11-468-005ELECTRICAL SPECIFICATIONS 1. GUARANTEES AND RESPONSIBILITY: ALL MATERIAL AND WORKMANSHIP FOR ONE YEAR FROM DATE OF ACCEPTANCE. ALL DEFECTS SHALL BE CORRECTED WITHOUT CHARGE, INCLUDING ALL PATCHING AND PAINTING AND OTHER INCIDENTAL REPAIRS OR REPLACEMENT. 2. WORKMANSHIP: ALL WORK SHALL BE INSTALLED IN A NEAT, ORDERLY MANNER. DEVICES, PLATES, EXPOSED RACEWAYS, ENCLOSURES, COVERS, FIXTURES, ETC. SHALL BE ALIGNED PERPENDICULAR TO OR PARALLEL WITH, THE PRINCIPAL STRUCTURAL MEMBERS. THE EDGE OF THESE COVERS, PLATES ENCLOSURES, ETC., SHALL BE IN VERTICAL OR HORIZONTAL PLANE AS APPLICABLE FOR THE ITEMS INVOLVED. EXPOSED RACEWAYS SHALL BE OFFSET WHERE THEY ENTER SURFACE - MOUNTED EQUIPMENT. WIRING INSTALLED IN PANELS AND OTHER ENCLOSURES SHALL BE NEATLY LOOPED AND LACED & NOT WADDED OR BUNDLED. 3. MATERIAL STANDARDS: ALL MATERIALS SHALL BE NEW & CONFORM TO THE APPLICABLE STANDARDS WHERE SUCH HAVE BEEN ESTABLISHED FOR THE MATERIALS IN QUESTION. THE PUBLICATIONS AND STANDARDS OF THE ORGANIZATIONS BELOW ARE APPLICABLE TO THE MATERIALS SPECIFIED HEREIN. A. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) B. UNDERWRITER'S LABORATORIES, INC. (UL) C. AMERICAN STANDARDS ASSOCIATION (ASA) D. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) E. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) WHERE REFERENCE IS MADE TO TRADE NAMES OR NAMES OF MANUFACTURERS, SUCH REFERENCES ARE MADE SOLELY TO DESIGNATE AND TO IDENTIFY THE QUALITY OF THE MATERIALS OR EQUIPMENT TO BE FURNISHED, AND DOES NOT PRECLUDE THE USE OF "EQUAL" EQUIPMENT AS APPROVED BY THIS ENGINEER. 4. REFERENCE STANDARDS: INSTALLATION SHALL COMPLY WITH THE REGULATIONS OF THE FOLLOWING: A. NATIONAL ELECTRICAL CODE (NFPA), LATEST EDITION B. SOUTH FLORIDA BUILDING CODE, LATEST EDITION 5. DO NOT SCALE ELECTRICAL DRAWINGS. REFER TO PLANS AND ELEVATIONS FOR EXACT LOCATION OF ALL EQUIPMENT. CONFIRM WITH OWNER'S REPRESENTATIVE. 6. THE MINIMUM WIRE SIZE SHALL BE #12 AWG, UNLESS OTHERWISE NOTED. ALL CONDUCTORS SHALL BE COPPER WITH TW INSULATION FOR SIZE #8 AND SMALLER. CONDUCTORS LARGER THAN #8 SHALL HAVE TYPE THE INSULATION, UNLESS OTHERWISE NOTED. ALL CONDUCTORS #10 AND SMALLER MAY BE SOLID AND ALL THOSE #8 AND LARGER SHALL BE STRANDED. 7. ALL RACEWAYS AND PIPES PLACED IN OR THRU A CONCRETE SLAB SHALL BE SPACED A MINIMUM OF 3 DIAMETERS OF THE LARGEST GROUNDING CKT SERVES ELECTRODE WIRE CON DUIT CONDUCTOR PHASE A C CKT SERVES BOLTED -TYPE WIRE oUT 0 CONNECTION DEVICE —� `— T OR RANGE 0 OR EXOTHERMIC WELD. B OCIM LIGHT GROUNDING O O NONMETALLIC • ELECTRODE PROTECTIVE (v� 30/2 SLEEVE. 3/4 5000 3 1 CO +` SWITCH LEG cM e a d • • " • CONCRETE FOUNDATION, d COPPER CONDUCTOR OR STEEL SMOKE DET , • • ° REINFORCING ARGOR ROD NOT CONNECTIOt d °° �° LESS THAN VINCH DIAMETER. NOTES: , • ° d 20 N. 9 d ° ° •' �; 1.- ALL SMOKE DETECTORS MUST H/ MIN. d .d° d a INTERCONNECTED, DISHWASHER 20/1 2.- ALL SMOKE DETECTORS TO BE F 20 FT DIRECT CONTACT CIRCUITS, AHEAD OF ALL SWITCHES, MIN. WITH EARTH. 3.- ALL BEDROOM RECEPTACLES OUT 1 1/2 800 ARC FAULT INTERRUPTER C.B. ENCASED GROUNDING 8 ELECTRODE DETAIL #12 1/2 SCALE: N.T.S. 9 WEATHERHEAD CONDUIT OR PIPE OF ANY OTHER SERVICE. NEW FPL SERVICE CONNECTION ELECTRICAL CONTRACTOR MUST CONTACT FPL FOR SCHEDULE 8. ALL RACEWAYS SHALL BE CARLON PY -DUIT, TYPE A, U.L. LISTED OR CONNECTION & REQUIREMENT INCLUDE IN BID ALL EQUAL. CONDUIT FITTINGS AND CEMENT SHALL BE PRODUCED BY NECESSARY WORK. THE SAME MANUFACTURER. A. RUNS IN CONCRETE IN CONTACT WITH EARTH, UNDERGROUND,EXPOSED OR IN INTERIOR WALLS OR FEEDERS 1 1/4" OR LARGER, SHALL BE RIGID STEEL OR PVC B. METALLIC ELECTRICAL CONDUIT MAY BE USED IN THE INTERIOR PARTITIONS AND CEILINGS. 9. OUTLET BOXES SHALL BE POLYVINYL CHLORIDE AND SHALL CONFORM TO THE N.E.M.A. STANDARDS. 10. THE DISCONNECT SWITCHES SHALL BE HORSEPOWER -RATED HEAVY DUTY, QUICK- MAKE/QUICK -BREAK IN N.E.M.A: 1 INTERIORA EXTERIOR. 11. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH & INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR THE EQUIPMENT TO BE PLACED IN A PROPER WORKING ORDER. SHOULD ANY ITEMS BE MISSING, HE SHALL NOTIFY THE ARCHITECT /ENGINEER BEFORE COMMENCING WORK. NO ADDITIONAL PAYMENT WILL BE MADE FOR THE CONTRACTOR'S FAILURE TO NOTIFY THE ARCHITECT /ENGINEER. ELECTRICAL NOTES: 1. OUTSIDE RECEPTACLES, RECEPTACLES AT BATH, GARAGE AND KITCHEN COUNTER, SHALL BE G.F.I. 2. ELECTRICAL METER AND PANEL LOCATION MAY VARY AS PER SERVICE ENTRANCE LOCATION. 3. ELECTRICAL CONTRACTOR TO COORDINATE SERVICE WITH F.P.L. 4. ALL "J" BOXES SHALL COMPLY WITH N.E.C. 314 5. ELECTRICAL OUTLETS (RECEPTACLES AND LIGHTING) BELOW BASE FLOOD ELEVATION SHALL BE INSTALLED AT THE HIGHEST PERMITTED ELEVATION AND SHALL BE INSTALLED ON (SEPARATE) INDEPENDENT CIRCUITS FROM THOSE IN THE HABITAT AREAS. 6. NO APPLIANCES OR APPLIANCE OUTLETS SHALL BE INSTALLED BELOW BASE FLOOD ELEVATION. 7. IT IS SUGGESTED THAT YOU CONFER WITH FLORIDA POWER AND LIGHT TO LOCATE THE ELECTRICAL METER TO COMPLY WITH FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS. 2SETS(2) #2/0 FROM FPL EXISITNG FPL METER TO BE REPLACED TABLE 250.66.SERVICE IN (2) #210. GROUNDING11 /0 1# 1/0 THWN -314" (GND) O 22,000 AIC 2 "�— (3) #3/0 THWN (3) #3/0 THWN I NEMA 311 2 I 225 -) TWO 5/8 "x10' GROUNDING RODS SPACED 6' BOND TO A 3/4" COPPER WATER PIPE STUB -OUT AT METER LOCATION & ENCASED GROUND SEE DETAIL. PANEL A 200A ELECTRIC RISER DIAGRAM SCALE: N.T.S. BUS RATING: 225A TYPE: SIEMENS,GE,SD OR EQUIV. , , MAINS: ML SERVICE: 10,3W PANEL A POLES: 50 MINIMUM VOLTAGE: 120/240 FEEDER: #3/0 AIC:10,000 NEUTRAL: #3/0 CKT SERVES TRIP POLE WIRE CON DUIT VA PHASE A C CKT SERVES POLE WIRE oUT VA 1 RANGE 50/2 #6 1 12000 • CEILING MOUNTED SMOKE DETECTOR 2 DRYER 30/2 #10 3/4 5000 3 1 CO 0 W N 0 C\l cM I Z • 4 u- Z Vi -a 5 WASHER 20/1 #12 1 1/2 1200 • 6 DISHWASHER 20/1 #12 1/21 1200 7 DISPOSAL 20/1 #12 1 1/2 800 • 8 SMALL APPLIANCES GFI 20/1 #12 1/2 1800 9 SMALL APPLIANCES 20/1 #12 1/2 1800 • 1110 GEN. LIGHTING. & RECEPT. 20/1 #12 1/2 1800 11 GEN. LIGHTING. & RECEPT. 20/1 #12 1/2 1800 • 12 GEN. LIGHTING. & RECEPT. 20/1 #12 1/2 1800 13 GEN. LIGHTING. & RECEPT. 20/1 #12 1/2 1800 114 GEN. LIGHTING. & RECEPT. 20/1 #12 1/2 1800 15 GEN. LIGHTING. & RECEPT. 20/1 #12 1 1/21 1800 • 116 GEN. LIGHTING. & RECEPT. 20/1 #12 1/2 1800 17 GEN. LIGHTING. & RECEPT. 20/1 #12 1/2 1800 118 EXTERIOR RECEPT. GFI 20/1 #12 1/2 1200 19 WATER HEATER 30/2 #10 3/4 4500 • 120 A/C UNIT 60/2 #6 1 11600 21 1 122 23 POOL PUMP 30/2 #10 3/4 1100 • 24 CONDEN. UNIT 50/2 #6 1 1 10800 25 1 1 1 • 26 27 SPRINKLER PUMP 30/2 #10 3/4 2200 • 28 SPACE 29 • 30 31 SPACE • 1132 33 1134 35 • 1136 37 138 39 • 40 41 • 42 ELECTRICAL LEGEND SYMBOL DESCRIPTION ® CEILING MOUNTED LIGHT ®- DUPLEX RECEPTACLE NEW CIRCUIT RECEPTACLE GROUND FAULT INTERRUPTER O EXISTING ELECTRICAL PANEL PB= PUSH BUTTON WALL SWITCH (SINGLE, DOUBLE) $3 WALL SWITCH (3 -WAY) ® 220 VOLT RECEPTACLE C3 DISCONNECT SWITCH in EXHAUST FAN ® CEILING MOUNTED SMOKE DETECTOR " WALL MOUNTED LIGHT IE] WALL MOUNTED LIGHT - WHEATER PROOF sD SMOKE DETECTOR W/ BATTERY BACKUP ABBREVIATIONS' U-) R.= EXISTING TO BE RELOCATED GFI= GROUND FAULT INTERRUPTER N = NEW CIRCUIT VH= VERIFY PRIOR TO INSTALLATION UC= UNDER CABINET PB= PUSH BUTTON C.= COUNTER TOP LEVEL VP= VAPOR PROOF BC.= BELOW COUNTER WP= WEATHER PROOF 000 EL= EXTERIOR LIGHT 1/4" BIRD SCRE RUST RESISTANT FLASHING 1/2" SHEET METAL SCREW (4 TYPICAL) 4"0 SHEET METAL EXHAUST DUCT. SEE FLOOR PLAN FOR SIZE GAUGE: 24 05 ELLMMET FANS BATH ROOM ROOF CAP DETAIL. (TYPA ELECTRICAL PLAN SCALE: 1/4"=l'-O" THE SCOPE WORK INCLUDE IN THE LAUNDRY AREA GENERAL REPARATIONS DUE FIRE: TRUSSES ROOF DRYWALL AT WALLS AND CEILING INTERIOR PARTITIONS FLOOR TILES PAINT ELECTRICAL CKTS AND DEVICES MECHANICAL INSTALLATIONS PLUMBING INSTALLATIONS 15 & 20 AMPS RECEPTACLES IN COMPLIANCE WITH NEC 2008 EDITION ITEMS 210.12 & 406.11 TO BE COMBINATED TYPE:ARC FAULT INTERRUPTOR CIRCUIT AND CIRCUIT — RESISTANT RECEPTACLES. AS PER NEC 210.12 PROVIDE ALL OUTLETS IN BEDROOMS, HALLWAY, LIVING, CLOSETS AND DINING ROOM TO BE ARC FAULT INTERRUPTER CIRCUIT. PROVIDE IN THE 15 & 20 AMPS RECEPTACLES CIRCUITS TAMPER — RESISTANT RECEPTACLES AS PER NEC 406.11 PROVIDE ALL SMOKE DETECTORS NTH BATTERY BACKUP AS PER FBC 907.2.8.3 AND NFPA 72 IE Z O Q W J W Z W ;!t z° I o U-) LO N Z�' " M ti LM E �a J LL � O U LO W E. 0. m O L W 000 N CU U z 0 " A LO @ O > 00 W (3) o N T— CO 0 W N 0 C\l cM I Z m o °o Z u- Z Vi -a Z z cu —j O woo _.� W LL N Z O Q W J W Z W ;!t z° I o U-) 04 -15 -2011 Z�' " M — cu AS SHOWN �a J LL � DESIGNED E. 0. U) W � ZLo � 0 0 It DATE 04 -15 -2011 SCALE AS SHOWN Y DESIGNED E. 0. w DRAWN AG DRAWING NO. Eml SHEET OF 2