12-910R-008I
0
I
,
a
AIR CONDITIONING SPECIFICATIONS
L GENERAL:
A. ALL DIMENSIONS AND ACTUAL CONSTRUCTION CONDITIONS MUST BE VERIFIED AT THE
PROJECT SITE PRIOR TO SUBMITTING BID. IT IS THE RESPONSIBILITY OF THE CONTRACTOR
TO NOTIFY ENGINEER OF ANY DISCREPANCIES IMMEDIATELY.
B. THESE DRAWINGS ARE DIAGRAMMATIC AND REQUIRE CLOSE COORDINATION WITH EXISTING
STRUCTURE, LIGHTS, CONDUITS, PLUMBING AND CEILING SYSTEM. THE CEILING SPACE IS
EXTREMELY TIGHT AND WILL REQUIRE CAREFUL ADVANCE PLANING BEFORE DUCT
INSTALLATION. THE CONTRACTORS PRICE FOR THIS PROJECT SHALL INCLUDE A SITE
VISIT TO FIELD VERIFY, ALL COORDINATION, DUCT TRANSITIONS AND FIELD ROUTING AS
REQUIRED FOR A COMPLETE OPERATING AND TESTED SYSTEM.
C. SUBMIT MANUFACTURERS DATA AND SHOP DRAWINGS ON ALL EQUIPMENT, MATERIALS AND
DUCT SYSTEM LAYOUT FOR REVIEW BY THE ENGINEER PRIOR TO ORDERING, FABRICATION,
OR INSTALLATION. PRIOR TO ORDERING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF
THE CONTRACTOR TO VERIFY THAT EQUIPMENT VOLTAGE SPECIFIED IS AVAILABLE.
D. ALL MOTORS STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR TO BE
WIRED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
E. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE FOLLOWING CODES:
1. THE FLORIDA BUILDING CODE 2007
2. NFPA -90A AIR CONDITIONING AND VENTILATION
3. SMACNA. LOW VELOCITY DUCT CONSTRUCTION
4. NFPA 101, LIFE SAFETY CODE
2. MATERIALS:
A. GALVANIZED STEEL SHEET METAL DUCT WORK INSTALLED IN ACCORDANCE WITH "SMACNA"
STANDARDS WITH R -6 FIBERGLASS DUCT WRAP INSULATION. PROVIDE MANUAL VOLUME
DAMPERS AT ALL BRANCH TAKE -OFFS. PROVIDE TURNING VANES AT ALL ELBOWS.
FLEXIBLE ROUND DUCTS MAY BE USED FOR DIFFUSER DROPS AS SHOWN ON PLANS.
SUBMIT SHOP DRAWINGS.
B. OUTSIDE AIR AND EXHAUST DUCTS SHALL BE AIR LEAK SEALED GALVANIZED SHEET METAL.
OUTSIDE AIR DUCTS SHALL BE INSULATED SAME AS SUPPLY DUCTWORK ABOVE.
3. CONTRACTOR'S WARRANTY:
A. CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FOR ALL EQUIPMENT AND
SYSTEMS FROM DATE OF FINAL ACCEPTANCE BY THE OWNER, (CERTIFICATE OF OCCUPANCY).
HVAC SYMBOL LEGEND:
Q)
THERMOSTAT
DUCT SMOKE DETECTOR
ROOF MTD. EXH. FAN
®
REMOTE BULB SENSOR
DUCT TURN DOWN
®
DUCT SMOKE DETECTOR
DUCT TURN UP
®
TEST, RESET & ANNUNCIATOR
��,�
FLEXIBLE DUCT
al=:�
TRANSITION
FX 1E
SMOKE CONTROL
EXISTING SUPPLY
TURNING VANE
1E
EXISTING RETURN
sp
45' BRANCH DUCT TAKE -OFF
R
RELOCATED SUPPLY
5V
HORIZONTAL FIRE DAMPER
1z_1R
RELOCATED RETURN
.V.D.
MANUAL VOLUME DAMPER
''!`
1
RETURN REGISTER
�N
NEW SUPPLY
�'
SUPPLY DIFFUSER
FIN
NEW RETURN
'
RETURN AIR GRILLE
—
F
FIRE DAMPER
COMBINATION FlRE /SMOKE DAMPER
—►
AIR FLOW DIRECTION
MOTORIZED DAMPER
®
EXHAUST FAN
--
VALVE
NOTES:
GYPSUM WA
RETAINING ANGLE
1 1/40 1/4 x1/8' ai
GYPSUM FILLER
DAMPER ;
MANUAL DAMPER W/
LOCKING ADJUSTMENT
HANDLE i
BRANCH
DUCT —
' G
COD
EXISTING
INLINE DIS
EXHAUST F
10 /;
/�� r
EXISTING
EXHAUST
FAN G� �
5�
P.
10 �\ pt
x,
\ \�
EXISTIN �' �X \S�• \r
INLINE EASE \ Nv \
13 -�
EXHAUS FAN
7
2 �n '200 . N`�'" __J
�
3 / —
\
r, •.. \ � . . � L I Lam' ~. .<�.; . .. .............. ... ... .... i ....
El
9
I \ as
El
E
j/)
L_.)
U.L. SIZE LIMITATIONS 0
VERTICAL MOUNT (DUCT OPENING SIZES);
MAXIMUM PANEL 60 "x54"
MAXIMUM ASSEMBLY: 120 "x114"
MINIMUM PANEL 4 "x4"
HORIZONTAL MOUNT (DUCT OPENING SIZES):
MAXIMUM PANEL 60 "x54"
MAXIMUM ASSEMBLY. 102 "44"
MINIMUM PANEL 4 "x4'
NOTES:
1. UNDERWRITERS LABORATORIES LISTED AND
1 -1/2 HOUR STANDARD 555. CLASS 'A
2. STANDARD CONSTRUCTION 18 GA. GALVINIZED STEEL
3. PROVIDE 1/8" MOUNTING SCREWS ON 6" CENTERS.
4. PROVIDE ACCESS PANELS IN ADJACENT DUCT FOR ACCESS.
NAILOR —HART MODEL 0110 TYPE A 1 1/2 HR "DYNAMIC TYPE"
VERTICAL MOUNT FUSIBLE LINK TEMPERATURE: 1657
FIRE DAMPER DETAIL:
NOT TO SCALE
DIRECTION OF
AIR FLOW
BRANCH TEE
TRUNK DUCT
DIRECTION OF
AIR FLOW
45* BRANCH DUCT
CONNECTION
TURNING VANES
CHANNEL
DAMPER
BLADE
ZSPLITTER DAMPER CONTROL
ROD W/ LOCK
HANGING
HANG ALL DUCT PER SMACNA STANDARDS
I
CHANNEL
i
STRAP & SADDLE
'Ely Dllxi7
CORNER ANGLE
TURNING VANES
HVAC DUCT DETAILS
NOT TO SCALE
MECHANICAL PLAN
PLAN KEY NOTES:
OREMOVE ALL SUPPLY & RETURN
DUCTWORK FROM SPACE BACK TO AIR
HANDLERS.
OEXISTING CHILLED WATER AIR HANDLER TO
REMAIN.
OREMOVE EXISTING KITCHEN HOOD SUPPLY
AND EXHAUST FANS AND DUCTWORK FORM
SPACE.
OREMOVE EXISTING GREASE DUCT FROM
SERVICE CORRIDOR AND CAP OFF AT
VERTICAL CHASE. PATCH WALL OPENINGS.
FIELD VERIFY COORDINATE W/ OWNER
EXACT LOCATION OF TERMINATION.
OREMOVE EXISTING EXHAUST FAN, DUCT AND
LOUVER. PATCH WALL OPENINGS.
OREMOVE EXISTING EXHAUST FAN AND CAP
DUCT.
OPROVIDE FIRE DAMPER IN EXISTING OUTSIDE
AIR DUCT. OFFSET DUCT AS REQUIRED
FOR FIRE DAMPER INSTALLATION. FIELD
VERIFY DUCT SIZE. PROVIDE DUCT ACCESS
DOOR AND ACCESS DOOR IN CEILING.
REUSE EXISTING FIRE DAMPER IF POSSIBLE.
OPROVIDE FIRE DAMPER IN EXISTING
EXHAUST DUCT. OFFSET DUCT AS
REQUIRED FOR FIRE DAMPER INSTALLATION.
FIELD VERIFY DUCT SIZE. PROVIDE DUCT
ACCESS DOOR AND ACCESS DOOR IN
CEILING. REUSE EXISTING FIRE DAMPER IF
POSSIBLE.
ORELOCATE EXISTING EXHAUST DUCT IN
CONFLICT WITH NEW CORRIDOR WALL.
10 EXISTING SUPPLY DIFFUSER TO REMAIN.
11 EXISTING RETURN GRILLE. CEILING IS
PLENUM RETURN.
12 NEW SUPPLY DUCT.
13 NEW SUPPLY DIFFUSER. 8x8" TITUS TCD
SURFACE MOUNT. 2 -WAY WITH OPPOSED
BLADE DAMPER.
SCALE: 1/8" = 1' -0"
CONTRACTOR SHALL
REUSE EXISTING
DIFFUSERS WHERE
POSSIBLE
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
DRAWN
FIRE DAMPER(S)
CHECKED,
DAS
SMOKE DAMPER(S)
FIRE RATED ENCLOSURE
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
FIRE STOPPING
SMOKE CONTROL
WARNING!
sm
MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG
ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND
LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL
COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAI
REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE
PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS.
CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING
PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF
REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS.
"0 THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED
IEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE
\PPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF
-IENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE
tEPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSIO
)F HENZ ENGINEERING INC.
I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE
LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION
OR FXUFMCIIIN PROVIDE ENGINEERING SERVICES IN THE MECHANICAL
I L E I IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS
(� •8Y. DER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER
I $ Br 11& ''f. ® OVER I CERTIFY THAT THE COMPANY OFFERING THE
II RING S Vi t NZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE
A"05 N 80-.TO PROVIDE THE ENGINEERING SERVICE.
!". -TATE OF
DEC 13 2011
DATE:
4117 RGlf R111G, InC.
consULTInG TnGlnim
2320 NE 9th Street, Sulte 200
Fort Lauderdale, Florldo 33304
T 954.523.4933
F 954.523.5052
www.henz.com
PROJECT No.: 11098.00
arc
NORBERTO ROSENSTEIN
ARCHITECT , INC.
MCHMCTM — NTM DPI — R M
126 S. FEDERAL HIGHWAY
SUITE # 202
DANIA BEACH, FLORIDA 33004
PH: (954) 922 -6551
FAX: (954) 922 -7388
EMAIL- info•rosensteinercNtect.com
WEB= www.rosensteinercNtect com
STATE REG. NO. AR00I6674
NATL. RECs. NO. 69178
COPYRIC*IT 02005
NOR15ERTO ROSENSTEIN ARCHITECT, AIC.
ALL RICsHTS RE5ERIjD. THI5 DOCUMENT
OR PARTS THEREOF, MAY NOT SE REPRODUCED
IN ANY FORM UdT'HOUT PERMISSION
DESIGNED
"_4::� =t
DRAWN
CHECKED,
DAS
-�•� ,. J
I HEREBY CERTIFY THAT THESE PLANS
WHERE PREPARED BY ME OR UNDER
MY SUPERVISION, AND TO THE BEST
OF MY KNOWLEDGE, COMPLY WITH ALL
APPLICABLE CODES.
LLU I OWNER REVISION 11/03/11
R E V I S 1 0 N S
COMM. DATE
2011 -37 0/1/2011
5701 SUNSET DR
SUITE A15A
WHITE BOX
5OUTH MIAMI
FLORIDA, 33143
MECHANICAL P LAN
M -1
El 1