11-468-005ELECTRICAL SPECIFICATIONS
1. GUARANTEES AND RESPONSIBILITY: ALL MATERIAL AND WORKMANSHIP
FOR ONE YEAR FROM DATE OF ACCEPTANCE. ALL DEFECTS
SHALL BE CORRECTED WITHOUT CHARGE, INCLUDING ALL PATCHING
AND PAINTING AND OTHER INCIDENTAL REPAIRS OR REPLACEMENT.
2. WORKMANSHIP: ALL WORK SHALL BE INSTALLED IN A NEAT,
ORDERLY MANNER. DEVICES, PLATES, EXPOSED RACEWAYS,
ENCLOSURES, COVERS, FIXTURES, ETC. SHALL BE ALIGNED
PERPENDICULAR TO OR PARALLEL WITH, THE PRINCIPAL
STRUCTURAL MEMBERS. THE EDGE OF THESE COVERS, PLATES
ENCLOSURES, ETC., SHALL BE IN VERTICAL OR HORIZONTAL PLANE
AS APPLICABLE FOR THE ITEMS INVOLVED. EXPOSED RACEWAYS
SHALL BE OFFSET WHERE THEY ENTER SURFACE - MOUNTED
EQUIPMENT. WIRING INSTALLED IN PANELS AND OTHER ENCLOSURES
SHALL BE NEATLY LOOPED AND LACED & NOT WADDED OR BUNDLED.
3. MATERIAL STANDARDS: ALL MATERIALS SHALL BE NEW & CONFORM
TO THE APPLICABLE STANDARDS WHERE SUCH HAVE BEEN
ESTABLISHED FOR THE MATERIALS IN QUESTION. THE
PUBLICATIONS AND STANDARDS OF THE ORGANIZATIONS BELOW
ARE APPLICABLE TO THE MATERIALS SPECIFIED HEREIN.
A. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
B. UNDERWRITER'S LABORATORIES, INC. (UL)
C. AMERICAN STANDARDS ASSOCIATION (ASA)
D. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA)
E. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
WHERE REFERENCE IS MADE TO TRADE NAMES OR NAMES OF
MANUFACTURERS, SUCH REFERENCES ARE MADE SOLELY TO
DESIGNATE AND TO IDENTIFY THE QUALITY OF THE MATERIALS OR
EQUIPMENT TO BE FURNISHED, AND DOES NOT PRECLUDE THE USE
OF "EQUAL" EQUIPMENT AS APPROVED BY THIS ENGINEER.
4. REFERENCE STANDARDS: INSTALLATION SHALL COMPLY WITH THE
REGULATIONS OF THE FOLLOWING:
A. NATIONAL ELECTRICAL CODE (NFPA), LATEST EDITION
B. SOUTH FLORIDA BUILDING CODE, LATEST EDITION
5. DO NOT SCALE ELECTRICAL DRAWINGS. REFER TO PLANS AND
ELEVATIONS FOR EXACT LOCATION OF ALL EQUIPMENT. CONFIRM
WITH OWNER'S REPRESENTATIVE.
6. THE MINIMUM WIRE SIZE SHALL BE #12 AWG, UNLESS OTHERWISE
NOTED. ALL CONDUCTORS SHALL BE COPPER WITH TW INSULATION
FOR SIZE #8 AND SMALLER. CONDUCTORS LARGER THAN #8 SHALL
HAVE TYPE THE INSULATION, UNLESS OTHERWISE NOTED. ALL
CONDUCTORS #10 AND SMALLER MAY BE SOLID AND ALL THOSE #8
AND LARGER SHALL BE STRANDED.
7. ALL RACEWAYS AND PIPES PLACED IN OR THRU A CONCRETE SLAB
SHALL BE SPACED A MINIMUM OF 3 DIAMETERS OF THE LARGEST
GROUNDING
CKT
SERVES
ELECTRODE
WIRE
CON
DUIT
CONDUCTOR
PHASE
A C
CKT
SERVES
BOLTED -TYPE
WIRE
oUT
0 CONNECTION DEVICE
—� `— T OR
RANGE
0 OR EXOTHERMIC WELD.
B OCIM LIGHT
GROUNDING
O
O NONMETALLIC
•
ELECTRODE
PROTECTIVE
(v�
30/2
SLEEVE.
3/4
5000
3
1
CO
+`
SWITCH LEG
cM
e a d
•
•
" • CONCRETE FOUNDATION, d
COPPER CONDUCTOR OR STEEL
SMOKE DET
, •
•
°
REINFORCING ARGOR ROD NOT
CONNECTIOt
d °°
�°
LESS THAN VINCH DIAMETER.
NOTES:
, • ° d
20 N.
9 d
° ° •'
�;
1.- ALL SMOKE DETECTORS MUST H/
MIN. d
.d°
d
a
INTERCONNECTED,
DISHWASHER
20/1
2.- ALL SMOKE DETECTORS TO BE F
20 FT
DIRECT CONTACT
CIRCUITS, AHEAD OF ALL SWITCHES,
MIN.
WITH EARTH.
3.- ALL BEDROOM RECEPTACLES OUT
1 1/2
800
ARC FAULT INTERRUPTER C.B.
ENCASED GROUNDING
8
ELECTRODE
DETAIL
#12
1/2
SCALE: N.T.S.
9
WEATHERHEAD
CONDUIT OR PIPE OF ANY OTHER SERVICE. NEW FPL SERVICE CONNECTION ELECTRICAL
CONTRACTOR MUST CONTACT FPL FOR SCHEDULE
8. ALL RACEWAYS SHALL BE CARLON PY -DUIT, TYPE A, U.L. LISTED OR CONNECTION & REQUIREMENT INCLUDE IN BID ALL
EQUAL. CONDUIT FITTINGS AND CEMENT SHALL BE PRODUCED BY NECESSARY WORK.
THE SAME MANUFACTURER.
A. RUNS IN CONCRETE IN CONTACT WITH EARTH,
UNDERGROUND,EXPOSED OR IN INTERIOR WALLS OR FEEDERS
1 1/4" OR LARGER, SHALL BE RIGID STEEL OR PVC
B. METALLIC ELECTRICAL CONDUIT MAY BE USED IN THE
INTERIOR PARTITIONS AND CEILINGS.
9. OUTLET BOXES SHALL BE POLYVINYL CHLORIDE AND SHALL
CONFORM TO THE N.E.M.A. STANDARDS.
10. THE DISCONNECT SWITCHES SHALL BE HORSEPOWER -RATED HEAVY
DUTY, QUICK- MAKE/QUICK -BREAK IN N.E.M.A: 1 INTERIORA EXTERIOR.
11. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR
DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO
FURNISH & INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL
SYSTEM AND PROVIDE ALL REQUIREMENTS FOR THE EQUIPMENT
TO BE PLACED IN A PROPER WORKING ORDER. SHOULD ANY ITEMS
BE MISSING, HE SHALL NOTIFY THE ARCHITECT /ENGINEER BEFORE
COMMENCING WORK. NO ADDITIONAL PAYMENT WILL BE MADE FOR
THE CONTRACTOR'S FAILURE TO NOTIFY THE ARCHITECT /ENGINEER.
ELECTRICAL NOTES:
1. OUTSIDE RECEPTACLES, RECEPTACLES AT BATH, GARAGE AND
KITCHEN COUNTER, SHALL BE G.F.I.
2. ELECTRICAL METER AND PANEL LOCATION MAY VARY AS PER
SERVICE ENTRANCE LOCATION.
3. ELECTRICAL CONTRACTOR TO COORDINATE SERVICE WITH F.P.L.
4. ALL "J" BOXES SHALL COMPLY WITH N.E.C. 314
5. ELECTRICAL OUTLETS (RECEPTACLES AND LIGHTING) BELOW BASE
FLOOD ELEVATION SHALL BE INSTALLED AT THE HIGHEST PERMITTED
ELEVATION AND SHALL BE INSTALLED ON (SEPARATE) INDEPENDENT
CIRCUITS FROM THOSE IN THE HABITAT AREAS.
6. NO APPLIANCES OR APPLIANCE OUTLETS SHALL BE INSTALLED
BELOW BASE FLOOD ELEVATION.
7. IT IS SUGGESTED THAT YOU CONFER WITH FLORIDA POWER AND
LIGHT TO LOCATE THE ELECTRICAL METER TO COMPLY WITH FEDERAL
EMERGENCY MANAGEMENT AGENCY REQUIREMENTS.
2SETS(2) #2/0
FROM FPL
EXISITNG FPL
METER TO BE
REPLACED
TABLE 250.66.SERVICE IN
(2) #210. GROUNDING11 /0
1# 1/0 THWN -314" (GND)
O
22,000 AIC
2 "�— (3) #3/0 THWN
(3) #3/0 THWN I
NEMA 311
2 I
225 -)
TWO 5/8 "x10' GROUNDING RODS SPACED 6' BOND TO
A 3/4" COPPER WATER PIPE STUB -OUT AT METER
LOCATION & ENCASED GROUND SEE DETAIL.
PANEL
A
200A
ELECTRIC RISER DIAGRAM
SCALE: N.T.S.
BUS RATING: 225A
TYPE: SIEMENS,GE,SD OR EQUIV. , , MAINS: ML
SERVICE: 10,3W PANEL A POLES: 50 MINIMUM
VOLTAGE: 120/240 FEEDER: #3/0
AIC:10,000 NEUTRAL: #3/0
CKT
SERVES
TRIP
POLE
WIRE
CON
DUIT
VA
PHASE
A C
CKT
SERVES
POLE
WIRE
oUT
VA
1
RANGE
50/2
#6
1
12000
•
CEILING MOUNTED SMOKE DETECTOR
2
DRYER
30/2
#10
3/4
5000
3
1
CO
0
W N
0 C\l
cM
I
Z
•
4
u-
Z
Vi
-a
5
WASHER
20/1
#12
1 1/2
1200
•
6
DISHWASHER
20/1
#12
1/21
1200
7
DISPOSAL
20/1
#12
1 1/2
800
•
8
SMALL APPLIANCES GFI
20/1
#12
1/2
1800
9
SMALL APPLIANCES
20/1
#12
1/2
1800
•
1110
GEN. LIGHTING. & RECEPT.
20/1
#12
1/2
1800
11
GEN. LIGHTING. & RECEPT.
20/1
#12
1/2
1800
•
12
GEN. LIGHTING. & RECEPT.
20/1
#12
1/2
1800
13
GEN. LIGHTING. & RECEPT.
20/1
#12
1/2
1800
114
GEN. LIGHTING. & RECEPT.
20/1
#12
1/2
1800
15
GEN. LIGHTING. & RECEPT.
20/1
#12
1 1/21
1800
•
116
GEN. LIGHTING. & RECEPT.
20/1
#12
1/2
1800
17
GEN. LIGHTING. & RECEPT.
20/1
#12
1/2
1800
118
EXTERIOR RECEPT. GFI
20/1
#12
1/2
1200
19
WATER HEATER
30/2
#10
3/4
4500
•
120
A/C UNIT
60/2
#6
1
11600
21
1
122
23
POOL PUMP
30/2
#10
3/4
1100
•
24
CONDEN. UNIT
50/2
#6
1 1
10800
25
1
1
1
•
26
27
SPRINKLER PUMP
30/2
#10
3/4
2200
•
28
SPACE
29
•
30
31
SPACE
• 1132
33
1134
35
• 1136
37
138
39
•
40
41
•
42
ELECTRICAL LEGEND
SYMBOL
DESCRIPTION
®
CEILING MOUNTED LIGHT
®-
DUPLEX RECEPTACLE
NEW CIRCUIT
RECEPTACLE GROUND FAULT INTERRUPTER
O
EXISTING ELECTRICAL PANEL
PB= PUSH BUTTON
WALL SWITCH (SINGLE, DOUBLE)
$3
WALL SWITCH (3 -WAY)
®
220 VOLT RECEPTACLE
C3
DISCONNECT SWITCH
in
EXHAUST FAN
®
CEILING MOUNTED SMOKE DETECTOR
"
WALL MOUNTED LIGHT
IE]
WALL MOUNTED LIGHT - WHEATER PROOF
sD
SMOKE DETECTOR W/ BATTERY BACKUP
ABBREVIATIONS'
U-)
R.=
EXISTING TO BE RELOCATED
GFI= GROUND FAULT INTERRUPTER
N =
NEW CIRCUIT
VH= VERIFY PRIOR TO INSTALLATION
UC=
UNDER CABINET
PB= PUSH BUTTON
C.=
COUNTER TOP LEVEL
VP= VAPOR PROOF
BC.=
BELOW COUNTER
WP= WEATHER PROOF
000
EL= EXTERIOR LIGHT
1/4" BIRD SCRE
RUST RESISTANT
FLASHING
1/2" SHEET
METAL SCREW
(4 TYPICAL)
4"0 SHEET METAL EXHAUST
DUCT. SEE FLOOR PLAN
FOR SIZE
GAUGE: 24
05 ELLMMET FANS BATH ROOM ROOF CAP DETAIL. (TYPA
ELECTRICAL PLAN
SCALE: 1/4"=l'-O"
THE SCOPE WORK INCLUDE IN
THE LAUNDRY AREA GENERAL
REPARATIONS DUE FIRE:
TRUSSES
ROOF
DRYWALL AT WALLS AND CEILING
INTERIOR PARTITIONS
FLOOR TILES
PAINT
ELECTRICAL CKTS AND DEVICES
MECHANICAL INSTALLATIONS
PLUMBING INSTALLATIONS
15 & 20 AMPS RECEPTACLES
IN COMPLIANCE WITH NEC 2008
EDITION ITEMS 210.12 & 406.11
TO BE COMBINATED TYPE:ARC FAULT
INTERRUPTOR CIRCUIT AND CIRCUIT —
RESISTANT RECEPTACLES.
AS PER NEC 210.12 PROVIDE ALL OUTLETS IN
BEDROOMS, HALLWAY, LIVING, CLOSETS AND
DINING ROOM TO BE ARC FAULT INTERRUPTER
CIRCUIT.
PROVIDE IN THE 15 & 20 AMPS
RECEPTACLES CIRCUITS TAMPER —
RESISTANT RECEPTACLES AS PER
NEC 406.11
PROVIDE ALL SMOKE DETECTORS
NTH BATTERY BACKUP AS PER
FBC 907.2.8.3 AND NFPA 72
IE
Z
O
Q
W
J
W
Z
W
;!t
z°
I
o
U-)
LO
N
Z�'
"
M
ti
LM E
�a
J
LL
�
O U
LO
W
E. 0.
m O
L W
000
N CU
U z
0
"
A
LO @
O >
00
W
(3)
o N
T—
CO
0
W N
0 C\l
cM
I
Z
m o
°o
Z
u-
Z
Vi
-a
Z
z cu
—j
O
woo
_.�
W
LL N
Z
O
Q
W
J
W
Z
W
;!t
z°
I
o
U-)
04 -15 -2011
Z�'
"
M
— cu
AS SHOWN
�a
J
LL
�
DESIGNED
E. 0.
U)
W
�
ZLo
�
0
0
It
DATE
04 -15 -2011
SCALE
AS SHOWN
Y
DESIGNED
E. 0.
w
DRAWN
AG
DRAWING NO.
Eml
SHEET OF 2