Loading...
14-88-033GENERAL PLUMBING NOTES: 1. A. ALL WORK SHALL BE DONE in accordance with the Florida Building Code 2010 and with all applicable regulations. B. DRAWINGS: Refer to all drawings for coordination of the plumbing work. C. ARRANGE AND PAY for all permits, licenses, inspections and tests. Obtain the required certificates and present to owner. D. GUARANTEE: The completed installation shall be fully guaranteed against defective materials and /or improper workmanship for a minimum of one year for material and labor. E. ALL HORIZONTAL SANITARY PIPING 3" and larger shall slope at 1/8 inch per foot minimum, unless noted otherwise. per foot minimum, unless noted otherwise. All piping 2" and smaller shall slope at 1/4 "inch per foot minimum. 2. SHOP DRAWINGS: Contractor shall submit for approval, within 30 days of signing contract, a minimum of five copies of fully descriptive literature, including but not limited to: water heaters, and plumbing fixtures. No work shall proceed without the approval of these submittals. 3. PLUMBING FIXTURES: Fixtures shall be as specified and shall be furnished and installed by this contractor. Fixtures shall be complete with drains, traps, supplies and any other accessory required. 4. MATERIALS: A. PIPING: a. Soil, waste and vent, above ground: Cast -Iron Soil Pipe, no hub fittings with S.S clamps & rubber gaskets. b. Domestic water. Copper pipe, Type L with sweat wrought copper fittings. Type M" in concealed spaces is acceptable. Isolate piping from concrete with insulating material. c. Condensate drain: DWV Copper pipe and fittings. d. P & T Relief and Drain Pan lines: DWV Copper pipe and ftgs. e. Domestic water supply assembly. Chrome finish tubing with angle shut off valves. 5. ALL AUTOMATIC ELECTRIC water heaters shall meet the standards of the latest state energy efficiency code. 6. PIPING TEST AND DISINFECTION& A. Test: All sanitary and domestic water supply piping shall be tested for leaks before piping is concealed or connected to equipment and plumbing fixtures. B. Disinfection: All domestic water piping shall be disinfected by introducing a solution of calcium hypochlorite of 50 parts per million of chloride and as per AWWA Standards. 7. VALVES: Domestic water valves shall be of bronze body, sweat ends. 8. HOSE BIBBS: Shall be 1/2 inch. rough brass construction with shut off valve and vacuum breaker. 9. ALL OUTDOORS FLOOR clean outs shall be terminated up to grade and shall be marked. 10. CONTRACTOR SHALL COORDINATE exact location of sanitary, storm and domestic water piping before starting any work. Notify Architect/Engineer of any deviations from design drawings. 11. FIRE EXTINGUISHER: Potter Roemer, Inc., Fig. No. 3005, 5 lbs. UA rating 2A: 10b: C 12. CLEANOUTS: A. Wall: Josam 58890 -15 B. Finished Floor Josam 56020 -88 -15 13. CONTRACTOR to fire protect and seal all openings and pipe penetrations thru fire rated walls and ceiling. Materials and methods of fire rating shall be approved by the local product control aproval department and shall be U.L. listed. 14. PROVIDE CEILING /WALL ACCESS DOORS where indicated on drawings and when required to access mechanical equipment. Doors shall be recessed type, fire rated if in fire rated wall or ceilings. As manufactured by Karp model RDW and KATR. 15. PLUMBING CONTRACTOR SHALL review structural drawings prior to bidding to fully familiarize himself with project. 16. SAW OR CUT CORE DRILL slab as required to install new plumbing work. Patch slab to match existing and seal all penetrations to maintain fire rating of floor. COVER SECURED WITH SCREWS THREADED C.O. PLUG C \1 ^M AMl 4 X 6" DIA. CONCRETE PAD FLUSH W /FIN. GRADE EXTERIOR TYPE SLIP JOINT EXISTING MAIN BLDG. S.0 VALVE. CONTRACTOR TO VERIFY EXACT LOCATION BEFORE JOB COMMENCEMENT. XX EXIST. 6K TO EXISTING REMAIN AS IS. 1/2 "HB. O O O O EXISTING KITCHEN NIC I EXISTING BEDROOM NIC REF. EXISTING MAIN BLDG. S.0 VALVE. CONTRACTOR TO VERIFY EXACT LOCATION BEFORE JOB COMMENCEMENT. EXISTING DINING EXIST. b& TO W/D REMAIN AS IS. I COMBO ! i i ! t ! EXISTING 3/4 "(13.9wsfu) DOMESTIC OCCUPANCY WATER LINE OTHERWISE, IT SHALL t BE PROVIDE AS SHOWN. X EXISTING WATER METER. HOT EXACT LOCATION TO BE U VERIFY BY CONTRACTOR. ADJUSTABLE COLLAR THREADED C.O. PLUG FIN. FLOOR -7 FLOOR TYPICAL CLEANOUT DETAIL N.T.S. WALL CL. A/C EXISTING BEDROOM NIC NEW COOG (2WAY) TO NEW SEPTIC \-EXISTING 4"(21FU) TANK SYSTEM BLDG DRAIN. 0 i0- 3 "ViR �I�V EXISTING 4 "(33FU) JI BLDG DRAIN. 3. 3 "(2FU) NOTE: • ALL HORIZONTAL DRAIN PIPE 3 "0 OR SMALLER SHALL BE SLOPED AT 1 /4 "/FT • ALL HORIZONTAL DRAIN PIPE 4 "0 OR LARGER SHALL BE SLOPED AT 1 /8 "/FT. MIN. �1 � 3/4 w 2 • (2FU) TIE -IN TO EXISTING 3/4" CW � \ & HW LINE. VERIFY POINT \ OF CONNECTION BEFORE JOB COMMENCEMENT. - -/ � WATER HAMMER SANITARY PIPING ISOMETRIC - NTS ,-____1I1_� x <, < ARRESTOR (TYP.) TIE -IN TO EXIS G 3/4" CW ONE STORY & HW LINE. VERI POINT EXISTING MAIN BLDG. S.0 RESIDENCE OF CONNECTION B ORE JOB I EXISTING 3/4"(13.9wsfu) DOMESTIC VALVE. CONTRACTOR TO , CO E NCNENT. -r - - - -, BEFORE JOB COMMENCEMENT. I I # 4301 - - WATER LINE. OTHERWISE, IT SHALL VERIFY EXACT LOCATION BE PROVIDE AS SHOWN. 1000 Sq.ft. t- - o - -- - - - -� EXISTING CLOSET � LAY t- - 0. -- - -- - - - 3/4• EXISTING WATER METER. LAY 3/4* EXIST. BA -.I ' EXIST. 4 '(11FU) EXACT LOCATION TO BE ' " I VERIFY BY CONTRACTOR. / 1/2 H.B EXISTING BATHROOM i @lIZIL FIXTURES TO REMAIN AS I TIE -IN TO EXISTIN AN. 1/2w IS. OUT SCOPE OF WORK I LINE. VERIFY EXAC PONT OF WIC I�' I 3/4" CONNECTION AND IN&Rr EXISTING LIVING I BEFORE JOB COM CE ENT. NIC 1/Y -- -- - - - - -- -- LAV / 1 /2 "H.B �-- - - - - - - SWATER PIPING ISOMETRIC - NTS - - New, ddition NEW fi4HROOM 400 sq.ft. // / LAV NEW REDR OM EXISTING C DECK MATCH EXISTING HO LSE FINISH FLOOR FACE OF WALL STAINLESS STEEL COVER SCREWED TO THREADED C.O. PLUG. NEW COOG (2WAY) 1 `NEW 4 "(21FU) BLDG REFER TO PLUMBING DRAIN. SITE PLAN FOR CONTINUATION. ,,AI- PLUMBING FLOOR PLAN. ® SCALE: 1/4" =1' -0" SECTION E103.3 WATER LOAD VALUES FIXTURES CALCULATION AS PER FLORIDA BUILDING CODE 2010 FIXTURES OCCUPANCY TYPE OF SUPPLY CONTROL LOAD VALUES, IN WATER SUPPLY FIXTURES UNITS (wsfu) TOTAL GROUPS OR FIXTURES TOTAL TOTAL COLD HOT TOTAL FULL BATHROOM GROUP PRIVATE FLUSH TANK 2.6 1.5 3.6 1 3.6 KITCHEN GROUP PRIVATE FAUCET 1.0 1.9 2.5 1 2.5 WASHER PRIVATE AUTOMATIC 1.0 1.0 1.4 1 1.4 KITCHEN SINK 11/2- 1/2" 1/2" PROVIDE 1.5 GPM FAUCET SK -1 KITCHEN SINK 11/2' FE WATER CLOSET PRIVATE FLUSH TANK 2.2 - -- 2.2 1 2.2 m LAVATORY BIDET PRIVATE PRIVATE FAUCET MIX. VALVE 0.5 1.0 0.5 1.0 0.7 1.4 2 1 1.4 1,4 m TUB PRIVATE MIX. VALVE 1.0 1.0 1.4 1 1.4 TOTAL WSFU 13,9 NOTE: EXISTING FIXTURE FOR REFERENCE, ONLY FOR LOAD VALUE TO FIXTURES. NOT IN SCOPE OF WORK. WC BIDET TUB MAXIMUM DISTANCE FROM FIXTURES TRAP TO VENT SIZE OF TRAP (inches) SIZE OF FIXTURE DRAIN (inches) SLOPE (inch per foot) DISTANCE FROM TRAP (feet) 1 1/4 1 1/4 1/4 3 1/2 1 1/4 1 1/2 1/4 5 1 1/2 1 1/2 1/4 5 1 1/2 2 1/4 6 2 2 1/4 6 3 3 1/8 10 4 1 4 1/8 12 For SI: 1 inch = 25.4 mm,1 foot = 304.8 mm, 1 inch per foot = 83.3 mm /m. NOTE: EACH FIXTURE TRAP SHALL HAVE A PROTECTING VENT LOCATED SO THAT THE SLOPE AND -RiE DEVELOPED LENGTH IN THE FIXTURE DRAIN FROM THE TRAP WEIR TO THE VENT nTTING ARE WITHIN THE REQUIREMENTS SET FORTH IN TABLE 906.1. FBCP PLUMBING FIXTURE C❑NNECTI ❑N SCHEDULE NO, DESCRIPTION DRAIN WATER REMARKS COLD HOT WC WATER CLOSET - 3" 1/2" - -- FLUSH TANK, 1.28 GPF LAV LAVATORY (COUNTER TYPE) 11/2- 1/2" 1/2" PROVIDE 0.5 GPM FAUCET SH SHOWER (NOTE 1) 2" 3/4" 3/4" BASIN BY ARCH. (PROVIDE 1.5 GPM SHOWERHEAD) BIDD BIDET 2" 3/4" 3/4" BY OWNER SK KITCHEN SINK 11/2- 1/2" 1/2" PROVIDE 1.5 GPM FAUCET SK -1 KITCHEN SINK 11/2' 1/2" 1/2" PROVIDE 1.5 GPM FAUCET REF REFRIGERATOR ___ 1/200 ___ PROVIDE ICE MAKER KIT W CLOTHES WASHER 2" 1/2" 1/2" BY OWNER, PROVIDE RECESSED BOX, GUY GREY T200 OR EQUAL DW DISHWASHER 1" IND ___ 1/2' - -- H.B. HOSE BIBB - -- 1/2" ___ WITH S.O.V. AND VACUUM BREAKER 1/2"RECESSED WALL HYDRANT - -- 1/2" ___ WITH S.O.V. AND VACUUM BREAKER NOTES: 1. ALL SHOWER HEADS SHALL BE OF THE ANTI- SCALD, PRESSURE BALANCE TYPE. 2. ALL FIXTURES SHALL COMPLY WITH THE FLORIDA BUILDING CODE WATER CONSERVATION STANDARDS. 3. ALL PLUMBING FIXTURES, FIXTURES FITTING AND APPLIANCES FOR NEW OR SUBSTANTIALLY RESIDENTIAL AND COMMERCIAL STRUCTURES SHALL INCLUDE HIGH EFFICIENCY PLUMBING FIXTURES, FIXTURE FITTING AND APPLIANCES AS PROVIDE IN TABLE 604.4 OF SECTION 8 -31 OF THE CODE OF MIAMI -DADE COUNTY. (W.0 1.28 gpf, LAV 0.5 gpm 0 60 psi INLET, SH HEAD 1.5 gpm, KIT FAUCETS 1.5 gpm 0 60 psi INLET.) .,F££iJ4 lif'!iJ'4!:.,, ;,•••�•- `!�`£1zi ,c i'j l; is °'£I! � [;! i�'I}: �` Eil.ili. I if if .I r � Ji� V£ !' '�! ✓J %� , }£I" Ili }% ,, , 4t If (€ , }(i IE. � }; 3,; !,t .: , . { , z .. 3 }i ��. 3 3 ! ;! i' {• i:R.+ a Q1 .4 we O f- Q if ti LLJ r V) < .4 175 FOUNTAINEBLEAU BLVD. STE. 2-G MIAMI, FLORIDA 33172. PH: 305 -277 -7165 FAX: 305 - 229 -3839 A.SANTANA ARCHITECTURE ASSOCIATE ,• U * NO.20233 E -� STATE OF c 1VAL�E� i '{+T *.;,.£T 1:K> at. R,G• +T, +::.'.>i' :k--, ,• ,�,C A^•aJ.'�.0 ,r ^.' :.[thATT;xtiS A ✓r :R1'x;.. "^.,kT1:T' ct:, %<.'CF i4J k.Y„ ?{ "Aa7V T'�% .'+;C ✓!'<TY C'- R' t :>;t *f, tS` - - <x "'h. *X:1• "AW 'vC''T.T ('s 1, �.3 :41h"*'Y;J4 "t CY f. "•<.4 �jf ti, ;A, r'c:*,c: ,<. •thxi.`.`• ',it ".ti. J,,; 'SIT )"T�f ?.T "w p'F,g4, !:T • �l� Y"YYMY,YYYwYww"wll 1 SHEET ` P=2 SHEET of- ',r we O f- Q ti LLJ r V) < O O a -o liez Y ~ Z w � U 175 FOUNTAINEBLEAU BLVD. STE. 2-G MIAMI, FLORIDA 33172. PH: 305 -277 -7165 FAX: 305 - 229 -3839 A.SANTANA ARCHITECTURE ASSOCIATE ,• U * NO.20233 E -� STATE OF c 1VAL�E� i '{+T *.;,.£T 1:K> at. R,G• +T, +::.'.>i' :k--, ,• ,�,C A^•aJ.'�.0 ,r ^.' :.[thATT;xtiS A ✓r :R1'x;.. "^.,kT1:T' ct:, %<.'CF i4J k.Y„ ?{ "Aa7V T'�% .'+;C ✓!'<TY C'- R' t :>;t *f, tS` - - <x "'h. *X:1• "AW 'vC''T.T ('s 1, �.3 :41h"*'Y;J4 "t CY f. "•<.4 �jf ti, ;A, r'c:*,c: ,<. •thxi.`.`• ',it ".ti. J,,; 'SIT )"T�f ?.T "w p'F,g4, !:T • �l� Y"YYMY,YYYwYww"wll 1 SHEET ` P=2 SHEET of- ',r