11-257-015GENERAL NOES. 1, SCOPE OF WORK, A. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIALS, LABOR, PERMIT FEES AND INSPECTIONS FOR A COMPLETE HVAC INSTALLATION IN ACCORDANCE TO THESE DIAGRAMATICAL DRAWINGS. B. MATERIAL AND WORKMANSHIP SHALL BE IN ACCORDANCE TO THE LATEST EDITION OF THE FLORIDA BUILDING CODE (2007 AND APPROVED SUPPLEMENTS), NFPA, AND ALL LOCAL CODES AND ORDINANCES. C. CONTRACTOR SHALL BASE HIS BID AFTER FAMILIARIZING HIMSELF WITH ALL EXISTING ASBUILT CONDITIONS. D. CONTRACTOR SHALL OBTAIN APPROVAL OF SHOP DRAWINGS, SUBMITTALS OF MATERIAL AND EQUIPMENT TO SUBSTITUTE BASIS OF DESIGN EQUIPMENTAND MATERIALS NOTED ON THESE DRAWINGS TEN DAYS PRIOR TO BID DATE. AFTER THIS DATE NO SUBSTITUTIONS SHALL BE ADMITTED. 2. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC, THEY DO NOT SHOW EVERY BEND, OFF -SET, ELBOW OR OTHER FITTINGS WHICH MAY BE REQUIRED FOR THE INSTALLATION IN THE SPACE ALLOCATED, OR FOR COORDINATION WITH OTHER TRADES, 3. CONTRACTOR SHALL VERIFY ALL EQUIPMENT, DUCTWORK, DIFFUSERS AND GRILLES TO WORK AND FIT PROPERLY WITH SPACE AVAILABLE ANDALL OTHER TRADES, AND ASSURE THAT THESE ITEMS DO NOT CONFLICT WITH ELECTRICAL FIXTURE LOCATIONS. 4. ANY APPARATUS, APPLIANCE, MATERIAL, WORK OR INCIDENTAL ACCESORIES OR MINOR DETAILS NOT SHOWN BUT NECESSARY TO MAKE THE WORK COMPLETE AND PERFECT IN ALL RESPECTS AND READY FOR OPERATION, EVEN IF NOT PARTICULARLY SPECIFIED SHALL BE PROVIDED BY THE CONTRACTOR. 5. ALL MATERIAL SHALL FIT THE SPACE AVAILABLE, VERIFY DIMENSIONS AND CLEARANCES AT BUILDING BEFORE COMMENCING WORK. 6. DRAWINGS ARE NOT TO BE SCALED. UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE ARCHITECTURAL AND /OR STRUCTURAL DRAWINGS, AND SITE CONDITIONS SHALL GOVERN EXACT LOCATION OF MECHANICAL EQUIPMENT AND APPURTENANCES, 7. VERIFY EXACT ROUTING OF DUCTWORK AND CONDENSATE DRAINS WITH STRUCTURAL ELEMENTS. LOCATION AND SIZE OF ALL SLEEVES THROUGH STRUCTURAL ELEMENTS SHALL BE SUBMITTED TO ARCHITECT FOR APPROVAL PRIOR TO EXECUTION. 8. CONTRACTOR SHALL TEST AND BALANCE ALL THE HVAC SYSTEMS, AND ADJUST ALL CONTROLS AND EQUIPMENT FOR PROPER OPERATION, TEST 8 BALANCE SHALL BE DONE IN ACCORDANCE WITH SECTION 13410,AB,4 OF THE FLORIDA BUILDING CODE. S. COORDINATE EXACT LOCATION OF ALL SUPPLY i RETURN AIR CEILING DEVICES WITH ARCHITECTURAL CEILING GRID 8 LIGHT FIXTURE LOCATIONS, 10. EQUIPMENT SHALL HAVE CAPACITIES REQUIRED TO OBTAIN A SUITABLE OPERATING BALANCE BETWEEN ASSOCIATED ITEMS OF EQUIPMENT. ALL DAMPER 8 CONTROLS SHALL BE ADJUSTED TO OBTAIN THE REQUIRED CAPACITIES UNDER ACTUAL OPERATING CONDITIONS OF EACH SYSTEM AS INSTALLED, OPERATING POWER REQUIREMENTS FOR EACH ITEM OF EQUIPMENT SHALL NOT EXCEED THE RATED MOTOR HORSEPOWER. 11, CONSTRUCT DUCTWORK FROM ONE AND ONE HALF INCH FIBERGLASS DUCTIOARD (R =111.5) FOR ALL INDOOR AIR CONDITIONED SUPPLY AND RETURN DUCTWORK. SHEET METAL DUCTS SHALL BE USED FOR EXHAUST, AND NON - CONDITIONED OUTSIDE AIR INTAKE. FABRICATE, SEAL AND INSTALL PER LATEST SMACNA MANUAL RECOMMENDATIONS. FLEXIBLE DUCTWORK SHALL BE THERMAFLEX MODEL M -KC, UL 181 CLASS 1 AIR DUCT OR SIMILAR. SIZES NOTED ARE CLEAR INSIDE DIMENSIONS, CONTRACTOR MUST ADJUST DIMENSIONS FOR DUCTS WITH INTERNAL INSULATION, 12. PROVIDE AIR VOLUME EXTRACTORS, SPUTTER DAMPERS OR ADJUSTABLE TURNING VANES AT ALL BRANCH TAKE -OFFS AS REQUIRED FOR PROPER AIR BALANCING, EVEN IF NOT INDICATED ON THE DRAWINGS. 13. COOLING SYSTEMS ARE DESIGNED FOR 75'F DO INSIDE CONDITIONS WITH OUTSIDE TEMPERATURE OF 91'F DI, 77'F Will. HEATING IS DESIGNED TO MAINTAIN MINIMUM INSIDE TEMPERATURES OF 72'F DO WITH AN OUTSIDE TEMPERATURE OF 4VF DR. 14. THERMOSTAT SHALL HAVE A MAXIMUM HEATING MODE TEMPERATURE SETTING OF 78'F AND A MINIMUM COOLING MODE TEMPERATURE SETTING OF 70'F. IT SHALL BE ADJUSTABLE TO PROVIDE A TEMPERATURE RANGE OF UP TO 10'F BETWEEN FULL HEATING AND FULL COOLING. HEATING AND COOLING TO BE NON- CONCURRENT. THERMOSTAT TO HAVE REQUIRED STAGES OF COOLING AND HEATING FOR COMPATIBILITY WITH AIR CONDITIONING EQUIPMENT PROVIDED. ALL THERMOSTATS SHALL BE OF THE PROGRAMMABLE TYPE, 15. CONTRACTOR MUST COORDINATE WITH OWNERIARCHITECT FINAL LOCATION OF PROGRAMMABLE THERMOSTAT (DISPLAY), 16, AIR DISTRIBUTION DEVICES SHALL BE CONSTRUCTED OF ALUMINUM, AS MANUFACTURED BY NAILOR, OR SIMILAR, ALL WITH OPPOSED BLADE DAMPER WHERE APPLICABLE AND TR TRANSITION WHERE INDICATED, COORDINATE COLOR WITH ARCHITECT. 17. THE WORD "PROVIDE" MEANS TO SUPPLY AND INSTALL. 18. AIR COOLED CONDENSING UNITS TO BE AS SCHEDULED. PROVIDE EACH UNIT WITH ANTI- CYCLING DEVICE, HIGH AND LOW PRESSURE CONTROLLERS, AND FILTER DRYER. 18. EXACT LOCATION OF MECHANICAL EQUIPMENT SHALL BE COORDINATED WITH ELECTRICAL EQUIPMENT INCLUDING, BUT NOT LIMITED TO, POWER AND SYSTEMS PANELS TO MANTAIN N.E.C. CLEARANCES AS REQUIRED BY NEC. 20. COORDINATE ALL WORK WITH OTHER TRADES INVOLVED. THIS INCLUDES WALL AND ROOF PENETRATIONS, REQUIRED ELECTRICAL SERVICE AND CONTROL WIRING. PLUMBER IS TO PROVIDE A MINIMUM 11/4 INCH CONDENSATE TRAP SEAL, AT EACH UNIT. 21. CONDENSATE PIPING MUST HAVE A MINIMUM PITCH OF 114" PER FOOT AS PER FLORIDA PLUMBING CODE. IF NECESSARY CONTRACTOR MUST INSTALL CONDESATE PUMP TO GUARANTEE PROPER CONDESATE DISPOSAL. 22. ALL AIR CONDITIONING CONDENSATE DRAIN PIPING SHALL BE SCH 40 PVC, EXCEPT WHEN INSTALLED IN AIR PLENUMS WHERE COPPER TYPE "DWV" OR EQUIVALENT MUST BE USED, INSULATE CONDENSATE PIPING WITH 3/4" ARMAFLEX. PROVIDE TRAP WITH CLEAN OUT AND UNIONS FOR CONDENSATE PIPING. 23. FLAME AND SMOKE RATING: ALL INSULATION PRODUCTS AND MATERIALS USED FOR THIS PROJECT SHALL HAVE A MAXIMUM FLAME SPREAD AND SMOKE DEVELOPED RATING OF 25/50 RESPECTIVELY IN ACCORDANCE WITH TESTS OUTLINED IN NFPA 255. 24. ALL EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATORS AND INSTALLED AS RECOMMENDED BY EQUIPMENT MANUFACTURER. 25. INSTALL FLEX CONNECTIONS BETWEEN UNITS AND DUCTWORK TO ISOLATE UNIT VIBRATION FROM BEING TRANSMITTED TO THE DUCT OR STRUCTURE. 26, CONTRACTOR SHALL PROVIDE ADEQUATE ACCESS TO ALL EQUIPMENT, DAMPERS, ETC. FOR FUTURE SERVICE, AS PER FLORIDA MECHANICAL CODE AND MANUFACTURER'S RECOMMENDATIONS AND REQUIREMENTS. 27. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING AND VENTILATING EQUIPMENT BEFORE STARTING THEM. THESE FILTERS MUST ALSO BE REPLACED PRIOR TO FINAL ACCEPTANCE BY OWNER, 28. EXACT LOCATION OF TIE -INS TO EXISTING SYSTEM MUST BE FIELD VERIFIED AT THE FIELD, 29, VERIFY ALL VOLTAGES WITH ELECTRICAL CONTRACTOR BEFORE ORDERING ANY EQUIPMENT, 30. ALL DUCT AND PIPE PENETRATIONS OF EXISTING FIRE RATED PARTITIONS SHALL BE SEALED WITH APPROVED FIRE RATED SEALANT TO MAINTAIN THE INTEGRITY OF THE SYSTEM. 31, CONTRACTOR SHALL FURNISH THE OWNER WITH ALL OPERATING MANUALS AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT INSTALLED. MANUALS SHALL RE BOUNDED IN THREE RING LOOSE LEAVE BINDERS AND INDEX BY PRODUCT TYPE. ALSO A SECTION WITHIN THE MANUAL SHALL BE INDEX WITH NAME, TELEPHONE NUMBER AND ADDRESS OF ALL LOCAL SUPPLIERS OF ALL MATERIAL AND EQUIPMENT INSTALLED TOGETHER WITH NAME, TELEPHONE AND ADDRESS OF ALL CONTRACTORS OF THE PROJECT. 32. CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED UNDER THE CONTRACT TO BE FREE FROM DEFECTIVE WORKMANSHIP, AND MATERIALS, USUAL WEAR EXPECTED, AND SHOULD ANY SUCH DEFECTS DEVELOP WITHIN A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE BUILDING BY THE OWNER, CONTRACTOR SHALL REPAIR AND /OR REPLACE ANY DEFECTIVE ITEMS AND ALL DAMAGE RESULTING FROM FAILURE OF THESE ITEMS, AT NO EXPENSE WHATSOEVER TO THE OWNER. COMPRESSOR SHALL CARRY 5 YEAR FACTORY WARRANTY, 33. CONTRACTOR SHALL PROVIDE 3 SETS OF SHOP DRAWINGS, SUBMITTALS FOR ALL MATERIAL AND EQUIPMENT TO BE USED IN THIS PROJECT FOR APPROVAL BY ARCHITECT /ENGINEER. 34. CONTRACTOR SHALL MAINTAIN A SET OF REPRODUCIBLE SEPIA DRAWINGS SHOWING AS BUILT CONDITIONS AS THEY OCCUR. COMPLETE SET OF ELECTRONIC AS -BUILT REPRODUCIBLE DRAWINGS SHALL BE SUBMITTED BY THE CONTRACTOR TO THE OWNER/ARCHITECT PRIOR TO FINAL ACCEPTANCE OF INSTALLATION. THESE DRAWINGS SHALL HAVE ALL INSTALLATIONS REFERENCED NY DIMENSIONS TO A SET REFERENCED POINT OR POINTS. SUPPLY DUCT 1" GALV STRAP - ANGLE UNDER DUCT SPIN IN COLLAR W/ DAMPER WRAP TOPS OF CEILING DIFFUSER FIN. CLG. 1 -1/2" GALV, STRAP W /INSULATION SADDLE UNDER DUCT (TYP.) FLEX, UL 181 DUCT PANDUIT STRAP CEILING DIFFUSER DUCT CONNECTIONS TO CEILING DIFFUSERS NOT TO SCALE A/C SPLIT SYSTEM SCHEDULE DESCRIPTION UNITS AHU -2 AHU-3 AREA SERVED - -- BEDROOMS & LIVING MASTER BEDROOM MANUFACTURER -- -- TRANE TRANE AIR HANDLING UNIT MODEL No. - - -- 4TEE3F39A1000A 4TEE3F3151000A CONDENSING UNIT MODEL No. - - -- 4TTR3042A1000A 4TTR3018A1000A COMBINED RATINGS SENSIBLE COOLING CAPACITY - BTU /HR. 35,200 12,400 TOTAL COOLING CAPACITY BTU /HR. 38,500 14,200 TOTAL HEATING CAPACITY BTU /HR. 14,500 7,000 REFRIGERANT TYPE -- R-410A R-410A ENERGY EFFICIENCY EER/SEER 14.00 SEER 14.00 SEER AIR HANDLING UNIT - AHU DISCHARGE TYPE - - -- VERTICAL VERTICAL TOTAL SUPPLY AIRFLOW CFM 1,500 700 OUTDOOR AIR CFM 50 40 EVAP. ENT. AIR CONDITIONS DB / WB ' F 77.6/64.5 771/65.111 EST. EXTERNAL STATIC PRESSURE IN. W.G. 0.40 0.35 AHU FAN MOTOR HP 1/2 1/2 ELECTRICAL CHARACTERISTICS V / Ph 240 V / 10 240 V / 10 ELECTRICAL HEATER SIZE KW 4.80 4.80 MIN. CIRCUIT AMPACITY (AHU INC. HEATER) AMPS 30.0 30.0 MAX. CIRCUIT PROTECTOR (AHU INC. HEATER) AMPS 30.0 30.0 APROX. UNIT WEIGHT LOS. 150.0 120.0 APROX. UNIT DIMENSIONS (W X H x D) INCHES 23.5" X 57.9" x 21" 21.5" x 43" x 21" CONDENSING UNIT - CU AMBIENT AIR TEMPERATURE 'F 95.0 95.0 ELECTRICAL CHARACTERISTICS V / Ph 240 V / 10 240 V / 10 COMPRESSOR - RLA AMPS 18.6 6.4 FAN MOTOR - FLA AMPS 1.3 0.7 MINIMUM CIRCUIT AMPACITY (CU) AMPS 25.0 9.0 MAXIMUM CIRCUIT PROTECTOR (CU) AMPS 40.0 15.0 APROX, UNIT WEIGHT LOS. 225.0 195.0 APROX. UNIT DIMENSIONS (W x H x D) INCHES 38" x 34" x 35" 33" x 33" x 30" ACCESORIES LIQUID LINE SIZE (AS PER MFGR.RECOM.) IN. O.D. 3 /8" 5/16" SUCTION LINE SIZE (AS PER MFGR. RECOM.) IN. O.D. 3/4" 314" EXTERNAL FILTER RACK YES/NO YES YES FILTER TYPE - - -- 1" THROWAWAY 1" THROWAWAY PROGRAMMABLE THERMOSTAT YES/NO COOL/HEAT COOL/HEAT NOTES: 1. LINE SIZES INDICATED ARE FORBIDDING PURPOSES ONLY AND HAVE BEEN ESTIMATED FOR A MAX. EQUIV. LENGTH OF 50 FEET. THE ACTUAL LINE SIZES SHALL BE ESTABLISHED BY THE CONTRACTOR IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND IN RESPONSE TO FINAL FIELD CONDITIONS, SUCTION LINE LOSS NOT TO EXCEED TWO DEGREES IF WITH MAINTAINING MINIMUM VELOCITY REQUIRED FOR ALL RETURNS. MAXIMUM SAG 112" PER FOOT OF SUPPORT SPACING F -0" MAXIMUM - .1 ----- ,- _.- -..._ -_...� - - FLEX DUCT NOTES: METAL STRAP 1.1/2" MINIMUM 1. DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING. 2. SUPPORT SYSTEM MUST NOT DAMAGE DUCT OR CAUSE OUT -OF -ROUND SHARE. FLEX DUCT SUPPORT DETAIL NOT TO SCALE SUPPLY / RETURN AIR DIFFUSER SCHEDULE TAG NECK SIZE PATTERN MANUFACTURER SERIES DESCRIPTION A C" x 4" 1 - WAY NAILOR 51 C-0 6" x 4"- CURVED SLADE CEILING SUPPLY REGISTER WITH VOLUME DAMPER S 6" x G" 1 -WAY NAILOR 51 C-0 6" x 6% CURVED SLADE CEILING SUPPLY REGISTER WITH VOLUME DAMPER C i" X G" 1 -WAY NAILOR 51 C-0 =" X 6"- CURVED BLADE CEILING SUPPLY REGISTER WITH VOLUME DAMPER D 10" x 6" 2-WAY NAILOR 51 C -O 10" x 6" - CURVED BLADE CEILING SUPPLY REGISTER WITH VOLUME DAMPER E 14" X 8" 1 -WAY NAILOR 51C -0 14" X 8"- CURVED BLADE CEILING SUPPLY REGISTER WITH VOLUME DAMPER Private Dwelling 3 4.0 15.00 60.0 1,689.5 1 8" x 8" -- -- NAILOR 5145H i" x 8" - TRANSFER GRILLE WITHOUT VOLUME DAMPER 2 12" x 12" - - -- NAILOR 5145H 12" x 12" - TRANSFER GRILLE WITHOUT VOLUME DAMPER NOTES: 1. ALL SUPPLY DIFFUSERS, GRILLES AND REGISTERS MUST BE PROVIDED WITH A VOLUME BALANCING DAMPER. BALANCING DAMPER SHALL BE OF THE OPPOSED BLADE WHERE APPLICABLE, 2. FINISH TO BE SELECTED BY ARCHITECT, 3. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF AIR DISTRIBUTION DEVICES. 4. CONTRACTOR MUST VERIFY MOUNTING SYSTEM (FRAME STYLE), WITH ARCHITECT, FOR ALL DIFFUSERS, GRILLES AND REGISTERS BEFORE ORDERING. OUTSIDE AIR (Florida Mechanical Cade - Section 403.3) AIR VE PITCH DOWN TOWARD DRAIN AHU CONDENSATE DRAIN DETAIL NOT TO SCALE CEILIr WALL DRA NEOPRENE ANGLE IR SUPPOR1 DIAGONA FLOI • Y • , • • a , , , • u OCCUPANCY NUMBER OF OCCUPANCY O.A. 1 O.A. 1 AREA HEIGHT VOLUME AIR O.A. 2 FINAL OA FINAL OA SYSTEM TAG • DESCRIPTION CATEGORY BEDROOMS LOAD CFM/Pers. Roq'�I Ft.2 Ft. Ft-3 CHANGES Re4 Req'd Supplied Z Tabl• 403.3 ELBOW People - - - - CFM 2.0 BATHROOM 50 PER HOUR CFM CFM CFM GAMARRA RESIDENCE Private Dwelling 3 4.0 15.00 60.0 1,689.5 8.4 14,023.8 0.35 81.8 85.0 50.0 AHU -2 50.0 AHU -3 40.0 AIR VE PITCH DOWN TOWARD DRAIN AHU CONDENSATE DRAIN DETAIL NOT TO SCALE CEILIr WALL DRA NEOPRENE ANGLE IR SUPPOR1 DIAGONA FLOI • Y • , • • a , , , • u A/C LEGEND FAN SCHEDULE FAN No. QTY. SERVICE CFM EST. SP MOTOR V / PH / Hz DRIVE AN TYPE DESIGN BASED ON MODEL No. ACCESORIES NOTES •+•r •••r• ••+ FIRE STOPPING DUCTWORK " • • y • r . • • , , FLEXIBLE DUCTWORK IN. WG. His / WATTS z c° Z '_ WITH TURNING VANES Z MANUFACTURER ELBOW a - - - - EF -1 2.0 BATHROOM 50 0.15" 38 WATTS 115/1/60 DIRECT CENTRIFUGAL GREENHECK SP -1350 A, B, C 1, 2, 3, 4 EF -2 1.0 MASTER BATH. 120 0.15" 53 WATTS 115/1/60 DIRECT I CENTRIFUGAL GREENHECK SP -A125 A, B, C 1, 2, 3, 4 ACCESORIES: CONDENSING UNIT NOTES: A- IACKDRAFT DAMPER F- SPEED CONTROL EXHAUST FAN 1, VERIFY ELECTRICAL CHARACTERISTICS BEFORE ORDERING ANY EQUIPMENT. B HANGING KIT G - TRANSFORMER 2. ALL ACCESORIES MUST BE PROVIDED BY MECHANICAL CONTRACTOR. C - VIBRATION ISOLATORS H - HUMIDITY SENSOR 3. FAN MUST INTERLOCK WITH LIGHT SWITCH. D - GALV, ROOF CURB I - TEMPERATURE CONTROL 4. ALL FANS MUST BE INSTALLED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, E - DISCONNECT SWITCH AIR VE PITCH DOWN TOWARD DRAIN AHU CONDENSATE DRAIN DETAIL NOT TO SCALE CEILIr WALL DRA NEOPRENE ANGLE IR SUPPOR1 DIAGONA FLOI • Y • , • • a , , , • u Y Y Y HVAC REQUIREMENT SCHEDULE: A/C LEGEND NO DUCT SMOKE DETECTOR „• 1 - r • Y , • • • FIRE DAMPER(S) .. X s o DESIGNATION FOR DIFFUSER9_ETTE±? AND`CFM (D THERMOSTAT X FIRE RATED ROOF /FLOOR CEILING ASSEMBLY •+•r •••r• ••+ FIRE STOPPING DUCTWORK " • • y • r . • • , , FLEXIBLE DUCTWORK u r SMOKE CONTROL z c° Z '_ WITH TURNING VANES Z < Z �FLN U ELBOW a - - - - EXISTING LU UC U-1 _+_11- UNDERCUT DOOR Z r� VD VOLUME DAMPER Z ® SUPPLY CEILING DIFFUSER LIJ o= fnO..rLNGL0- RETURN / TRANSFER AIR GRILLE C15 �- CONNECT NEW TO EXISTING AHU AIR HANDLING UNIT CD CONDENSATE DRAIN CU CONDENSING UNIT LO EF EXHAUST FAN Y Y Y HVAC REQUIREMENT SCHEDULE: YES NO DUCT SMOKE DETECTOR 04 X FIRE DAMPER(S) .. X SMOKE DAMPER(S) cn o X FIRE RATED ENCLOSURE � c*�M X FIRE RATED ROOF /FLOOR CEILING ASSEMBLY -©" �- t., 22 cxs X FIRE STOPPING cZMCn emu_ X SMOKE CONTROL z c° Z '_ X NOTES IT IS THE INTENT OF THESE PLANS TO PROVIDE A COMPLETE OPERATING SYSTEM, A/C CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED EQUIPMENTS, MATERIALS, ETC., EXCEPT WHERE SPECIFICALLY NOTED AS BEING FURNISHED BY OTHERS. SHOULD THERE BE ANY QUESTIONS CONCERNING RESPONSIBILITY, THEY SHALL BE SETTLED BEFORE BID SUBMISSION AND CONTRACT SIGNING,- NO EXTRA CHARGES WILL BE ALLOWED. 1" UNDERCUT ALL NEW INTERIOR DOORS UNLESS OTHERWISE NOTED STRUCTURE OF FLOOR ABOVE SUPPLY AIR DUCT WALL FAN SECTION REFRIGERANT PIPES FROM COND, UNIT COIL SECTION FILTER PROVIDE 4' MIN. CLEARANCE AROUND AIR HANDLING UNIT 1.112" DEEP EMERGENCY DRAIN PAN AS PER FMC SECTION 30723 AIR HANDLING UNIT MOUNTING DETAIL NOT TO SCALE ;TWORK 'EKED ELBOW WITH __LBLEWALL TURNING VANES ✓kFRAME MITTERED ELBOW NOT TO SCALE BI MI� WI- I 00 C0 4 go + 04 . Z z < .. . C0 cn o � c*�M O +=' Cz O -©" �- t., 22 cxs EO U cZMCn emu_ L,I-I z c° Z '_ N Z3 Z < Z �FLN U C: .� a C' W �p W LU R v V O. 0 C '0 U-1 N C a. tC1 Z c o_� o�< -) o z" Z mica E5 LIJ o= fnO..rLNGL0- 00 C0 Drawn by go + 2,1 a t INDICATED . C0 C J LL O +=' Cz EO > (1) �;> N Z3 d E) C: .� (1) O CO "• Z _� /cc V 05 a) 0 L11 O ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF Toms Design Group, AND MAY NOT BE DUPLICATED, USED, OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF Tome Design Group Inc. TO THE BEST OF MY KNOWLEDGE THE PLANS AND APPLICABLE SPECIFICATIONS COMPLY WITH THE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE - SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTES. CHAPTER 1 105.13.4.4 OF (FLORIDA BUILDING CODE 2007) Cn •.j a W W I-ee Z Wk W W Cn V J _V Z C� F- 1 TOMA DESIGN GROUP INC. Td: (305) 466 -4077 Fax: (305) 466.4077 20900 NE 30th Ave. # 514 Aventura, FL, 33190 Date C0 Drawn by 0. GOMEZ Chocked By r Scale INDICATED C0 C J LL O +=' Cz EO > (1) C: N Z3 d E) C: .� (1) O CO cp _� /cc V 05 a) 0 L11 O O C15 �- 0 0 LO Cn •.j a W W I-ee Z Wk W W Cn V J _V Z C� F- 1 TOMA DESIGN GROUP INC. Td: (305) 466 -4077 Fax: (305) 466.4077 20900 NE 30th Ave. # 514 Aventura, FL, 33190 Date 10 -08 -2010 Drawn by 0. GOMEZ Chocked By P. MORALES Scale INDICATED Sheet No M -2 ', CAD ID: 10- 040- M- 2.DWta