Loading...
11-257R-0051 =. ELECTRICAL RISER - EXISTING 3 #3/0 THW + 1 #6 GND IN 2 "C. 200A METER Q PANELA (Existing) 200 A M.C.B. 30 CKTS 22 KIAC (Existing) FROM FPL.; VERIFY GROUNDING AS TRANSFORMER PER NEC ARTICLE 250.50 NOT TO SCALE THW + 1 #6 GND IN 11(2". PANEL B 150 A NOTE; M.L.O. 30 CKTS ELECTRICAL CONTRACTOR MUST VERIFY ALL 10 KIAC EXISTING FEEDERS, REUSE IF FEASIBLE AND REPLACE IF NOT IN GOOD CONDITION OR NOT SIZED AS SPECIFIED IN DRAWINGS. GROUND LEVEL, ELECTRICAL RISER - MODIFIED NOT TO SCALE ELECTRICAL SYMBOLS LEGEND SINGLE RECEPTACLE OUTLET, 120 VOLTS, 3 -WIRE, GROUNDING TYPE, 20 AMPS. INSTALL 18 "A.F.F, UNLESS OTHERWISE NOTED. DUPLEX RECEPTACLE OUTLET, 120 VOLTS, 3 -WIRE, GROUNDING TYPE, 20 AMPS. INSTALL 1111"A.F.F. UNLESS OTHERWISE NOTED. DUPLEX RECEPTACLE OUTLET, 120 VOLTS, 3 -WIRE, GROUNDING TYPE, 20 AMPS. INSTALL 48 "A.F.F. UNLESS OTHER WISE NOTED SPECIAL RECEPTACLE OUTLET, 240 V,FEED BY NORMAL POWER PANEL, COORDINATE WITH EQUIPMENT MANUFACTURER, INSTALL AT 12" A.F.F. UNLESS OTHERWISE INDICATED TELEPHONE CONDUIT STUB UP 4 TV /CABLE OUTLET - INSTALL 75" A.F.F. OR AS NOTED SINGLE POLE LIGHT SWITCH, 120 VOLTS, 20 AMPS. INSTALL 48 "A.F.F. THREE WAY LIGHT SWITCH, 120 VOLTS, 20 AMPS, INSTALL 48 "A.F.F, SINGLE POLE LIGHT SWITCH, 120 VOLTS, 20 AMPS. W/ DIMMER. INSTALL 48 "A,F•F• �'--� -1 POWER PANEL WITH REQUIRED CLEARANCE L J 360 ELECTRICAL DISCONNECT SWITCH 3- NUMBER OF POLES, 60- FRAME SIZE, 40 - FUSE SIZE BRANCH CIRCUIT HOMERUN TO PANEL BOARD A-I NUMBER INDICATE CIRCUIT DESIGNATION GFI GROUND FAULT INTERRUPTER VP VAPOR PROOF WP WEATHER PROOF SD SMOKE DETECTOR SD DUCT SMOKE DETECTOR GD COMBO (SMOKE & CARBON MONOXIDE) DETECTOR WALL MOUNTED THERMOSTAT LIGHTING SYMBOLS LEGEND ELECTRICAL GENERAL NOTES 1. THE PROJECT IS THE RENOVATION OF AN EXISTING FACILITY. THE CONTRACTOR SHALL VISIT THE JOB SITE TO DETERMINE THE EXTENT OF WORK INVOLVED WITH THESE DOCUMENTS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND ALLOW FOR ANY CHANGES THAT MAY BE MADE DURING THE COMPLETION OF THE JOB. ANY ELECTRICAL WORK THAT MAY HAVE TO BE DONE TO COMPLETE ANY ALTERATIONS SHOWN ON ANY PLAN SHALL BE INCLUDED IN THIS CONTRACT WITH NO ADDITIONAL CHARGES TO THE OWNER AFTER THE CONTRACTS ARE LET. 2. THE WORK INCLUDED CONSISTS OF ALL SUPERVISION, LABOR, MATERIALS EQUIPMENT AND INSTALLATION REQUIRED THE COMPLETE SATISFACTORY AND APPROVED ELECTRICAL SYSTEM AS INDICATED ON THE DRAWINGS OR AS MAY BE REASONABLY IMPLIED BY EITHER. 3. ALL WORK TO BE PERFORMED AND ALL IMPLEMENTATION ASPECTS OF THE REQUIREMENTS OF THESE DRAWINGS SHALL RE IN FULL COMPLIANCE WITH THE LATEST NEC EDITION, LOCAL CODES AND ORDINANCES, AND THE RULES AND REGULATIONS OF THE LOCAL UTILITY COMPANY. 4. CONTRACTOR SHALL REVIEW AND UNDERSTAND THE CONTENT OF THESE DRAWINGS, VISIT THE SITE AND THOROUGHLY REVIEW EXISTING CONDITIONS PRIOR TO BID. NO ALLOWANCE WILL BE MADE FOR ANY EXISTING CONDITION THE CONTRACTOR DID NOT BECOME AWARE OF OR UNDERSTOOD. 5. THE ELECTRICAL CONTRACTOR SHALL INSURE THAT ALL DRAWING(S) REQUIREMENTS ARE MET AND NO CHANGES ARE MADE WITHOUT THE PREVIOUS APPROVAL OF THE ARCHITECT OR ELECTRICAL ENGINEER OF RECORD; AND THE PROPER APPLICABLE AUTHORITIES. G. CONTRACTOR SHALL PAY FOR PERMITS, FEES, INSPECTIONS AND TESTING. CONTRACTOR TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINING WORK OR ORDERING EQUIPMENT. 7. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES AS WELL AS PROVIDING TEMPORARY POWER AND LIGHTING AT PROJECT SITE FOR ALL TRADES. THE OWNER SHALL BE RESPONSIBLE FOR ALL FEES NECESSARY TO BRING UTILITY POWER TO PROJECT SITE. 8. ELECTRICAL DRAWINGS ARE NOT TO SCALE. THE CONTRACTOR SHALL REFER TO ARCHITECTURAL, CEILING GRID AND OTHER DRAWINGS FOR EXACT LOCATION OF EQUIPMENT, FIXTURES, OUTLETS, SWITCHES AND OTHER ELECTRICAL COMPONENTS AND CONFIRM WITH ARCHITECT PRIOR TO START WORK. ANY POTENTIAL CONFLICT WITH OTHER EQUIPMENT, COMPONENT, OR STRUCTURAL MEMBER MUST BE REFERRED TO THE ARCHITECT PRIOR TO START IMPLEMENTING THIS WORK. 9. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COMPONENTS, INCLUDING REQUIRED CONNECTORS, FITTINGS, LUGS, CONTRACTORS AND OTHER HARDWARE REQUIRED TO MAKE THE SYSTEM OPERATIONAL. THIS ALSO INCLUDES THE COORDINATION OF RECEPTACLES TO EQUIPMENT PLUGS AND CONNECTORS. 10. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE APPLICABLE. 11. ALL NEW EQUIPMENT INSTALLED IN THIS PROJECT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDED INSTALLATION INSTRUCTIONS. 12. CONTRACTOR TO ASSURE THAT PROPER CLEARANCE (AS PER MANUF. RECOMMENDATIONS) IS PROVIDED AROUND ALL NEW EQUIPMENT FOR SERVICING AND REPLACEMENT PURPOSES. 13. CONTRACTOR SHALL VERIFY ALL EQUIPMENT VOLTAGES AND LOADS PRIOR TO ANY WIRING OR INSTALLATION. 14, LABEL ALL EQUIPMENT (DISCONNECT SWITCHES, CIRCUIT BREAKERS, CONTROLS ETC.) WITH ENGRAVED LAMINATED PLASTIC. 15. ALL CIRCUITS SHALL BE CLEARLY IDENTIFIED AND SHOWN ON PANEL DIRECTORIES. CONTRACTOR SHALL IDENTIFY ALL CIRCUITS, FEEDERS, JUNCTION BOXES AND OUTLETS AND PROVIDE A TYPE WRITTEN DIRECTORY IN EACH PANEL BOARD. 16. ALL CONDUCTORS SHALL BE COPPER WITH THW/THWN INSULATION FOR SIZE #10 AND SMALLER. CONDUCTORS LARGER THAN #10 SHALL HAVE THW/THWN INSULATION, ALL CONDUCTORS #10 AND SMALLER MAY BE SOLID. ALL CONDUCTORS #8 AND LARGER CWA11 RC CTD1RIr1Cr%TVDC •Yy+ r .� • • • 17. ALL SECTIONS OF METALLIC CONDUIT SYSTEM SHALL BE GROUNDED AND •`• ELECTRICALLY CONTINUOUS. •Y•Y 18. USE ELECTRICAL METALLIC TUBING ( EMT) FOR INTERIOR CONCEALED WIRING. •. Y` OUTDOOR UNDERGROUND CONDUITS SHALL BE IN PVC SCHEDULE -40., UNDER PAVED AREAS IT SHALL BE ENCASED IN CONCRETE, MINIMUM COVER SHALL BE 18 ". OUTDOOR ABOVE GROUND CONDUITS SHALL BE RIGID. INTERIOR EXPOSED OR CONCEALED CONDUIT SHALL BE EMT. COMPRESSION TYPE FITTINGS FOR CONDUIT 2 1/2" AND SMALLER STEEL SET -SCREW FITTINGS FOR CONDUIT 3" AND LARGER. 19. ALL WIRING INSTALLATION SHALL BE MADE AS REQUIRED BY NEC ART. 300. 20. ALL ITEMS REMOVED SHALL BECAME PROPERTY OF THE OWNER AND SHALL BE DISPOSED OF AS PER THE OWNER'S INSTRUCTIONS, UNLESS INDICATED OTHERWISE. ALL ITEMS WHICH ARE NOT TO BE STORED ON SITE BY OWNER SHALL BE REMOVED FROM THE BUILDING IMMEDIATELY, AT CONTRACTORS EXPENSE, 21. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS. CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS, 22. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MAKE QUICK -BREAK ENCLOSURES AS REQUIRED BY EXPOSURE. 23. ALL LIGHTING FIXTURES MUST COMPLY WITH NEC ARTICLE 410.73 (G). 24. ELECTRICAL CONTRACTOR MUST USE EXISTING PANELS, WIRING, OUTLETS, RECEPTACLES, FIXTURES AND SWITCHES WHEN FEASABLE. 25. PROVIDE ALL REQUIRED CONNECTIONS FOR OTHER TRADES, AND FOR EQUIPMENT PROVIDED BY THE OWNER. 26. ALL ELECTRICAL WIRING FOR THE HVAC SYSTEM INCLUDING WIRING THRU LINE VOLTAGE CONTROL DEVICES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. 27. ELECTRICAL CONTRACTOR IS TO COORDINATE WITH MECHANICAL AND PLUMBING CONTRACTORS FOR THE INSTALLATION OF ANY EQUIPMENT TO BE SUPPLIED BY THEM, BY THE OWNER OR THE OWNER'S SUBCONTRACTOR OR SUPPLIER AND TO BE CONNECTED BY UNDER THIS CONTRACT BEFORE ANY WIRING IS TO BE MADE. IN THE EVENT THE ELECTRICAL CONTRACTOR PROCEEDS WITHOUT THIS COORDINATION HE /SHE AT HIS EXPENSE SHALL REPLACE ANY NON - CONFORMING WIRING OR DEVICES. ANY CHANGES FROM THIS REQUIREMENT SHALL BE APPROVED BY THE ARCHITECT AND ELECTRICAL ENGINEER OF RECORD. 28. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER AND COMMUNICATIONS COMPANIES, AND SHALL BE FULLY COORDINATED WITH THEM PRIOR TO COMMENCEMENT OF WORK. 29. ALL MOUNTING HARDWARE SHALL BE BY ELECTRICAL CONTRACTOR. 30. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS REQUIRED BY THE LATEST EDITION OF THE N.E.C. OR LOCAL CODES. 31. THE ELECTRICAL CONTRACTOR SHALL INSURE THAT WORK IS PERFORMED BY PROPERLY CERTIFIED AND LICENSE PERSONNEL; OR UNDER IMMEDIATE DIRECT SUPERVISION, IF APPLICABLE. 32. THE ELECTRICAL CONTRACTOR WILL MAINTAIN AT THE JOB SITE, IN GOOD CONDITION, ONE SET OF UP -TO -DATE ELECTRICAL DRAWINGS. 31 ONCE CONSTRUCTION IS COMPLETED, AS -BUILT DRAWINGS SHALL BE PROVIDED TO THE ARCHITECT DULY SIGNED BY THE ELECTRICAL CONTRACTOR. 34. THE ELECTRICAL INSTALLATION SHALL MEET THE WRITTEN APPROVAL OF THE OWNER'S REPRESENTATIVES BEFORE ACCEPTANCE. 35, ALL WORK SHALL BE GUARANTEED FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. • . • J • • J • Y J r r•r�� • r a •r•c v Revisions co d' No. Date Description r co ti 1; .97 -1� -11 ; OWNER'S REVISION ti 3;'• 07 -2' 01 ;. OWNER'S REVISION LO �C} HL LO qjr U) t a • Q Or V) U) a)u Mc O �0 um i U ��� ° dzCso MU. L1.1 *= to c u E Z taZ �t°N U Cn x IY y LU a q "0 W W O N W CL u i je V V' a C_ t� U Q -0 i r0 co d' so O. GOMEZ Checked By r co UJI M ti LO �C} Z LO qjr U) t a 4) b Q Or V) U) a)u Mc O �0 um J U ��� ° dzCso MU. L1.1 *= to c u E Z taZ �t°N U Cn x IY y LU a q "0 W W O N W CL u je V V' a C_ t� U Q -0 z Z p G 3 00 0r- - w 0a-(LN0 -a r0 co d' so O. GOMEZ Checked By r co UJI M C J LL F.. •,t , cj CZ O N Q Or V) N ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE THE i ORIGINAL AND UNPUBLISHED WORK OF Toms Design Group, AND MAY NOT ME DUPLICATED, USED, OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF Toms Design Group Inc. TO THE BEST OF MY KNOWLEDGE THE PLANS AND APPLICABLE SPECIFICATIONS COMPLY WITH THE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE - SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 6833 FLORIDA STATUTES. CHAPTER 1 105.13,4.4 OF (FLORIDA BUILDING CODE 2007) L Q O ..j Cn III W H Z in W 'J Im Lu Z 10 G? Cl)n / Z WO CO ONOWN Cr. J � J F- U V W j W L TOMA DESIGN GROUP INC. Tel: (305) 466 -4077 Fax: (305) 4668 -4077 20900 NE 30th Ave. R 514 Avntura, FL, 33180 Date co d' Drawn by O. GOMEZ Checked By r co Scale INDICATED M C J LL O CIO CZ O N Q Or 2 N -�� Q N cc O *= E V, Cn x W 00 W O W O O O L L Q O ..j Cn III W H Z in W 'J Im Lu Z 10 G? Cl)n / Z WO CO ONOWN Cr. J � J F- U V W j W L TOMA DESIGN GROUP INC. Tel: (305) 466 -4077 Fax: (305) 4668 -4077 20900 NE 30th Ave. R 514 Avntura, FL, 33180 Date 10.08.2010 Drawn by O. GOMEZ Checked By P. ARIAS Scale INDICATED Sheet NO E -4 CAD ID: 10- 040- E -4.DWG