12-910R-007THROUGH- PENETRATION FIRESTOP SYSTEMS (XIEZ)- Continued System No. CAJ1008 (Formerly System No:'93) F Ratings -1, 2 and 3 Hr (See items 1, 2A, 20 and 2C) i T Rating--O Hr L Rating At Ambient -2 CFM /sq ft (See Item 5) L Rating At 400 F -less than 1 CFM /sq it (See Item 5) aectlen A -/l 1. Floor or Wall Assembly --I Ightwelghl or normal weight (100 -150 pefl concrete. Min thickness, OF concrete floor or wait Is 2-1/2 In. for 1 hr F Hating and 4.1/2 In. for 2 or 3 hr F Rating.! Wall may also be constructed of any UL Classified Concrete Blocks'. Max area of cperitngi 1152 sq In. with max dimension of 36 In. See Concrete Blocks (CAZT1 category In the Fire Reslslance Directory for names of manu -I facturers. 2. Pipe or Conduit -Nom 12 in. dlara (or smaller) Schedule 10 (or heavler) steel pipe, nom a ln,l diem (or smaller) steel conduit, nom 4 In. diam for smaller) steel EMT or Type l for heavier)' copper tubing. Min clearance between pipes 1 In. Min clearance between pipe and wall of through opening 1/4 In. When single nom 4 In. diem (or smeller) pipe, conduit or EMT is tn. stalled In nom 7 In, diem (or smaller) circular throlugh opening, min clearance between pipa, conduit or EMT and wall of through opening is O In. (point contact). Pipes and conduits rigidly I supported an both sides of floor or wall assembly. 3. FIR. Void or Cavlty Matatials' -Wrap Strip -Nom 1/4 In, thick intumescent alsstameric ma- Seriel faced on ono side with aluminum foil, supplied in strips. Min 2 In. wide strip wrapped wound plpe/conduit (foil side exposed) and secured in place with steel wire or aluminum fall (ape. Wrap strip to extend approx 7/8 In. beyond each face of the Intumescent sheet (Item 4).1 When nom 6 M, diem (or smaller) pipe, conduit or EMT Is installed In through opening, no; wrap strip is required on pipe, cnndult or EMT for 2 hr F Rating, I Minnesota Mining & Mfg. Co. -Types FS -195, FS -195+ ' 4. Fill, Void or Cavity Materials• -- -Intumescent Sheet -Rigid aluminum foil -faced sheet with' galy steel sheet backer. Sheet cut to tightly follow the Contours of the pipe wrap strip for Indl -! vldual pipe) and with a min lap of 2 In. on all sides of the through opening. Sheet to be In -1 stalled whit the gals steel sheet backer exposed (aluminum foil facing against floor or wall, Surface). Sheet secured to top surface of floor and both sides of wall using min 1/4 In. diem by 1 -1/2 In. long steel expansion bolts, or equivalent. In conjunction with min 1 -1/4 Fn. diem' sleet fender washers. Max spacing of sheet fasteners not to exceed a In. OC. Prior to installs -1 lion of the sheet, a nom 114 in. diem bead of caulk Clem 5) shad be appnod as a gasket be -1 twoen the sheet and The aurface.of the floor or wall around the perimeter of the through' opening. As an alternate when (1) the max pipe or conduit sire is nom 4 In. diem, (2) each' pipe or conduit Is provided with a loyor of wrap strip and (3) no bundled cables or Insulated' pipes pre installed in the through opening, the intumescent sheet may be Installed on bottom' surface of floor or on only one side or wan. Minnesota Mining & Mfg, Co: -Types CS -195, CS -195+ I 5. Fill, Void or Cavity Meterlels•- Ceulk-•Generous application of caulk to be applied around the base of the wrap strip (or individual pipe) at its egress from the Intumescent shoot(s) In ad dltion (o completely covering the wrap strip up to the interfaces) with the pipe, pipe Insula. Sion and /or cable bundle. Nom 1/4 in, diem bead of caulk to be applied as a gasket between the Intumescent shoot and the floor or wall surfaces. I Minnesota Mining & Mfg. Co Types CP -25 SA, CF-25 WS, CP -25 W8, CP.251 WB+. (Note: L Ratings apply only when Type CP -25 WB+ caulk Is used.) S. Steel Cover Strip -Min 2 in. wide ship of min 0.015 Ta thick (3D gauge) gale stool centered) over entire length of slit made In Intumescent sheet (Item 4) to permit instpnation about that pipe /cable bundle. Prior to instaltiGon of the steal strip, slit In Intumescent sheet covered with nom 1/4 in, diem bead of caulk poem 51. Steel cover strip secured to gale steel backer of in(u 1 mescent sheet with steel shoat -metal screws or steel rivets spaced max 2 In. OC on each side Of slit. 7. Support Channel -fiat Shown)-When ayes of through opening exceeds 5713 zq In An Inter - modiste support channel shall be Installed flush with top surface of floor or both surfaces of wall. Support channels to be min 1 -5/8 by 1 -5 /8 In. and formed of min 0.083 In, thick (No. 12 gouge) painted or gety steel. Ends of stool channel bolted or welded to steel angles an- chored to Inside walla of through opening. When steal rupport channels are centered beneath butted seams of Intumescont shoats, no steel cover strip poem 6) Is required over butted seam. Intumescent sliest secured to stool support channels with steel sheet metal Screws In conjun lion with min 1.1/4 In. diem steal fonder washers. When support channel Is used beneath but rod seam of Fntumoscont sheets, fasteners spaced max 3 In. OC on each side of butted seem. When support channel Is located away from Intumescent sheet seam, fasteners ,paced max BI LOOK FOR MARK ON PRODUCT FIRE RESISTANCE DIRECTORY f8XRH) 1 THROUGH - PENETRATION FIRESTOP SYSTEMS (XHEZ)- Continued System No. CAJ1018 (Formerly System No. 162) F Rating -2 Hr T Ratings -0, 1/4, 1/2, and 3/4 Hr (See Item 2) .a41. A"TRI11.1 1. Floor or Well Assembly -Min 2 -1/1 in. thick reinforced lightweight or normal weight (105 pcf) concrete. Well may also be constructed of any UL Classified Concrete Blocks% Max diem of opening is 8 In. See Concrete Block (CAZTI category in the Firo Resistance Directory for names of manu facturers. 2. Through Penetrants -- Metallic pipe, conduit or tubing to he centered within the firestop Sys- tem. Pipe, conduit or tubing to be rigidly supported on both sides or floor or wall assembly Stool pipes or eonduots may be Installed Individually or In multlples- The spats betwaan adja� cent pipes, conduits or tubing• and between pipes, conduits and tubing and periphery of 1 n metallic i as'i opening shall be min 0.63 In, In max 2.15 in. The following types ands sizes f p p , conduits or tubing may be usod: A Steer PTp"cm 8 In. diem (or smelter) Schedule 5 for heavier) stoat pipe. 9. Conduit -Nam 4 Ill diem (or smapor) electrical metallic tubing. I C. Conduit --Nom 6 In. diem (or smaller} rigid gale steel conduit I The T Ratings are dependent upon the concrete slab thickness and size of steel pipe. Conduit or tubing as shown In the following table: i Min flax Dlam T Concrets of Sts") Pipe I n&Hhg Thickness or Conduit pn) 1H+) 2-1/2 In. 6 0 I - 2 -1/2 in. 1 -1/2 114 1 2.1/2 in. 1-1/4(+) 174 2.1/2 fn. 1/2 1/2 3 -1/4 )n. 1/2 3/4 i ( +) Multiple conduits or pipes. 3. Form"Not shown) -Used as a form to prevent leakage of fill material during Installation') Forms to be a rigid sheet material, cut to fit the contour of the penetrating hem and friction filled within opening to accommodate required thickness of fill material. Forms to be removed after fill material has cured 4. FIR, Void or Cavity Materiels'- Mortar -Min 2 -1/4 in. thickness of fill material applied within the annulus, "ush with top surface of floor or with both surfaces of wait. in walls, the total depth within the opening can be completely fined with the fill material, or the fill material n be Installad symmetrically to a min depth of 2 -1/4 In. on each side of the wall. r Co-Type W. R. a e.. A C o YD a ZF1 1 Cle smcallon Mark long n the UL s 0 1ng LOOK FOR MARK ON-PRODUCT Wgn No. 3918 Unrestrained Assembly Rating -1 Ar. tH • rr. 3 P70 �=_ =•C� � Y- , _ _ !J `.._.. . -. - . - . 1 . - ) . . :..4 2 Unrestr6ined &==4End Detail 1. - Precast Contxete Units• - Carbonate, siljceoils, br Jig rhtweight'aggregate. 4 or 8 It wide units with -cross section similar to the above illustration. .Opening( Wy be­ provided through the units for piping, ducts, or similar services and should be suitably enclosed with constructions having at - ateast equal resistAnce, acceptable to euthofittes )taying jurisdiction. American Precast Concrete, Inc- .. Arnold ,Concrate.Products -- Greensboro Div. of Carolina Steel Corp.. Breeko Industries . ­Cleveland Bufilert"Suppty Co. . Nitterhouse'Contrete Prodded, Inc.. ' Southern Cast Stone Co., Inc. ' - Strifston Industries' •- . :" t • - TPAC Div of the Tanner Companies 2. Min Bearing -1-1/2 tn. eM ' ' •. ' : 3. Gmut- Sand - cement type, 3500 psi compressive strength. For a grout stop, compressible material may be placed at bottom of the joint before applying grout. "Bearing the UL Classification FIRESTOPPING DETAILS N.T.S. Irinuuurl- rervtlt(AIJUN 1-IHt51UP SYSTEMS (XHEZ} - Continued System No, CAJ1175 F Rating -2 Hr T Rating -0 Hr - SECTIO14 A--A 1. Floor or Wan Assembly -Min 2 -1/2 in. thick lightweight or normal weight IIOD -160 pcQ con. creto. Wan may also be constructed of any UL Classified Concrete Blocks*. Max diem of dr- cuter through opening Is 10 in. See Concrete Blocks (CAZt) category in the Fire Resistance Directory for names of monu- Feeturere. iA. Stool Sleeve - (Optional} --No. 10 In. dlam for smaller) Schedule 10 (or heavier) steel pipe sleeve cast into concrete floor or wall. Sleeve to be Rush with or project max 2 In. from top surface of floor or from both Irurfacos of wall. 2- Pipe or Condult -Nom 8 In, diem for smaller) Sehedulde 10 (or heavier) steal pipe. nom 6 In. diem (or smaller) rigid steel condott, nom 4 In, diem (or smanpr) cast Iron *pipe or stool EMT. Max one pipe or conduit per through opening Max annular specs between pipe or conduit and edge of nyough opening not to exceed 1.3/8 in. Min annular space between pipe or con- duit and edge of through opening is zero in. (point confect). Pipe or conduit to be rigidly sup. ported an both sides of flour or wall assembly. 3. Pecking Moter)al--Min 1 in. thickness of tightly-spacked mineral -wool belt material used as a permanent form. Packing material to be recessed min 1/2 In, from top or bottom rustics Of floor or from either surface of wag as required to accommodate the required thickness of caulk fill material (Item 4j. 4. Fill, Void or Cavity Materiels•- Ceulk--Applied to Fill the annular space to a min depth of 1; 2 in. flush with the top or bottom surface of the floor or either surface of the wall. A min 114 Int. diam tread of caulk shall be applied to the floor or wall surface where the pipe. conduit o, EMT Is installed in point contact with the edge of the through opening. Minnesota Mining St Mfg. Co. -Type CP -25 WB+ *Bearing the UL ClesslFcalion Marking FiRE RESISTANCE DIRECTORY MXRH) 1641 THROUGH - PENETRATION FiRESTOP SYSTEMS (XHEZ)- Continued System No. CAJ2002 (Formerly System No. 64 -B) . F Rating -2 Hr T Ratings --O and 2 Hr (See Item 3) L Rating at Ambient -7 CFM /sq ft (See Item 3C) L Rating at 400 F-less than 1 CFM /sq h (See Item 3C) SECTION A -A 1. Floor or Wall Assembly -Min 2.1/2 in. thick lightweight or normal weight 1100.150 pcf) corn crate. Wall may also be constructed of any UL Classified Concrete Blocks'. Max diem of cir. cular opening Is 8-1/2 In. See Concrete Blocks JCAZTI category in the Fira Resistance Directory for names of menu. faoutrers. ' 2. Nonmetallic Pipe or Condult -Nom 4 in. diem for smaller) Schedule 40 polyvinyl chloride (PVC) pipe or Rigid Nonmetallic Conduit+ for use in closed (process or supply) or vented (drain, waste or vent) piping systems. A max of one pipe or conduit Is permitted In the firestop System, Except as noted kt item e, the pipe or corduk shall be centered In the through open- ing. Pipe or conduit to be rigidly supported on both sides of floor or was assembly. See Rigid Nonmetallic Conduit (DZK'q category In the UL Electrical Construction Materi. als Directory for names or manufacturers. 3. Firestop System -The hourly T Ratings for the firestop system are dependent upon the fires - lop orientation (well or rloorl, the size of the nonmetallic pipe or conduit, and rho now thick- ness, as tabulated below: Nam Annular F T Orientation Pipe Space, Rating, Rating, (a) Dlam, In In Hr fir F(b) 1/2.2 1/4 -1 2 0 F(b) 2-1/2.3 1 /I.1 2 0 W. F 1/2 -2 1/4 -1 2 2 W. F 2-1/2,3 1/2 -1 2 2 W. F 3-1/2.4 3/4 -1 2 2 (a)W wall, F -floor p31MFn concrete floor thickness Is 2412 In. The details of the Flrestop System shall be as follows: A. Stool Support Clips -flom 1 In. wide by from 0.019 in. thick 128 gauge) gait steel strips field -formed into "2` -shape with height of Zshape equal to the floor thickness and with width of bottom (as Installed) leg of sufficient length to span annular space. Top (as in- stalled) tog of Zshape to be min 2 In. long and secured In lop surface of floor with 1/4 in. diem by min 1 -1/2 In. long steel expansion bales in conjunction with steel nuts and washers. As in alternate to the 2 -shape clips, the galy stool strips may be formed Into "L ^• she a with height e u p al l0 2 In. and with bottom As t 4 ins al le of suHlcte t length i n e tit to >� g 9 span annular space. Caps secured to outermost wrap strip layer with stool wire tie prior to Insertion in . Min through v enin r g p g e three steel support clips to be used, symmetrica lly lo- Gated, with bottom tag of dips Rush with bottom plane or Floor. When annular space around nom i12 In. to 2 In. diem pipe In floor assembly is 1/4 to 3/8 tn.. steel support .tips are not required. U. F18, Void or Cavity Meterlols• -Wrap Strip -Nowt 1/4 In. thick intumescent efestomeric material faced on one side whh aluminum fan, supplied In 2 in. wide strips. Nom 2 in. wide strips tightly wrapped around nort-metaftle pipe (foil side exposed) to till annular space around pipe. A min of ono layer of wrap strip Is required for nom 1/2 In. to 2 In. diem pipes. Amin of two layers of wrap strip is required for nom 2 -1/2 res, and 3 Fn. diem pipes. A min of three layers of wrap strip Is ragtrived for nom 3.1/2 In. and 4 in. diam pipes. Each layer of wrap strip to be installed with butted seam with butted seams in *uc. osssive layers staggered. Wrap slrlp layers securely bound with stool wire or aluminum fall tape and slid into through opening such that tits bottom edges are flush with the bot- tom plane of the Floor end are restIng on She steel support clip lops. When nom 2 In. to 4 In. diem PVC pipe Is used In min 4.1/2 In. thick concrete floor, the pips may be Installed eccentrically In the through opening (min zero clearance at paint contact location) provid. ad that It) the Inside diem of the through opening is 1.3 to 1.6 times larger than the out- side dram of the pipe, (2) the annular space betwoan the pips and the sides of the open - in at the bottom 2 rn of the through opening g ls completely 0 Pe 9 P lifted with wrap std layers Installed Following the contour of the pipe and Y p P Sy 9 P P (� tits bottom edges of the wrap strip lay. ers era reliably, supported by -I'- shaped stoat support clips anchored to the top surface of the concrete floor. in we x 11 assemblies, the wrap strip layers on the nonmatelGc pipe are to be In tailed In too some manner used for Door assemblies but shall be orestalls11 eymmeui "ally on both sides of the wan with the exposed edges of the wrap strip layers flush with the wen surfaces. Minnesota Mining lit Mfg. Ca -Types FS -195. FS-195+ C. Fill, Void or Cavity Materials'- Caulk ---MFn 114 in. diem continuous bead applied to In- side welts of through opening prior to installation of steel support clips and/or wrap strip. Caulk bead to be recessed 1 in. from the bottom plane or floor. In wail assemblies, caulk bead to be recessed 1 in. from wall surface on both sides of wait. In floor essembries, a nom 1/2 In. stick coating of caulk its to be applied to the top edges of the wrap strip lay- ers and to fill all gaps at the wrap strip /concrete Interface. In wall assemblies, the ex. posed edges of the wrap strip layers and art gaps at She wrap strip /concrete interface on both sides or the wag to be coated with thin layer of caulk. Minnesota Mining & Mfg. Co -Types CP -25 SA, CP -25 N /S, CP -25 WD, CP-25 WB +. (Note: L nedngs appty only when Type CF-25 We+ caulk Is used) •Gearing the UL Classification Marking THROUGH - PENETRATION FIRESTOP SYSTEMS (XHEZ)- Continued System No. WL1001 (Formerly System No. 147) F Ratfngs-1, 2, 3 and 4 Hr (See Items 2 and 3) T Ratings -0, 1, 2, 3, and 4 Hr (See Item 3) L Rating At Ambient --fens than 1 CFM /sq It (See Item 3) L Rating At 400 F-ress than 1 CFM /sq It (See Item 3) SECTION A -A 1. Watt Assembty -The 1. 2. 3 or 4 fir fire•tated gypsum wallboard/stud wall assembly she# be constructed of the materials and In the manner described In the Individual U300 or 11400 Se- rise Was or Partition Designs in the UL Fire Resistance Directory and shad induda the follow - Ing construction features: A. Studs -Wall framing may consist of either wood studs imax 2 IS file rated assemblies) or steal channel studs. Wood studs to Conti$[ of nom 2 by 4 In. lumber spaced 19 In. OC with nom 2 by 4 in. lumber and plates and cross braces. Steel studs to be min 3 -6/8 In. -ids by 13/8 in, deep channels spaced max 24 In, OC. S. Wallboard, Gypsum• -Nom 1/2 or 0/a tn. thick, 4 ft. wide with square or tapered edges. The gypsum wallboard type, thickness, number of faysrs, Fastener type and sliest Oriente - lion shall be as spaclfled in the Individual U300 ur U400 $*rise Design in the UL Fire Re- sistance Directory. Max diem of opening Is 13 -1/2 In. 2. Pipe or Conduit tom 12 In. dram la smallat) Schedule 10 for heavier) steal pipe, mom a In. diem (of smaller) steal conduit. nom 4 In. diem for smaller) steel electrical metallic tubing or Type L or (or heavier) copper tubing or nom 1 to diem (or srnal)w1 flexible sited condu#. When copper pipe or flexible stool conduit Is armed, mu IF Rating of firestop system poem 3) Is 2 h. Steof pipes or conduits larger [inn nom 4 In. diem may only be used In wait$ con- structed using steal channel studs. A max of on* pipe or conduit is permitted In ft Ilroslop system. Pipe sir conduit to be installed near tamer of stud cavity width and to be d2filly sup- ported on both sides of wail assembly. 3. Fill, Vold or Cavity MetetlaV- Caulk -Caulk (ill malarial Installed to completely (dl annuluf space between pipe or conduit and gypsum wallboard anti with a min 1/4 In. $Ham bead of caulk applied to perimeter of pipe or conduit at its egress from the wait. Caulk Installed sym• metrically on both aides of well assembly. The hourly F Rating of the Rrestop system Is depen- don[ upon tits hourly Fir* rating of the wag assembly In which it Is Installed, as shown In the following table The hourly T Rating of the nreetop system Is dependant upon the type or sirs of the pipe or conduit and the hourly fire rating of the wall assembly In which it to Installed, as tabulated below: Max Plpa Annular F T or Conduit: Space. Rating. Ratin Dism, to In Hr Ik 1 0 to 3/10 1 or 2 0 +, 1 or 2 1 1/4 to 1/2 3 or 4 3 or 4 4 0 to 1/4 1 or 2 0 8 1/4 to 1/2 3 or 4 0 12 3/ 18 to 3/8 1 or 2 0 +When copper pipe Is used, T Rating Is 0 h . Atlnnesote Mining fit Mfg. Co. Types CP -25 SA. CP -25 WS, CF-25 WB, CP -25 W5 +. (Note: L Ratings apply only when Type CF-23 WB+ caulk Is used.) 'Bearing the UL Classification Marking LOOK FOR MARK ON PRODUCT THROUGH - PENETRATION FIRESTOP SYSTEMS (XHEZ) - Continued as a permanent fort. Packing material to be foeessed from both sides of wall as required to Accommodate the required thickness of fie material. +13 ailing the UL Listing Mark *Dealing the UL Classlflcatlon Marking System No. WL2002 (Formerly System No. 148) F Ratings -e•1, 1 -1/2 and 2 lit (See Item 3) T Ratings --3/4, 1, 1 -1/2 and 2 Hr (See Item 3) L Rating At Amblent -7 CFM/sq ft (See Item 3C) L Rating At 400 F -1 CFM /sq ft (See item 3C) SECTION A -A 1. Well Aaeembly -The I or 2 hr fire -rated gypsum wallboard/stud wan assembly shall be can. structad of the materials and in the manner described In the Individual U300 or U400 Series Wall or Partition Design In the UL Fire Resistance Directory and shall Include the Following comitrtaction features: A. Studs -Well framing may consist of &other wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 In. hrmbw spliced 10 In. OC with nom 2 by 4 In. lumber end plates and cross braces. Stool studs to be min 3-6/8 In. wide by 1-3/8 In• dsep channels spaced max 24 In. OC. B. Wallboard, ayposum• -6/8 Ism. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and shoot orientation shad be as specified In the individual 0300 or U400 Series design In the UL Fire Resistance DI. ractory. Max diem of opening Is 7 In. 2. Nonmetallic Pipe or Conduit-Ono nonmetallic pipe or conduit is centered within the firestop system. Pipe or conduit to be Installed near center of stud cavity width and to be rigidly sup• ported on both sides of wall. The following types and sizes of nonmetallic pipes or conduit may be used: A Nom 8 In, diem (or smaller) Schedule 40 for haavied sotidcora polyvinyl chloride p'VC) 8. NI om 4 in diem for smaller) Schedule 40 for heavier) cellular -core polyvinyl chloride (PVC) pipe. C. Nam 4 in. diam (or smaller) Schedule 40 (or heavier) solid -cote scrylonirdle-bulacitene- styrene JABS) pipe. D. Nom 4 in. diem (sir smaller) Schedule 40 tar heavlad fire retardant polypropylene (FRPP) pips. E Nom 4 In. diem (or smaller) Rigid Nonmetallic Conduit formed of PVC. F. Nom I In. diem ( amaler) Electrical Nonmetallic Tubing formed of PVC. See Rigid Nontnotalllo Condult(02KT) and Electrical Nonmetallic Tubinol(1111) catego- ries in UL Electrical Construction Materials Directory for names of manufacturers. 3. Flrestop System- Installed symmetrically on both aides of wag assembly. The hourly F and T Ratings for the f aseop system are dependant upon the type and s i rs of no nmet allic pipe or conduit, the piping system type (closed systems such as process or supply piping or vented systems such as drain, waste or vent piping) and the hourly nre rating of the wall assembly In which it Is Installed, as shown in the following table. Nom wan ' Pipe/ Pope Artnulr Piping Firs F T Condult Dlam. Space, Systam Ratitag, Rating, Raling, Type In In (a) Ik Hr fir r"PP 1/210 2 0-3/18 V 2 1 -1/2 1.1/2 FRPP, PO 1/2 to 2 "lie C 2 2 2 ADS 1/2 to 4 0-3/16 C,V 1 1 3/4 ADS 1 /2lo 4 03/16 C,V 2 1.1/2 1.1/2 PVC 11/204 0.3/16 C,V 1 I 1 PVC 1/2 to 4 0J /16 C.V 2 2 2 FRPP+ 2,1/2104 0J/16 C.V 2 1 -1/2 1 -1/2 PVC} 5, 8 0 -3/16 C.V 2 1 -1/2 1 -1/2 PI a coverlei material wrap n both Ides of wall. + p g ep regWred on pipe o s WC - closed systems. V - vented systems. The deluib of the firestop system Shan be as follows. A. Fit Vold or Cavity Materiels• -Wra Nom 1 4 in. thick intumescent slastomeric L Ser / ry P 11s- material (aced on are ilde with aluminum foil, supplied in 2 In. wide strips. Nom 2 In. wilts strips tightly wrapped irourtd nonmetallic pipe or conduit poll side exposed) with the edges butted against the Surface of the wall. Sufficient layers of wrap strip shall be It, stalled to lap a min of 3/116 Tn. on fire wall surface around the entire perimeter of the oir- outer dnotlgh opening. For norn 1/2 In. to nom 2 In. diem pipes of conduits, a min or Otto . layer of wrap strip Is required. rot nom 7-1/2 In. and nom 3 In. diem pipes, a min or two layers of wrap Strip Is required. For nom 3.1/2 In, and nom 4 In. diem pules, a min of three layers of wrap ship Is required. For nom 5 and S In. diam, two tiers (4 In. overall las0 ml of three layers of wra p strip Is required. with adjulining wrap strip layer e r edges be- Swears flows tlphl ty butted. Each layer of wrap strip to be Installed with butted seam with butted seams In successive layers sleggere& Wrap strip layers temporerHy held in posi- tion using a urnfntan fog laps, stool wire ft* cr equivalent - Minnesota Mlning lit Mfg. Co.- .Types FS.11?5. FS- 195.1- B. Steel Coffar-Nom 2 or 4 in. deep collar with 1 -1/4 in. wide by 2 fn, long anchor tabs and min 3/4 In. long labs to retain wrap strip leywit. Coils or recut 0.0 t a in. thick (No. 30 gauge) gale sheet steel available from wrap Strip manufacturer. As an alternate, collar may be field - fabricated From min 0.010 fn. thick (No. 30 gauge) gely sheet steel In accordance with Instruction sheet supplied by wrap strip manufacturer. Sleet collar. with anchor tabs bent outward 90 deg• wrapped tightly around wrap elrlp tey- e1S with miri 1 res. ovathap at the seem. With steel collar anchor tabs pressed tightly ago mat wall surface, compress collar around wrap strip layers using a min 1/2 in. wide by 0.028 in, thick: stainless steel bend clamp with worm drive tightening mechanism at the collar midhelght. As an alternate to the stainless steel band clamp, the steel collar may be compressed around nom 4 in. dram (or smaller nonmetallic pipes using two min l8 SWG (0.0025 In. diem) steel wires secured with multiple twists. Secure toner to wan surface with 3/10 In. diem steel toggle bolts (8/5 I'm or 1.114 In. grip) In conjunction with min I. 1/2 in, diem steel washers. Three bolts, Symmetrically located, required for 2 In deep stool collar for nom 1/2 In. to nom 3 in. diem pipes. Four bone, symmetrically located, required for 2 in. deep steel col• for for nom 3.1/2 and 4 In. diem pipes. Five to seven bolts (every other anchor tab) to. quired for 4 In. deep steel collar for nom 5 and 8 In. diem pipes. As a Final stop, bend retainer labs 80 deg toward pipe to lock wrap strip layers In position. C. FIR. Void or Cavity Materiels' - Caulk -- Generous bead of caulk applied to outer perima• ter of wrap strip at Interface with wan surface and to perimeter of pipe or conduit at its egress from the wrapp strip layers- , Minnesota Ming & Mfg. Ca -Types CF-25 SA. CF-29 WS. CP -28 W8, CP -25 WB +. (Nola: L Ratings apply only when Type CP -25 WB+ caulk Is used4 • - 0. Pipe Covering{Not Shown) -Nom 1 in. thick hollow cylindrical heavy density (min 3.5 W glass fiber units jacketed on the outside with an *n service Jacket. When required (see table), min 6 In, length of pipe covering Installed around PVC pipe at Its egress from stool collar on both sides of wall. Pipe covering secured to pips with steel wire lies spaced max 4 In. OC. Edge of pipe covering abutting steel collar to be sealed with a min 1/4 Fn. diem bead of caulk poem C1. Boo Pipe and Equlptitent Covering-MeterFsts PMGU) category In Building Materials DI- rectory for names of manufacturers. Any pips covering malarial meeting the above specifl. Cations and bewho; the UL Classification Marking with a Flame Spread index of 25 or Isis and a Smoke Developed Index of 50 or less may be used. r Fhanlan 0evIro• -4NOI shown) -AP on allnmRle to Items A. 0 and C for nom 1.112, 2, 3 of 4 ht. diem nonnistnllla pipes, a lllaetop device consisting of a efnaatateal split collar ilned with Intumescent material and provided whh stool clips for attachment may be used. Flrsstop device to be Installed an both sides of wall In accordance with the accompanying Installation instructions. ,. Mfnnetots Mining St Mfg, Co, -Types PPD 150, PPO 200, PPD 300, PPD 400 *Beefing the UL Classification Marking . ''' - . ' -- Design No. U914 - -. ' . Bearing Wall Rating *'3 k. - N(inbeadrig Wall Ratilig =-3 -HR. I : •). . d.. �... .., : ;. , 1 .. 2 7-1- "'. .:• .. ;. 7- 5 /,6't4IN, ;or- i '' 0: '. l�l. ,. - . ��J �_____J. 11 ..7-1.8.1. /aI . 6 - ' 1. Concrete Blocks"- Various designs. Classification: D -21 (2 hr). See of - Lttonem4e Blocks- category for the 'of, eligibtk (tantihChlrery . :" 2. Mortar- Btocks Uid in full bedrof mortar, itom 3/8 iii hick; of not less I M w than 2,1/4 and not more tharir3 -i/2 purls ctean`sharp :sand to•1 part j Portland cement (proportioned by.votume} acid -not rnoro than 50 percent hydrated time (by cement voWme). Yert(cal bints'itaggg(i!red ; 3. Furring Channels -Min O.D19 iris thiLit (25' gauge)�gat,'ttfrel, 1 -3 /Sin. wide on to� and 2 -3/4 in, wide at bottom by 7 8 in: ldeep. Spaced 24 in. . I a el 3 0 lieu ma t C n la to floor wi' i tit chap sox net aral�lto'andla . Y :'�'in.aliove floor•arid 3 in, below ceilin .'Clearance between vertical and 9 I - hotizontal channels 1/2 in. -' ' ' --= - • :: - . . 4. Channel Fasteners-1-1/4 in. ton mason -screws with 3 16 in. body / g masonry / • h the . . and :5/16 in: diameter head, fasteners spaced ,24 in. •O.C. with . fastefers staggered on each long leg of the furring channel.-- 3. Wallboard, Gypsum" -1/2 in.: thick, .4 ft wide; secured to furring channels with wallboard fasteners (Item 6 . Gypsum laster not more - ) YP P . than 1/16 in. thick may be applied to wallboard in addition to joint . txeaoment. - l • • • floral Gypsum lm-Type BG-C. - FIRE RESISTANCE RATINGS - ANSI /UL263 (MV)-- Conthwed . • - Canadian Gypsum Company - Types. C, IP -X2, t . Continental Gypsum Company -T a CG -C. . 'i . • Eagle - Gypsum Products --Type EG3.1i:.. . . G-P Gypsum Corp. -Types 5, GP,ES -C- , r-..:1 .. - -; • .. - fabco Gypsum Co. -Type PG.C. ' • . -, Republic Gypsum Co. -� RG -C; _,. -). - ,•- , Standard Gypsum.Cor. SG -C. •' = • - . .• . Templ4- Intind Forest Prodigu Cq . -Type :TP•5. • : ' i. J. United States .Gypsum Cotl- jypes. C. IP-X2. :. :. - ,.: _; c ,' sleso P4"m'erica a $1,de,CY .-Types .Cry IP -X2; i -,, - �, -r 6. Wallboard Fasteners --1 irl, fling, self. r�jlt{ttgtself -Ta Ping�fs�tcg6screws rlrith tiuglg 4eads� FaStepers attarh ltq "arils 'n �i'jnnsft _ F red 8 in. Mat bud joints and 12 in4IG- il(tthT�7In b ' pa�with fulling channeLi .ICteararlce;be�ryeen;,J #Mers_And gf.- �rallbQard 3/4 in:.., I •I -rt;v t1C!-: 42 1 h• to +tq n 2 . i2 '� .1 7. Joint ";System -(Not Rho" -Paper ,#a e hi dded� 'cemerltitious ei. 1 . compound over jointF. Paper. pe art�.gxp1> scmw hi44s co}rerid with two layers of compouf4. Edges of 6mpatmd #eat�ered.out. :i ,rl- *Beanno the UL.Classificatian. Markin .: - - - - ..... -- . , THROUGH - PENETRATION FiRESTOP SYSTEMS (XHEZ)- Continued System No. WL2005 (Formerly System No. 148) F Ratings -1 and 2 Hr T Ratings -0, 3/4, 1, 1 -1/2 and 2 Hr L Rating At Amblent -7 CFM /sq ft (See Item 3D) L Rating At 400 F -less than 1 CFM /sq ft (See Item 3D) SECTION A -A 1. Wait Assembly -The 1 or 2 Iu Itro -sated gypsum wallbowd/stud wall assembly shell he con- structed of the materials and In tit* manner described In She Individual 11.1300 or U400 Serles Wall or Partition Design in the UL fire Resistance Directory and shag include the following construction features: A. Studs -Wall training may consist of either wood studs or sisal channel studs. Wood studs to consist of nom 2 by 4 In. lumbar spaced 16 kL OC with nom 2 by 4 In. lumber and plates and cross braces. Steel studs to be min 3.6/0 In, wide by 1 -3/8 In. deep channels spaced max 24 in. OC. D. Wallboard. Gypsum' -5/8 In. thick, 4 It wide with Square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified In the lndWud U300 or U400 Series Design In the UL Fire Resistance Di- rectory. Max diem of opening is 13 -3/4 In. 2. Nonmetallic Pips--Norm 8, 8 or 10 In. diem Schedule 40 polyvinyl chloride (PVC) pipe for use In closed (Process or supply) or vented (drain. waste of vent) piping systems. One pips to be centered in the firestop system. Pipe to be Installed near center of stud cavity width and to be rigidly supported on both sides of wall. 3. Flrestop System - Installed symmetrically on boil[ sides of wall assembly. The hourly F and T Ratings for the firestop system are dependent upon the size of nonmetallic pipe and the hour- ly fire rating of the wall assembly in which It Is installed. as tabulated below: Nom Annular Wall Fire F T Pipe Space. Rating, noting, Raling, 01am, In In Hr Hr fir 9 3/4 1 1 1 8 3/4 2 2 2 8 1 1 1 3/4 a 1 2 2 1.1/2 to 1.1/2 1 1 3/4 10 111/2 2 1 314 The details of the firesto system spelt be as fanows. A Stool Slsevs- 4Cylind ical sleeve fabricated from min 0.018 Fn. thick (No. 30 gauge) galv sheet steel and having a min 1 In. lap along the longitudinal seam. Length of stool sleeve shag be equal to thickness of well plus 9.1/2 In. 101n. or 11 Fn. for the 8, s and 10 In. diem pipe sizes, respectively. Inside diem of steer sleeve and diem of through opening In the gypsum wallboard layers to be equal to outside diem of wrap ship ((tam B) layers on pipe. Cylindrical sleeve Inserted In annular space around nonmetallic pips and cantered in wall. After installation of wrap strip iftem 0) layers, min 1/2 In. wide by min 0.028 In. thick stainless steel band clamps Installed around steel collar on both sides of wall assem. bly with am band clamp located near the wall surface and another located approx 1 In. from the outer sdgga of the wrap ship layers. Edges of steel sleeve to be slit approx i In. OC around cireumlerence of sleeve on both aides of wen, with length of slits approximate. ly equal to thickness of mat wrap layers, to form retainer labs. Retainer tabs bent 00 deg toward pipe to lock wrap strip layette) In position. B. Fill, Vold or Cavity Materiels• -Wrap Strip -Nom 1/4 In. thick infumescent alastomerlc material faced on one side with aluminum fop, supplied In 4 In. wide by 24 in. long strips. Nom 4 In, wide wrap strips tightly - wrapped around nonmetallic pipe on each side of wall and and Into steel sleeve (Item A) such that inner edges are flush with or recessed max I/ 4 In. Into surface of wall. For nom 8 In. dram pipes, three layers of wrap strip are is. quilted. For nom 8 In. diem pipes, four layers of wrap strip are required. For nom 10 In. diem pipes, six layers of wrap itrlp are required. Each fever of wrap strip to be installed with butted seams, with the butted seams in successive layers staggered. Wrap strips tent literality held In position using aluminum foil tape, filamOnt laps, stall wire da, or equiva. lent. Minnesota Mining d Mfg. Co. -Types FS -195, FS -196+ C. Pipe Ccverin ' -No m 1 in. thick hollow cylindrical heavy dorsally (min 3.5 tie f glees fiber volts jacketed n I o the outside with art s# service jacket. M- i 1 j et m 6 in. length of pips covering Installed hound PVC pipe at its egress from the wrap strip layers Clem h) on both sides o f It's wait. covering secured l o 1 o with ,test of pipe covering abutting wrap strip to be sealed with la min 1 /4cIn. diem bead of'caulk Post" 01 Sea Pips And Equipment Covering -Ma tot Isis (BRGU) category In the Building Materials Directory for names of manufacturers. Any 'pipe covering material meeting the above speo- IRcalTons'end bearing the UL Classification Marking with a Plants Spread Index of 25 or less and a Smoke Developed P ed Index of 50 or less may o be used. D. Fill Vold or Cavity Metollats•- Caulk- Generous bead of caulk to be applied to outer perimeter, or steel sleeve at Interface with wan surfaces and to perimeter or pipe covering material wrap at its Interface with the wrap strip layers. Minnesota Mining & Mrg. Co. -Types CP -25 S/t• CP -25 N /S, CP -25 W8, CP -25 WB -I , (Note: L netings apply only when Type CP -25 W0+ caulk is used.) 'Dearing the UL Clesshlestion Marking Warnock Hersey _AMiff � ® TUPV - 120 -01 2 Hour Fire Rated Joints for Concrete Steel Fluted Decks to Gypsum Wall Assemblies using TREMstop Acrylic. . . Drawing not to scale ( AA) Pre -Rated Concrete Fluted Steel Deck: Min. 2 -1 12a Thickness. B) Pre -Rated Gypsum Wallboard/Stud Wall Assembly. C) Continuous Steel Stud - Galvanized Stool Runners. Max. Joint Width = 3 -518". I 4 Packing Material - Full depth of mineral wool insulation (min. 3.5 pcf) is installed into joint. Packing Material must also be installed into the steel flutes of deck. 30 TREMstop Acrylic - Min. 1/2" thickness of sealant applied within opening, flush with both surfaces of the wall assembly. . The alcove described assembly and products have been tested and are based on bolb past and anticipated performance criteria. Tremco shalt not be Gable for any damagos, direct or consequential, resulting from use of this material or design. Tremco shall only be responsible for roplacing material found to be defective. FLOE 147 MEMO ``pttlJJre i or 2 Hour Fire Rated Joints for Concrete Floors and Gypsum Walls ®� using TREMstop Acrylic. aroma HWD0016 - Movement Capabilities= 25% Compression Drawing not to scale 10 A) Pre -Rated Concrete Floor: Min. 4 -1/2 "Thickness B) Pre -Rated Gypsum Wallboard /Stud Wall Assembly Y C) Steel Floor and Ceiling Runners - Min. 28 gauge gals. steel channels mechanically fastened to the lower Surface of the floor assembly. I Max. Joint Width = 1 ". Q Packing Material - For 1 Hr. F- Rating: Install Bond Breaker Tape prior to applying sealant. For 2 Hr. F- Rating: Install 2 layers of 718" diam. polyurethane backer rod. I 13 TREMstop Acrylic - Min. 112" thickness of sealant applied within opening, i�f) P r 9 flush with both surfaces of the wall assembly. I The above described assorrhly and products have been tested and are hasad on both flttst and anticipated performance criteria. Tremco shall not he liable for any damages, dlreci or consequential, resulting train use of this material or design. lierrico shall only be responsible for replacing material found 1a ba defedjvu. '40E 137 1 MEMO �, pt Sr!!f, U� " "I., HW51004 2 Hour Fire Rated Joint,- - -: _ -: - - - - -- - for Concrete Floors and Walls - _ ; . using DYMERIC. - - - - - - - - _ _ _ - �l;rwing Get to scalK ^ ^ ^ ^ - - - 10 A) Pre -Rated Concrete Floor: Min, 4 -1/2" Thickness B) Pre -Rated Concrete or Block Wall: Min. 4 -112" Thickness. Max.Joint Width = 3 ". 2O Packing Material - Min. 3 -112" mineral wool insulation (min. 5.0 pcf) firmly packed into opening as a permanent form. Q DYMERIC -Min. 1/2' thickness of sealant applied within opening, flush with both surfaces of the wall assembly. The above described assembly and products have been tested and are based'on bell] past and anticipated performance criteria. Tremim shall not be gable for any damages, direct or conserinentiett, resulting from use or [his material Or design• i)errico shall only be responsible for teptacing material found to be defective. �ryyy E &OE 138 /i7I wCo. 1,1301 2 Hour Fire Rated Through f enetration *-'wo FIRE RESISTANCE RAnNGs - ANSI/1.11253 (BXUy)- [opined Firestop for Single Plastic Pipe through Third In W- 2 -1 4 In. tart In I^on 1/ nds s nd 24 in Y- / .thick a P-114, w a Non Beard Walt Ratings-1, - Ra s 1 2 r Bearing , 3 0 < Hr See Item < 9 Items Concrete Walls using • . FYRE -CAN SLEEVE. WJ2017 F - rating = 2 Hr. so. t"ie� tI n.Ual• �- T - rating = 1 fir. Drawing not to scale (D Pre -Rated Concrete or Concrete Block Wail Assembly - Min. 4-1/2" thickness. 0 Plastic Pipe - Nom. 3" diam. (or smaller) Sch, 40 PVC pipe for use in open or closed piping systems. - Nam. 3e diam (or smaller) SDR17 CPVC pipe for use in closed piping systems. 03 FYRE -CAN SLEEVE - Intumescent device installed around pipe and lightened with a hose clamp. Prior to installation, the concrete wall is notched on one side to allow Insertion of the device with the hose clamp Into the opening. See table below for system specifics: Nom. Pipe Dinim, of Annular Space Diem. fin.) Device SIwe . , o(>ening (1n.1 1110 1 -1/2 TS1.5 3 9116 2 TS2 3.1/2 9116 3 TS3 4-W4 5/8 9) TREMstop WBM - Min, 1/4" bead of sealant applied at the wall /device and pipe /device interfaces. Additional sealant is applied to fill the notch created for the hose clamp to a min. depth of 1 ". The above described assembly and products have been lesied and are based on both past and antkipaled performance eriterla.Tionsco shall not he liable lot any damages, direct or consequential, resunhng from use of Ibis material or design.'Remoo shall only be responsible for repladng material found to be defective. 56 E &OE 696 FIRE RESISTANCE DIRECTORY retain rill[ ASSISTANCE DIRECTORY (t %rq FIRE RESISTANCE RATINGS - ANSVM63 (BXuvt _ Continued FIRE RESISTANCE RAnNGs - ANSI/1.11253 (BXUy)- [opined ' Design No. U 41i a Third In W- 2 -1 4 In. tart In I^on 1/ nds s nd 24 in Y- / .thick a P-114, w a Non Beard Walt Ratings-1, - Ra s 1 2 r Bearing , 3 0 < Hr See Item < 9 Items Eau Il�amw rth • 2•s In. tong for 1 A t n. thkk . D+c 9 1/ s ed 1i In. D nett o< Sans o/fset min 61n • . 6. rent' Olarn.ls-(Optsuna nr shown, hx rVgie or doubte um turfing Pus Namk.r or I+r•n 4 sysmsu)�Ra,, chanwts hbncned iron nip 25 XSG corso i - pmtecbd suet spapd wnk]ay a maw of 2< In. OC. Nnge s attached to rack Inters" �^9 so. t"ie� tI n.Ual• �- smd with 1/2 in. Long Type S-12 panr.ad sled stmR. I - - 7. latest U ad M- N Csmpw d nsein d r I: ed ry of compoud applied m two cam to)))oirds and sc.w heads of oouta l•1'fri _ ? -- Pap-U non 2I& ooh, embedded tit first 1,, r f nmpowd -,a I __ - - )amts d ruts panels a Sfeaq, trkir sir Stuae-(00WA not shown) - Alminue, vinyl m =_Oed sling, brkk cancer et my ,1 neebng too rag I_ts d teal , U3A • 2 -•'� Eck; a d y In panels. ed3 cancer attathed to �paH .L X nmg q had to exA ! teal with steal 7 - 4 ' edit cauot b - ' O'saewt•nat d S41A1lnlath )-- 9' WW,it, pU S-nd the flat sMwn) -A bead of roaustkal s anent appBed arouM the pnitmn pesimew for souM cornraL 7. Fmr aM [nUng Runr,an -(Not shown) - Channel shaped, hbricated floor stn 25 A% taroston-pntected steel, min wdth m a nodata Umnd State eypsuw Cw -Typo AS *11-in too UL C="F1oty- Narking shd ma, w" mn 1 in. long legs, attxArd m floor and cetbnq wnh fxtm 24 Im OC saw. - Z. Sent Studs -Ch. .l shap.4 hbriotsd from min 25 MSG cononoo• as Indicated render Item 4, pin 1-1/4 M. r,rca W 1m•I/i sit. nan9es - - I - aastatl No. 0420 M s paced a.o b 24 m. K. Smds m W cut 3/8 to 3/4 in. less than assembly height. Nonbearing Wall Rating -1 or 2 HR. ' 1 tans and IhNrem•- (Rpuirsd as NdkatM under Item <) -Nnaal wool Wry hicUon Rued bdreen studs and .nacre Min roes thickness 1- ,lac -., zt•.< -, as tMxated under Item 4. Set Rata and alankeb (81(1111 s 82.12) AmTdas fr Nnes at Classified compulws, 3A. fleas and Ilaa4o•- (DpUonaq -eland In smd cavities, aml qua fits- r -'--I wool mutation b-11r-q9 Ore UL CLtsi r - ic.tbn "arNsg m to Surtace Burning Chanel -sties sd/r RA Rmistmm See Brb aM . a Bhnkab (BKNV r 827 CateBo "es far NwS of Elamfied companies. Ime¢arrttC s M., ' <. YralUNrd, 6y,sm• -Gr:- r.ta with bevel"& sguan r hDned nand filed verticaW' or korfmrralke YertkM kiKS centered osn studs one stud ovd, ns op,*dta sdn of wAL vatkat .1..0 I briay"a�e MlUrbi:oW butt tipped aN stud nrnY c .ii' -- ---• - s '. Tee nW Is scads sng I. .min of 12 iz IkaixsWl• oppoum sides a tdra Joints and hoAmnbl butt pkas M adlanm (ryas tmultRaye sysU- adoer� a ,des of 12 in TIN thfdmess and hC Is . ' v."M C sECI- ' Innahar of I+Y•rs far too 1 l li , 3 hr aM 4 M rabngs - r (allows: .. �B- •CAanNt-- shsped 1 S/8 m. ooh anti 131 In.==,.. stiaaim, ftablim Fop lusted from No. 15 M5G pal stte '114 . abebeaed Pr6matke w rid Ski of wall .. ' a. Of Le-E MM Thkk- Rk SW ' AM 7-Anm Of I -U". In. Iris NM Ps - I beight. .- - t. tdo typed rype T:14 ft- too etM -,, R 1%2 in. 1�e�mJ asteded m tW sods -Xh fwd Xo.; by t/Z In. seH- drlWnq. Bally MP& M1ama (lam 75) 1 - 3- In'''' 1 Is^ 5/1 m thr6 C,,i.,d :- ..- ^" -�pt14 sted satws kr ndr stud. Typo 1-Cui hem the gypw -Uboad a to In. tong aM 1! i...Id.. Fastened m the usds MCr lso, 1 2 -1n 1 Isy-, 1/t 1. thid - 1 -1/2 irr U••• Type S waUWard acrtws at ed. Vwtkal Val g d bradnq not m curse N m. OL t - 13n : 2 L-sem 1/2 in. tkkk 2 1-5n 2lsyas, s/r in. thld "' p grs'ul,l ' 2 3-712 2• Flar w E•Nn Wen4 s -GaR M-sWpd 7 sro In. rule" th 1 in legs, rapkaW No. zs N568alesmy, AttacMd m ft- .,.d .Wes .., . , 1 l y-, 3/4 K thick . 31. -, 3 1 -5/8 . - 3 tsym. In in. thick Opti..i 1 . 1 -Sn. 2layers; 3/4 e. Urkk_. �, Optional . 4 3-S?e - 4 by.,; 1/2 io. thkk ' , <• spred 14 In. OL . 4 . .y6( -My 5/8 In. Oft - 11board for he efinance f � -"" W-•' - nT'ed adTt' optknd' 4 2 -tn, a 't 2 WYers. 3/4 in. thief '' • • 21n. -' ,. NW,- - stamp --0nfl d wsUbmd m W'i ll& Aaplir.Vir .Uy Ustathe kypw,r(o.; 1/2(n thkk�,TpyT� C 7 a IP42: 5/8 m. T ui. - w'Rh iwna nn Wd der studs. Fasnned m aids with 1 In. Iona Type 'S Wnd screws SWal B n OC At theJolyds bated 3/6 In. tme too -41. - = , wRCAC IP42. 3/4 M. -' ' mlthdt d T adgq W 12 In. a In the Md. FnMrn m be spaced B In. OC at the tilted St . =. Cw -fn k. LAid� type E:' flit`- tP•%2: - " 5/8 k. tMck TYPO Sat• Sal%, VR%, IP•z1, AR, C, WIC or IHC1: 3/4 ' for 2 W Wa , -Two tayen of .AbW d m be use& The inn- lay- m W appled to the umt, - W n Ox the 1 W using. T W outw Jaya m •7 irC thkk IxT.*OOE at Type 1P•X3 r. '. ,y.6 hNSartoao SA do N -1/2 m thkk TyypC. Witt rIP•%2. ..' "s/B1n.Onek ffyyppsaSal, Ste, wRx IFtkt, AR, C INK rtPJQ: 3/4 �, W hawed tq fM studs (t1notIqh U. inner uyw) uslry 1 SA N. mne, Type-; iEaubowd•scsews3paw4 J M -Oe n -IM 1oNts, WC4Qd,3A,%. *ter Arrlz•E2 fs-OC *too 6ai& - --ti I—— •'. k, tics ULTRACO11 a k" IPd3. .: �. t i S-It stU -0nLLNG sep•nppkst steel 5'u.wsr ,edges lfast -sys Ialtk a In: ax,tM mnrrrs,,loOrh m ha aagge%d 24 .,y',1nt.�101 Fla�j1 f.-��._t+� - -.T -•M mII a�Wd")-"TYMSw pMk m sods plan 2) r fuMnq c W..0 (Its. 6). Sinplt ur•r systaes S In. mry' 112 :, =.r _" Sw wdea. GGovia OIa) atysy for Mmes of nanufa- ctu-mi. t and5/p ta.thks panels r 1-1/4 M. long fqr 3/4* till paM1s, send i kI. QC.he. p.NU an applied 12 ti, Of 46,:trdlb-14 GyBture• -ills dn•almnata m ltes <) --Now 1/< Ica prid. trubSid a dwasbd In9tYF < "hit' 1- 1 /4In. lay Typt 5 craws I. m wits palls - AlW y -trolly 1we Mlrya,sJsStsl n•RrOs 1 in. mpg for -1/2 aM S/a In: till parcls r In I-I Ir 3 4 I, thick 16I& OL Swond a aN,gld (rirsr) Irfa aM 2 -1/4 kc lone Type S screws kr aunts IyEr -. -.1 UaWke ypaae Cas,sy +TYW A0. , week speed laYw- 1 -5/8 Fn. long for 112 in. thick W Mk r 2.1/41.. tang for 3/4 Vr, thick p:alb, spaced 16 - OC .Ith soon oeset 8 In. how first layer =W Shbu GYPeum Cw -Typo AR. Yns Paaasetoae SA C Ir W A AR. rkrE6•fayr sYSteena Rrst by -- 1 m I•^9 fr 1/2 In. thkk panels, 4a wallbord, 4ypws� -+(As s aNerMCe to Item ! aM M) -5 /B w. thkt klshl4d as, dncrlbtl In S, spaced 24 in. OL SecoM layer- f -Sn in, long fr 1 /21n, thick puts, spaced ri 1n. OL Thib layer- z -1/4 M. Loy (or 112 in. ttrkk pock _. .Item .Tolnt covannp (lull 5) rot ,c "Bided fr -^ layr.s,ems. .• :b." .. Uaadis Gypsam T wax sp -ed I2 in. OL Xrews octet mn 6 In. hem hues halo. Four -lawn syrmmc Rrst lay- -1 in. Irq fr 1n m. thkk parWs, spend 241n. OL . IAHed StaW Grptum ee. -Tye w9L Ynw SA dew S-mM (aye- 1 -sro In. mesa fr 1R in thkk oanNa �aamarinre -T - __ _., ... - -- -- - ..,p'�'L �� . architect NORBERTO ROSENSTEIN ARCHITECT , INC. AFO GL 1 M - n FM LJGs71ki\ - RAM I 126 S. FEDERAL HIGHWAY SUITE # 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 FAX: (954) 922 -7388 EMAIL -info�rosensteinarchdect.com WED WW osensteinarchitectecom STATE j EG. NO. AR0016674 NATL. REG. NO. 69178 COPYRIGHT © 2008 NORBERTOi ROSENSTEIN ARCHITECT, INC. ALL RIGHTS RESERVED. THIS DOCUMENT OR PARTS THEREOF, MAY NOT BE REPRODUCED IN ANY'FORM NATHOUT PERMiS ;ION. /, ` r DESIGNED v, J, t Q � V 1. - V.> � N.R. `-� r y "- :•� i - DRAWN ' W' ` J.G. ' a �� a:, CHECKED 4 /►�,��31 it ... * N.R. ,e .••- �A��% II0iIIIt1111••. I HEREBY C RTIFY THAT THESE PLANS WHERE PRE ARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNO%WLEDGE, COMPLY WITH ALL APPLICABLE CODES. 3 11-3-4011 OWNER REVISION t)2 10- 172011 OWNER REVISION 10 -4 -2011 BLDG DEPT COMMENTS 0 t R E 1V I S 10 N S COMM. DATE 2011 -37 8/17/2011 5701 SUNSET DR SUITE A15A WHITEI BOX SOUTH MIAMI FLORIDA, 3 143 FIRESTOPPING & UL DETAILS A-6 El a -6 ____