm) thick (28 gauge) galv sheet steel available from wrap strip manufacturer. As an alternate, collar may be field- fabricated from min 0.016 in. (0.41 mm) thick (28 gauge) galv sheet steel in accordance with instruction sheet supplied by wrap strip manufacturer. Steel collar, with anchor tabs bent outward 90 deg, wrapped tightly around wrap strip layers with ruin 1 in. (25 nun) overlap at seam. Anchor tabs to be pressed tightly against wall surfaces, and collar to be compressed around wrap strip layers using a min 112 in. (13 mm) wide by 0,028 in. (0.71 mm) thick stainless steel band ZA zc � G, wall surfaces with 3/16 in. (5 mm) diam steel toggle bolts, or equivalent, in conjunction with min 1 -1/4 in. (32 nun) diam steel fender A za ,:M 5�� C_ Fill, Void or Cavity Materials* - Caulk, Sealant or Putty (Not Shown) - Min 1/2 in. (13 mm) diam bead of caulk or putty shall be 2C SECTION A -A 31NI COMPANY -CP 25WB +, IC 15WB +, FireDam 150+ caulk, FB -3000 WT sealant or MP +putty (Note: CP 25 WB +not suitable for use with CPVC pipes. CP 25WB +not suitable for use with CPVC pipes.) 1. F1oorAssembly -Min 4 -1/2 in. (114 nun) thick lightweight or normal weight (100 -150 pef or 1600 -2400 kg/m') concrete. ' 'M Anchors Strips or with 1/4 in. (6 mm) diam by nun 1 -1/2 in. (38 mm) long steel toggle bolts in conjunction with min 1 -1/4 in. (32 rani) 2. WallAssembly -The I or 2 fire rated gypsum wallboard/steel stud wall assembly shall be constructed of the materials and in the manner g 3M COMPANY - Ultra RC Pack 2.0, 3.0, 4.0 described in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include then ` This material was extracted and drawn by 3M Fire Protection Products from the 2001 edition of the UL Fire Resistance Directory. Canada closed only. c UL us following construction features: � Choose option 4 for FAX ON DEMAND A. Steel Floor And Ceiling Runners -Floor and ceiling runners of wall assembly shall consist of galy steel channels sized to Features B. Limitations accommodate steel studs (Item 213). When U- shaped deflection channel (Item 3A) is used, ceiling runner installed within the Do not apply 3MT1 FireDamT"" 150+ weather resistant and exhibits deflection channel with 1 in. (25 min) gap maintained between the top of ceiling runner and top of deflection channel. When deflection ' temperature is less than 40 "F channel is not used, ceiling runner secured to concrete floor slab with steel masonry anchors spaced a max o£24 in. (610 mm) OC. (4 °C) and in conditions when seals • Excellent adhesion Al. Light Gauge Rraming *- Slotted Ceiling Runner --As an alternate to the ceiling runner in Item 2A, slotted ceiling runner to consist of steel with slotted flanges to 213). Slotted • Compression /extension recovery spray for 12 to 18 hours, Also do galv channel sized accommodate steel studs (Item ceiling Tuner secured to not apply under the following • Re- enterable /repairable concrete floor slab with steel masonry anchors spaced max 24 in. (610 nun) OC. When slotted ceiling runner is used, deflection • Cures upon exposure to • Building materials that bleed oil, channel (Item 3A) shall not be used plasticizers or solvent (e.g., • Applied with conventional METAL -LITE INC -The System caulking equipment caulks, green or partially • Paintabie SCAFCO STEEL STUD MANUFACTURING CO, SLIPTRACK SYSTEMS INC - SLP -TRK • Wet or frost - coated surfaces A2. Light Gauge Framing* -- Clipped Ceiling Runner --As an alternate to the ceiling runner in Items 2A and 2A1, clipped runner • Areas that are continuously 703.2 713.4 to consist of galy steel channel with clips preformed in track flanges which positively engage the inside flange of the steel studs ROOF /CEILING (Item 213). Track sized to accommodate steel studs (Item 2B). Track flanges to be min. 2 -1/2 in. (64 mm). Clipped ceiling runner BARRIERS PENETRATION secured to concrete floor slab with steel masonry anchors spaced max 24 in, (6 10 mm) OC. When clipped ceiling runner is used, THAN TWO STORIES REFERS TO 714 deflection channel (Item 3A) shall not be used. SHALL INDICATE TOTAL STEEL SOLUTIONS L L C - Snap Trak 705.6 (FLOORS) A3. Light Gauge Framing* - Notched Ceiling Runner --As an alternate to the ceiling runners in Items 2A through 2A2, notched 711.3 ceiling runners to consist of C- shaped galv steel channel with notched return flanges sized to accommodate steel studs JOINTS- REFERSTO 709.7 (Item 2B). Notched ceiling runner secured to concrete floor slab with steel masonry anchors spaced max 24 in. (6 10 nun) OC. 705.7 704.1.1 When notched ceiling runner is used, deflection channel (Item 3A) shall not be used. FIRE RESISTANT DENMAR STEEL INC -Type SCR 714 JOINT SYSTEMS R Studs - Steel studs to be min 3 -5/8 in. (92 nun) wide. Studs cut 1/2 to 3/4 in. (13 to 19 mm) less in length than assembly height. Studs Code 70 NEC THROUGH- attached to ceiling runner with sheet metal screws a min of 1/2 in. (13 mm) below bottom of deflection channel, when deflection TO JUSTIFY UNTESTED REQUIREMENTS channel is used. When deflection channel is not used, steel studs shall not be secured to ceiling runner. When slotted ceiling runner MATERIALS USED FOR (GENERAL) (Item 2A 1) is used, steel studs secured to slotted ceiling runner with No. 8 by 1/2 in. (13 nun) long wafer bead steel screws at midheight INTERNATIONAL FIRESTOPS F &T of slot on each side of wall. Stud spacing not to exceed 24 in. (6 10 mm) OC. Electric Code REQUIREMENTS C. Gypsum Board* - Gypsum board sheets installed to a min total thickness of 5/8 in. (16 mm) and 1 -1/4 in. (32 nun) on each side of RATINGS 714.1 THROUGH 714.1.6.2 wall for a I or 2 fir rated assemblies, respectively, Wall to be constructed as specified in the individual Wall and Partition Design in the BUILDING CODE WALL ASSEMBLIES UL Fire Resistance Directory, except that a nom 3/4 in. (19 mnu) gap shall be maintained between the top of the gypsum board and the UBC STANDARD 7 -1 ( 2003 Edition) lower surface of the floor, The screws attaching the gypsum board to studs at the top of the wall shall be located 1 in. (25 mm) below 300 21 FIRESTOPPING EQUIVALENTTO the bottom of the U- shaped deflection channel (Item 3A) or slotted ceiling runner ner (Item 2AI). FIRE WALLS AND 714.2 THROUGH 714.2.6.5 The hourly fire rating of the joint system is dependent on the hourly fire rating of the wall. PARTY WALLS FLOORICEILING AND 3. Joint System --Max separation between bottom of floor and top of wall is 314 in. (19 mm). The joint system is designed to UBC STANDARD 7 -5 702 DEFINITIONS accommodate a max 17 percent compression or extension from its installed width. The joint system consists of a deflection charnel CABO forming material and a fill material, as follows: 712 PENETRATIONS - REFERS TO 714 A. Deflection Channel -- (Optional) -A nom 3 -3/4 in. (95 nun) wide by min 2 in. (51 mm) deep mitt 24 ga steel U- shaped channel. ASTM E 814 PENETRATIONS Deflection channel secured to concrete floor slab with steel masonry anchors or by welds spaced max 24 in. (6 10 mm) OC. The ceiling Family Dwelling runner (Item 2A) is installed within the deflection channel to maintain a I in, (25 min) gap between the top of the ceiling runner and the 7028 NONRATED ASSEMBLIES Code top of the deflection channel. The ceiling runner is not fastened to the deflection channel. NFPA 5000 713 B. Fill, Void or Cavity Material* - Caulk ---Min 5/8 in. (16 turn) thickness of fill material installed on each side of the wall between the ak (2006 EDITION) top of the gypsum board and bottom of floor, flush with cacti surface of gypsum board. 721'0 3M COMPANY -FU -150+ 709.0 FIREBLOCKiNG AND *Bcaring the UL Classification Mark 8.8 This material was extracted and drawn by 3M Fire Protection Products from the 2001 edition of the UL Fire Resistance Directory. a UI us FIRESTOPPING PENETRATIONS e I70.tt'e i01I P.iOKiUCtS - PrododSupport,hne l-, 9 32$ 1687 ASSEMBLIES (FiREBLOCKNG IN OTHER www 3m com /`firestop HEN D 0134 * 1 (hooseop ono 0! 1 option for FAX Ohl QFMAND %3 709.6 System No. vV L -2147 May 23, 2005 F Rating -1 And 2 IIr (See Item 1) T Rating --1 And 2 Hr (See Item 1) SECTION A -A 1. Wall Assembly -The 1 or 2 In: fire rated gypsum board/stud wall assembly shall be constructed of die materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs -Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in, (406 mm) OC. Steel studs to be min 3 -1 /2 in. ( 89 ram) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Design, Max diam of opening is 5 i u. (127 Turn). The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One nonmetallic pipe or conduit to be centered within opening with a nom 1/4 in, (6 mm) annular space between pipe or conduit and periphery of opening. Pipe or conduit to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe -Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. Rigid Nonmetallic Conduit-f-I - -Nom 4 in. (102 mm) diani (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70). ' C. Chlorinated Polyvinyl Chloride (CPVC) Pipe --Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for ruse in closed (process or supply) piping systems. D, Acrylonftritle Butadiene Styrene (ABS) Pipe -Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. E. Fire Retardant Polypropylene (FRPP) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. 3. Firestop System -The details of the firestop system shall be as follows: A. Fill, Void or Cavity Materials* --Wrap Strip -Nom 1/8 in. (3.2 mm) thick intumescent material supplied in 2 in. (51 mm) wide strips. Wrap strip tightly wrapped around nonmetallic pipe with continuous layers and butted tightly against both surfaces of the wall. The nun number of layers required is dependent upon the nom diam of the pipe. For nom 2 in. (51 mm) diam (and smaller) pipes, one layer is required. For nom 2 -1/2 in. and 3 in. (62 and 76 mm) diam pipes, two layers are required. For nom 3 -1/2 in. and 4 in. (89 and 102 mm) diam pipes, three layers are required. Wrap strip layers temporarily held in position using aluminum foil tape, steel wire tie, or equivalent. 3M CONIPArNY -Ultra GS B, Steel Collar --Nom 2 in. (51 nun) deep collar with 1 -1/4 iii. (32 nun) wide by 2 in. (51 mm) long anchor tabs and min 1/2 in, (13 mrn) long tabs to retain wrap strip layers. Coils of precut 0.016 in. (0.41 mm) thick (28 gauge) galv sheet steel available from wrap strip manufacturer. As an alternate, collar may be field- fabricated from min 0.016 in. (0.41 mm) thick (28 gauge) galv sheet steel in accordance with instruction sheet supplied by wrap strip manufacturer. Steel collar, with anchor tabs bent outward 90 deg, wrapped tightly around wrap strip layers with ruin 1 in. (25 nun) overlap at seam. Anchor tabs to be pressed tightly against wall surfaces, and collar to be compressed around wrap strip layers using a min 112 in. (13 mm) wide by 0,028 in. (0.71 mm) thick stainless steel band clamp at the middle of collar: As an alternate to the band clamp, collar for systems with three or more layers of wrap strip may be fastened together along the overlapping seam with three No. 6 by 3/8 in. (10 mm) long self- tapping steel screws. Collar to be secured to wall surfaces with 3/16 in. (5 mm) diam steel toggle bolts, or equivalent, in conjunction with min 1 -1/4 in. (32 nun) diam steel fender washers. Min of two, three or four anchor bolts, symmetrically located, for nom 2 in. (51 mm) diam (and smaller), nom 3 in (76 mrn) diam (and smaller) and nom 4 in, (102 mm) diam (and smaller), pipes, respectively. C_ Fill, Void or Cavity Materials* - Caulk, Sealant or Putty (Not Shown) - Min 1/2 in. (13 mm) diam bead of caulk or putty shall be applied to outer perimeter of collar at its interface with wall surface(s). 31NI COMPANY -CP 25WB +, IC 15WB +, FireDam 150+ caulk, FB -3000 WT sealant or MP +putty (Note: CP 25 WB +not suitable for use with CPVC pipes. CP 25WB +not suitable for use with CPVC pipes.) D. Firestop Device* -As an alternate to Items 3A and 3B, firestop device to be installed in accordance with the accompanying installation instructions. Firestop device to be installed and latched around pipe and secured to both sides of wall with Ultra Fast Anchors Strips or with 1/4 in. (6 mm) diam by nun 1 -1/2 in. (38 mm) long steel toggle bolts in conjunction with min 1 -1/4 in. (32 rani) diam steel fender washers. Min of two, three or four anchor straps or anchor bolts symmetrically located, for nom 2 in„ 3 in. and 4 in. (51 mm, 76 mm and 102 mm) diam pipe respectively. 3M COMPANY - Ultra RC Pack 2.0, 3.0, 4.0 ++Bearing the UL Listing Mark *Bearing the UL Classification Mark This material was extracted and drawn by 3M Fire Protection Products from the 2001 edition of the UL Fire Resistance Directory. Canada closed only. c UL us `IhCB "Y'iQtEC(IOall tic 's, Pr, "oduciSbp'pb Line 1 8{U 32$ www.3m.com /firestop W4.2 147 • 0f Choose option 4 for FAX ON DEMAND --i O C Cc� `L7 m N O Q 1/t CO O O O C/) (D tD Gi N C all J L►- A System No. AVL -319:4) December 12, 2006 F Ratings - I and 2 Hr (See Item 1) T Ratings -0 and 1/2 Hr (See Item 1) � I 3 1A _�_ 1B V SECTION A -A 1, WallAssembly --The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in tie manner described in the individual U300, U400 or V400 Series Wail and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs -Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3 -1/2 in. (89 mm) wide spaced max 24 in. (610 mm) OC, B. Gypsum Board* -The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specked in the individual Design in the UL Fire Resistance Directory. Max diam of opening is 5 in. (127 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. The hourly T Rating is 0 and 1/2 Hr for i and 2 Hr fire rated assemblies, respectively. 2. Steel Sleeve - (Optional) - Cylindrical sleeve fabricated from min 0.018 in. (0.46 mm) thick (No. 28 gauge) galv sheet steel and having a min 1 in. (25 mm) lap along the longitudinal seam. Length of sleeve to be equal to or max 2 in. (51 mm) greater than the thickness of wall. Ends of sleeve to be flush with or extend a max I in. (25 mm) beyond each surface of wall, 3. Cable -Max 4 in. (102 mm) diam cable bundle installed eccentrically or concentrically within opening. Annular space between cable bundle and periphery of opening or sleeve to be min. 0 in. (0 nun, point contact) to max 1 in. (25 mm). Cable bundle to be rigidly supported on both sides of wall. The following types and sizes of cables may be used: A. Max 200 pair No. 22 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) insulation and jacketing material. B. Max I/C No. 350 kcmil (or smaller) copper conductor cable with cross - linked polyethylene (XLPE) or PVC jacket, C. Max 71C No. 12 AWG (or smaller) copper conductor power and control cAles with XLPE or PVC insulation with XLPE or PVC jacket. D. Max 3/C No. 2/0 AWG (or smaller) copper or aluminum conductor SER cables with XLPE or PVC insulation and jacket. E. Max 4/C No. 2/0 AWG (or smaller) copper conductor, aluminum clad or steel clad TECK 90 cable with or without PVC jacketed. F Max 110/125 fiber optic (FO,) cable with PVC insulation and jacket. G. Max 31C with ground No. 8 AWG (or smaller) copper conductor NM cable with PVC insulation and jacket. H. Max RG/U coaxial cable with fluorinated ethylene insulation and jacket. I. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Ilylar jacket and insulation, J. Through Penetrating Product* --Any cables, Armored Cable+ or Metal Clad Cable-l- currently Classified under the Through Penetrating Product category. See Through Penetrating Product (XHLY) category in the Fire Resistance Directory for names of manufacturers. 4. Fill, Void or Cavity Material* - Caulk or Sealant -Min 5/8 in, (16 nun) thickness of caulk applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 nun) diam bead of caulk applied to gypsum board/cable bundle interface at point contact location on both sides ofivall. 3M COMPANY -IC 15WB +, CP 25WB-I- caulk or FB -3000 WT sealant *Bearing the UL Classification Mark This material was extracted and drawn by 3M Fire Protection Products from tlne 2006 edition of file UL Fire Resistance Directory. c UL us OEC1 t Qii. P S,:, .. . i'0C)IliCt , _... .. .. __ . _ _ _.•_ _ ,.; _ _.. Product SaPPtln Line. T $00 32F w O O O CV oz, cartridges and 4,5 gal. pail. 8. Safe Handling Information Consult Material Safety Data Sheet prior to handling and disposing of 3Mrm FireDamTM 150+ Caulk. Warranty and Limited Remedy, This product will be free from defects in materials and manufacture for a period of ninety (90) days from date of purchase, 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user's application. If this 3M product is defective within the warranty period stated above, your exclusive remedy and 3M's sole obligation shall be, at 3M's option, to replace the 3M product or refund the purchase price of the 3M product. CL 0 Limitation of Liabti{i Except where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability. Building and Commercial Services Division 3M Center, Bldg, 223 -2S -24 St. Paul, MN 55144 -1000 Phone 800 -328 -1687 Fax 888 -362 -2737 www3m.com/firestop WAYNE E. DENIMS ARCHITECT & PLANNER FLORIDA REGISTRATION No. 5561 P.O. BOX 143551 CORAL GABLES , FLORIDA 33114 TEL: (305) 661 0711 c! l 1 3.;i 3r tike q�•pfRiA� "1�,- Printed in U.S.A. Bolger 7020246 CO 3M 2006 98- 0400 - 4974 -8 Aug. 2006 liq i. Product Data SSIFj�� 5. installation Techniques 6. Maintenance O Extrusion Rate: 25 -30 g /sec • No sag formulation tP* W ��* 4s a7 Consult your 3M Authorized Fire 3MT" FireDamTM 150+ Caulk is L Protection Products stable under normal storage mDistributor /Dealer for drawings and conditions. Shelf life is 12 months Q_ system details. from date of manufacture when 8857 ASTM E 84 stored in a clean, dry area with A. 3MT"' FireDam ""' 150+ Caulk is Installation Notes: temperatures between 40'F and o • Clean surface of the opening 90 °F (4 °C and 32 °C). Avoid such as, metallic pipes, and all penetrating items to repeated freeze /thaw of 3MT`^ component acrylic latex elastomer allow proper adhesion of firestop FireDam " 150+ Caulk while still in conduits. Controls the spread of materials. • Install damming materials as packaging. flexible seal. 3M T"` FireDamTM 150+ z necessary to meet requirements % Availability penetrations through floor slabs, of appropriate system. walls and other fire -rated building �5, • Install the proper amount of 3MT" FireDamT"" 150+ Caulk is FireDamT"' 150+ Caulk, when 3MT" FireDamT"" 150+ Caulk for available from 3M Authorized Fire . -: appropriate system and rating. Protection Products Distributors after exposure to fire. • Metallic pipes and Dealers. Caulk is available in • Construction joints 3MT1" FireDam 150+ Caulk 10.1 oz., 20.0 oz. sausage, 28.0 w O O O CV oz, cartridges and 4,5 gal. pail. 8. Safe Handling Information Consult Material Safety Data Sheet prior to handling and disposing of 3Mrm FireDamTM 150+ Caulk. Warranty and Limited Remedy, This product will be free from defects in materials and manufacture for a period of ninety (90) days from date of purchase, 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user's application. If this 3M product is defective within the warranty period stated above, your exclusive remedy and 3M's sole obligation shall be, at 3M's option, to replace the 3M product or refund the purchase price of the 3M product. CL 0 Limitation of Liabti{i Except where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability. Building and Commercial Services Division 3M Center, Bldg, 223 -2S -24 St. Paul, MN 55144 -1000 Phone 800 -328 -1687 Fax 888 -362 -2737 www3m.com/firestop WAYNE E. DENIMS ARCHITECT & PLANNER FLORIDA REGISTRATION No. 5561 P.O. BOX 143551 CORAL GABLES , FLORIDA 33114 TEL: (305) 661 0711 c! l 1 3.;i 3r tike q�•pfRiA� "1�,- Printed in U.S.A. Bolger 7020246 CO 3M 2006 98- 0400 - 4974 -8 Aug. 2006 liq i. Product Data SSIFj�� Typical Performance Properties (As Cured) Slump Resistance (ASTM D 2202): Pass • Water clean -up Extrusion Rate: 25 -30 g /sec • No sag formulation tP* W ��* 4s a7 • Two colors, sky blue and Cure Time (77 °F, 25 °C, 50% R.R): 14 -45 days limestone (Depends on thickness) Application Temperature Range • Resists dirt pick -up after cure RII, aterials For Use in Through - Penetration • No priming required Firestop Systems and Joint Systems UV and Ozone Resistance: Good See UL Fire Resistance Directory 2. Applications 8857 ASTM E 84 A. 3MT"' FireDam ""' 150+ Caulk is 1. Product Description ideal for sealing construction 706 joints and through - penetrations 3M'"° FireDamT"" 150+ Caulk is a such as, metallic pipes, ready to use, gun - grade, one- conduits, power and component acrylic latex elastomer communication cables and that cures upon exposure to the conduits. Controls the spread of atmosphere to form a monolithic fire, limits the spread of noxious flexible seal. 3M T"` FireDamTM 150+ gas, smoke and water. Caulk firestops openings and Maintains the integrity of fire penetrations through floor slabs, rated construction. walls and other fire -rated building FLOORS partitions. and assemblies. 3MT" Primary firestopping applications: FireDamT"' 150+ Caulk, when • Telephone, signal and control installed properly helps control the and power cables spread of fire before, during and • Metallic conduit after exposure to fire. • Metallic pipes PROVIDING RATINGSAT OINTS -REFER TO 709.7 J • Construction joints 3MT1" FireDam 150+ Caulk CONSTRUCTION Features B. Limitations Sealant remains elastomeric, Do not apply 3MT1 FireDamT"" 150+ weather resistant and exhibits Caulk when surrounding excellent adhesion to a full range of temperature is less than 40 "F construction substrates. (4 °C) and in conditions when seals • Excellent adhesion may be exposed to rain or water • Compression /extension recovery spray for 12 to 18 hours, Also do of +/ -19% of original joint width not apply under the following • Re- enterable /repairable conditions. • Cures upon exposure to • Building materials that bleed oil, atmosphere plasticizers or solvent (e.g., • Applied with conventional impregnated wood, oil based caulking equipment caulks, green or partially • Paintabie vulcanized rubber) • Wet or frost - coated surfaces FLOORICEILING OR • Areas that are continuously 703.2 713.4 damp or immersed in water 4. Performance 3. Specifications Materials A. The fire stopping sealant is a one component, ready to use, gun grade, acrylic latex elastomer. The sealant shall be listed by independent test agencies such as UL, FM or Intertek/OPL and be tested to and pass the criteria of ASTM E 814 (UL 1479) Standard Test Method for Fire Tests of Through - Penetration Fire Stops and ASTM E 1966 (UL 2079) Standard -test Method for Fire- Resistive Joint Systems. It shall comply with the requirements of the NEC (NFPA 70), BOCAI, ICBO, SBCCI, IBC and NFPA 101. Typically Specified Sections 07270 (1988) Firestopping 07840 (1995) Firestopping A. Typical Physical Properties (As Supplied) Typical Performance Properties (As Cured) Slump Resistance (ASTM D 2202): Pass Hardness (ASTM C 66 Shore A): 45 Extrusion Rate: 25 -30 g /sec Elongation at Break (ASTM D 412): 150% Dry to Touch (77'F, 25 °c, 50% R.H.): 30 -60 minutes Tensile Strength: 85 psi (0.59 MPa) Cure Time (77 °F, 25 °C, 50% R.R): 14 -45 days Volume Shrinkage (ASTM C 1241): 28% (Depends on thickness) Application Temperature Range Recovery (ASTM C 736): Pass Artificial Weathering (ASTM C 732): Pass (ASTM C 1299): 40° to 122 °F (4° to 5wc) Low Temp. Flexibility (ASTM C 734): Pass Color: Blue and Limestone UV and Ozone Resistance: Good Specific Gravity: 1.50 Service Temperature Range: -201 to 180 °F ( -28° to 82 °C) HEVISED AND JOINTS ASTM E 84 Flame Spread Index: 0 EXPANDED DEFINITIONS Smoke Developed Index: 0 706 Note: Contact 3M for current sales specification B. Firestopping Properties &FIRE BARRIERS Meets the criteria of ASTM E 814 Standards Test Method for Fire Tests of Through- Penetration Fire Stop and ASTM E 1966 Standard Test Method for Fire Resistive Joint Sytems. Consult current independent test laboratories directories for listings. C. Firestopping Code Requirements PENETRATED ICBO Uniform SBCCI Standard BOCA Basic /National Building Code NFPA Life Safety Building Code Building Code (1996 Edition) Code 101 (1997 Edition) (1997 Edition) (1997 Edition) 702 104.2.4 702.0 709.7 6- 2.3.2,4 DEFINITIONS PLANS MUST SHOW HEVISED AND JOINTS PENETRATIONS AND HOW INTEGRITY iS EXPANDED DEFINITIONS MISC. OPENINGS 706 MAINTAINED FOR FOR PENETRATIONS 711,0 &FIRE BARRIERS CONSTRUCTION ASSEMBLIES AND JOINTS FIRE PARTITIONS JOINTS PENETRATED 6.2.42, EXCEPTION 708 202 703.1 711.6 CONSTRUCTION PENETRATIONS - 5 OPENINGS (EXPANSION OR SEISMIC JOINTS) IN WOOD FRAME DEFINITIONS DOCUMENTS SHALL REFERS TO 714 FLOORS CONSTRUCTION INDICATE DETAILS AND FIREBLOCKING 705.3 MATERIALS FOR 711.7 APPENDIX WOOD FRAME PROVIDING RATINGSAT OINTS -REFER TO 709.7 J A -6 -2.4.2 709 CONSTRUCTION JOINTS AND WALL & PARTITION FIREBLOCKING PENETRATIONS 713,0 6 -3.6.1 PENETRATION 703 1 1 FLOORICEILING AND PENETRATIONS AND PROTECTION 705.3.1.5 PENETRATIONS AND ROORCEILING MISC. OPENINGS 2.2 CURTAIN WALL GAP JOINTS SHALL NOT BE ASSEMBLIES IN FLOORS AND CURT CURTAIN WALL GAP 705.4 (GENERAL) CONCEALED FROM 713.2 SMOKE BARRIERS PENETRATIONS OF VIEW BEFORE INSPECTION CURTAIN WALL GAP NFPA #221 710 FiRE RATED FLOORICEILING OR ASSEMBLIES 703.2 713.4 FIRE WALLS AND ROOF /CEILING BUILDINGS FOR MORE PENETRATIONS - BARRIERS PENETRATION 705.5 (WALLS) THAN TWO STORIES REFERS TO 714 PROTECTION SHALL INDICATE 705.6 (FLOORS) ALL PENETRATIONS 713.5 711.3 JOINTS- REFERSTO 709.7 SHAFT ALTERNATIVE 705.7 704.1.1 NFPA FIRE RESISTANT SUFFICIENT DATA 714.0 714 JOINT SYSTEMS SHALL BE AVAILABLE PENETRATIONS - ALL Code 70 NEC THROUGH- TO JUSTIFY UNTESTED REQUIREMENTS PENETRATION MATERIALS USED FOR (GENERAL) National INTERNATIONAL FIRESTOPS F &T RESTORATION OF FIRE Electric Code REQUIREMENTS RATINGS 714.1 THROUGH 714.1.6.2 BUILDING CODE WALL ASSEMBLIES UBC STANDARD 7 -1 ( 2003 Edition) X070 300 21 FIRESTOPPING EQUIVALENTTO FIRE WALLS AND 714.2 THROUGH 714.2.6.5 ASTM E 119 PARTY WALLS FLOORICEILING AND UBC STANDARD 7 -5 702 DEFINITIONS 707.10 ROORCEILING ASSEMBLIES CABO EQUIVALENT TO 712 PENETRATIONS - REFERS TO 714 One and Two ASTM E 814 PENETRATIONS 714.3 THROUGH 714.3.2 Family Dwelling 7028 NONRATED ASSEMBLIES Code NFPA 5000 713 JOINTS - REFERS To 709.7 (1995 Edition) (2006 EDITION) FIRE RESISTANT JOINT SYSTEMS 721'0 709.0 FIREBLOCKiNG AND 602.7 8.8 FiRE SEPARATION DRAFTSTOPPING FIRESTOPPING PENETRATIONS ASSEMBLIES (FiREBLOCKNG IN OTHER 8.9 709.6 M DEL CODES) JOINTS PENETRATIONS - REFER TO 714 SHEET TITLE: FIRE STOPPING SUBMITTAL: REVISIONS: SCALE: DATE: