11-257-022IN ■r, E V t GENERAL PLUMBING NOTES 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE INSTALLATION OF A COMPLETE PLUMBING SYSTEM IN ACCORDANCE WITH THESE DRAWINGS, THE APPLICABLE EDITION OF THE FLORIDA BUILDING CODE (2007 AND APPROVED SUPPLEMENTS), ALL OTHER APPLICABLE STATE, COUNTY AND LOCAL CODES AND ORDINANCES. IF WORK AS LAID OUT, INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES, BUILDING CODES AND /OR REGULATIONS, THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECT /ENGINEER BEFORE SUBMITTING A BID, THE ARCHITECTIENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED. 2. CONTRACTOR SHALL VISIT THE SITE AND REVIEW ALL PERTINENT UTILITY DRAWINGS TO FAMILIARIZE HIMSELF WITH THE LOCATION OF ALL EXISTING AND /OR PROPOSED UTILITY STUB OUTS, PIPING, EQUIPMENT, ETC,, AND MAKE DUE ALLOWANCES FOR ANY CONDITION AFFECTING HIS WORK. 3. THE WORD PROVIDE MEANS "FURNISH AND INSTALL ". 4. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT FEES, INSPECTIONS AND ALL OTHER COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK, UPON FINAL ACCEPTANCE, A CERTIFICATE FROM THE LOCAL INSPECTION AUTHORITY SHALL BE FURNISHED TO THE OWNER. PLUMBING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS OF HIS WORK BY REGULATORY AUTHORITIES. 5. REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 6. ALL MATERIALS AND EQUIPMENTS SHALL BE NEW, OF U.S. MANUFACTURER AND OF GOOD QUALITY OF RESPECTIVE KIND AND GRADE, AND MUST BE FURNISHED SO AS TO PREVENT ANY DELAY IN THE PROGRESS OF THE WORK. 7. ALL WORK THROUGHOUT SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. ALL EXCAVATION AND BACKFILL AS REQUIRED SHALL BE A PART OF THIS CONTRACT. S. THE LOCATION OF ALL ITEMS SHOWN ON THE DRAWINGS ARE NOT DEFINITELY FIXED BY DIMENSIONS AND APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BE DETERMINED BY THE CONTRACTOR AT THE PROJECT SITE IN RESPONSE TO FIELD CONDITIONS. EXACT LOCATION OF TIE -INS TO EXISTING BUILDING SYSTEMS MUST BE FIELD VERIFIED. 9, PLUMBING CONTRACTOR MUST COORDINATE ALL WORK WITH THOSE OF OTHER TRADES. 10. CONTRACTOR SHALL VERIFY IN THE FIELD ALL INVERT AND GRADE ELEVATIONS AND MAKE ANY NECESSARY ADJUSTMENT AS REQUIRED BY THE FIELD CONDITIONS, AND REQUIRED TO OBTAIN THE PROPER SLOPE, 11, MATERIALS: A. ALL SANITARY, WASTE AND RAIN LEADERS UNDERGROUND OR IN SLAB BELOW BUILDINGS SHALL BE PVC DWV SCH 40 ASTM D 2665, B. ALL ABOVE GROUND SANITARY, WASTE, VENT B RAIN LEADERS SHALL BE CAST IRON OR PVC DWV SCH 40 (ASTM D -565) WHERE ALLOWED BY CODE. PVC MAY NOT BE USED THRU RATED ASSEMBLIES OR IN PLENUMS. C. ALL UNDERGROUND WATER PIPING SHALL BE COPPER TYPE "K" . ALL ABOVE GROUND WATER PIPING SHALL BE COPPER TYPE *V. WHERE DOMESTIC WATER TEMPERATURES CAN CAUSE SWEATING, ALL COLD WATER PIPING SHALL BE INSULATED WITH ARMAFLEX INSULATION, THICKNESS AS PER F.B.C. 2007 CHAPTER 13 TABLE 411.1 D. ALL HOT WATER, PRESSURE AND TEMPERATURE RELIEF PIPING SHALL BE COPPER TYPE "K ". E. HOT WATER PIPING INSULATION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE - PLUMBING SECTION 607 (TABLE 607.1). INSULATION TO BE ARMAFLEX OR SIMILAR APPROVED WHERE APPLICABLE, F. ALL AIR CONDITIONING CONDENSATE DRAIN PIPING SHALL BE SCH 40 PVC, EXCEPT WHEN INSTALLED IN AIR PLENUMS WHERE COPPER TYPE "DWV" OR EQUIVALENT MUST BE USED. INSULATE CONDENSATE PIPING WITH 314" ARMAFLEX. PROVIDE TRAP WITH CLEAN OUT AND UNIONS FOR CONDENSATE PIPING. SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION OF PIPING. 12. ALL PLUMBING PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE - PLUMBING SECTION 301 (TABLE 308,5), 13. ISOLATE ALL COPPER PIPE FROM HANGERS OR SUPPORTS WITH ISOLATOR PADS OR MATERIAL, 14. ALL PLUMBING FIXTURES SHALL BE PROVIDED WITH ALL NECESSARY ACCESSORIES SUCH AS STOP VALVES, ?"TRAPS, SUPPORTS, P i T VALVES, ETC., AS REQUIRED. ALL EXPOSED PIPING AT FIXTURES AND EQUIPMENT SHALL BE CHROME PLATED BRASS PIPE OR TUBE. 15, PROVIDE SHUT -OFF VALVES AND UNIONS TO ALL FIXTURES, ETC„ REQUIRING WATER SUPPLY, 16. PROVIDE DIELECTRIC COUPLINGS AS REQUIRED, INCLUDING ALL DISSIMILAR METALS IN PIPING AND EQUIPMENT CONNECTIONS. 17. PROVIDE WATER- HAMMER ARRESTORS TO ALL PLUMBING FIXTURES AS REQUIRED. SIZE AND INSTALL AS PER MANUFACTURER'S RECOMMENDATIONS, 18. PLUMBING CONTRACTOR MUST COORDINATE WITH EQUIPMENT SUPPLIER FOR EXACT LOCATION OF ROUGHING -IN. 19. PROVIDE CLEANOUTS (WITH CHROME PLATED WALL OR FLOOR ACCESS FRAMES AND COVERS AS REQUIRED) AT THE BASE OF ALL WASTE AND /OR VENT STACKS, PROVIDE PITCH PANS i LEAD FLASHING FOR ALL SANITARY SYSTEM VENTS. 20. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES. ACCESS PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING AND MUST MATCH THE FINISH OF THE WALL IN WHICH THEY ARE INSTALLED. 21. ALL FIXTURES SUPPLIES AND STOPS SHALL BE CHROME PLATED (C.P,) 22. ALL EXPOSED FIXTURE "P- TRAPS" SHALL BE MINIMUM 17 GAL. i CHROME PLATED CAST BRASS OR 316 STAINLESS STEEL. 23. ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALUFLOOR SLEEVES WITH FIRE RATED FOAM, TO ACHIEVE THE SAME RATING AS WALLS OR FLOORS AS PART OF THE PLUMBER'S WORK, 24. PROVIDE LABELING ON ALL MAJOR EQUIPMENT, VALVES PIPING, ETC. A REPRODUCIBLE DIAGRAM WITH LOCATION OF ALL VALVES AND EQUIPMENT SHALL BE PROVIDED FOR OWNER/OPERATOR. 25. ALL POTABLE WATER USE FIXTURES SHALL COMPLY WITH "NO- LEAD" REQUIREMENTS, 26. THE MAXIMUM WATER CONSUMPTION FLOW RATES AND QUANTITIES FOR ALL PLUMBING FIXTURES AND FIXTURE FITTINGS SHALL BE IN ACCORDANCE WITH TABLE P604.4, FBC (PLUMBING) AND I OR LOCAL CODES AND ORDINANCES, 27. WATER PIPING SYSTEM UPON COMPLETION SHALL BE DISINFECTED AS PER FIG 602.3,4 AND 610.1 (PLUMBING). 28. PLUMBING CONTRACTOR SHALL NOT INSTALL ANY PIPING DIRECTLY ABOVE AN ELECTRICAL PANEL AS REQUIRED BY N.E.C. 25, CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED UNDER THE CONTRACT TO BE FREE FROM DEFECTIVE WORKMANSHIP, AND MATERIALS, USUAL WEAR EXPECTED, AND SHOULD ANY SUCH DEFECTS DEVELOP WITHIN A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE BUILDING BY THE OWNER, CONTRACTOR SHALL REPAIR AND /OR REPLACE ANY DEFECTIVE ITEMS AND ALL DAMAGE RESULTING FROM FAILURE OF THESE ITEMS, AT NO EXPENSE WHATSOEVER TO THE OWNER. 34. CONTRACTOR SHALL FURNISH THE OWNER WITH 3 COPIES OF ALL OPERATING MANUALS AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT INSTALLED. 35. CONTRACTOR SHALL MAINTAIN A SET OF REPRODUCIBLE SEPIA DRAWINGS SHOWING AS BUILT CONDITIONS AS THEY OCCUR. A COMPLETE SET OF "ELECTRONIC" AS -BUILT REPRODUCIBLE DRAWINGS SHALL BE SUBMITTED BY THE CONTRACTOR TO THE OWNERIARCHITECT PRIOR TO FINAL ACCEPTANCE OF INSTALLATION. THESE DRAWINGS SHALL HAVE ALL INSTALLATIONS REFERENCED BY DIMENSIONS TO A SET REFERENCED POINT OR POINTS. PLUMBING FIXTURE CONNECTION SCHEDULE PLUMBING FIXTURES AND FIXTURE FITTINGS (AS PER TABLE 2903.2a - FOC RESIDENTIAL) TRAP WATER CONN. FU 1/8 LAVATORY, PRIVATE TAG DESCRIPTION SIZE COUNT REMARKS SLOPE 1.28 GALLONS PER FLUSHING CYCLE - EXISTING SANITARY LINE - - - --- •-- -- - NEW VENT LINE - - -- - - - COLD HOT COLD WATER HW HOT WATER WC WATER CLOSET 3" 1/2" N/A 3 SPECIFIED BY OWNER 3" & 4" @ 1 /B" / FT. L LAVATORY 1 -1/4" 1/2" 1/2" 1 SPECIFIED BY OWNER @ 1/4" / FT. SK SINK 1 -1/2" 1/2" 1/2" 2 SPECIFIED BY OWNER @ 114" / FT. T TUB 2" 1/2" 1/2" 2 W / PRESSURE AND TEMP. TYPE ANTI - @ 1/4" / FT SCALDING VALVES SET TO MAX. 110' F SH SHOWER 2" 1/2" 1/2" 2 W / PRESSURE AND TEMP. TYPE ANTI - @ 1/4" / FT. SCALDING VALVES SET TO MAX. 110' F MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING FIXTURES AND FIXTURE FITTINGS (AS PER TABLE 2903.2a - FOC RESIDENTIAL) PLUMBING FIXTURE MAXIMUM FLOW RATE OR FIXTURE FITTING 1/8 LAVATORY, PRIVATE 1,5 GPM AT 60 PSI SHOWER HEAD 1.5 GPM AT 20 PSI SINK FAUCET 1.5 GPM AT 60 PSI WATER CLOSET 1.28 GALLONS PER FLUSHING CYCLE SLOPE OF HORIZONTAL DRAINAGE PIPE SIZE (INCHES) MINIMUM SLOPE (INCH PER FOOT) 2 1/2 OR LESS 1/4 3TO6 1/8 NOTE: 1. TABLE 704.1 OF THE FLORIDA PLUMBING CODE 2007. LEGENDS - NEW COLD WATER LINE - NEW HOT WATER LINE -- CONNECTIONS EXISTING COLD WATER LINE - 652 - A EXISTING HOT WATER LINE - - Z NEW SANITARY LINE W Z u. 6 Cq - - - - - - - EXISTING SANITARY LINE - - - --- •-- -- - NEW VENT LINE - - -- - - - - EXISTING VENT LINE CW COLD WATER HW HOT WATER FU FIXTURE UNITS SAN SANITARY VTR VENT THRU ROOF CO CLEAN OUT FCO FLOOR CLEAN OUT WATER HAMMER ARRESTER SPECS. P.D.I. UNITS F.U. RATING MODEL No. MANUFACTURER CONNECTIONS A 1 - 11 652 - A SIOUX CHIEF 112" NOTE: 1. SIOUX CHIEF WATER HAMMER ARRESTORS ARE APPROVED FOR INSTALLATION WITHOUT ACCESS DOOR REQUIRED, CONFORMS TO ANSI/ASSE 1010 STANDARDS. Gw 31'1„ iv o� \ 31"1 r) 314 h1 4, C 30112'' AV v 11T \ \ l�„ � CW R�Rp 11z q1� � \ f� �E) X112 „ „o 5� > E)112 (E) �0 d 11� 314h CW Cw 112G vi1 (E) WATER PIPING ISOMETRIC • owe** • • . . w . • • • w • • • u • +ur • •••U •goo •r• •Yi4• • • f r • • • w •••U • • r • r • • • • • • auto • u•••• • ••u r rru• • "� ��( 3/4h 14. 31 Qv S � G 11� 112' � 1 /2"CW � VV/ '0 i VV 1121 G CV1 (E)11 11, F ER �I NI NEW WH -1: if ELECTRIC TANKLESS WATER HEATER 112 3�4° TEMPRA STIEBEL- ELTRON MODEL No. TEMPRA VV/ G� 20, 240 VOLTS, 19.2 KW, EF= 0.98 %, 1 0 0 V� V� G �P, 31"1 N. 1h � CW F klgT i WgTR (IN 0 «� �v �hA A Sk sk 1 C 1ST - -2•" 0 SA_N - . _ ... - - � � Fl. 2" 0 SAN 4 FU 2 FU �- -0 CONCRETE SPLASH BLOCK DETAIL T NOT TO SCALE 11I�J��� � --A FA SANITARY ISOMETRIC NOT TO SCALE NOT TO SCALE Zh _1 1ST Revisions No, Date Description U M } N r, o Z L0 Scale INDICATED LO so C14 0) 0 �cchoc� C Z W W Z u. 6 Cq z < z C� -so �I' viLU s �,vr � W ° O a c a rn V zit ° o 48 1 � - 2 V Z Z -5 E o ..-- W fe N O 0 C (nD - aNda ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF Tome Design Gnu', AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF Tome Design Gnu' Inc. TO THE BEST OF MY KNOWLEDGE THE PLANS AND APPLICABLE SPECIFICATIONS COMPLY WITH THE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE- SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND $33 FLORIDA STATUTES. CHAPTER 1 105.13.4.4 OF (FLORIDA BUILDING CODE 2007) M M ;`T • �.; r'„ err, -,, t Checked By T M Scale INDICATED Uj C0 C J LL O z� �I' .CZ s �,vr � •' ^' 14f�T F W .© taC Lss O= ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF Tome Design Gnu', AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF Tome Design Gnu' Inc. TO THE BEST OF MY KNOWLEDGE THE PLANS AND APPLICABLE SPECIFICATIONS COMPLY WITH THE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE- SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND $33 FLORIDA STATUTES. CHAPTER 1 105.13.4.4 OF (FLORIDA BUILDING CODE 2007) V U) W Issss O Z ed Cn W W Z Cn 0 Z m (L U) _0 FE I- W 2 ti Pssss H U Iw TOMA DESIGN GROUP INC. Tel: (305) 464 -4077 Fax: (305) 466 -4077 20900 NE 30th Ave. k 514 Avntura, FL, 33180 Date M Drawn by M. VELASOUEZ Checked By T M Scale INDICATED C0 C J LL O z� O .CZ O N N N N s = .© taC Lss O= .� cc O < C\1 Co O Cn O W p O 0 LO V U) W Issss O Z ed Cn W W Z Cn 0 Z m (L U) _0 FE I- W 2 ti Pssss H U Iw TOMA DESIGN GROUP INC. Tel: (305) 464 -4077 Fax: (305) 466 -4077 20900 NE 30th Ave. k 514 Avntura, FL, 33180 Date 10 -02 -2010 Drawn by M. VELASOUEZ Checked By P. MORALES Scale INDICATED Sheet N" P-2 CAD ID: 10- 040- P -2.DWG i i