Loading...
14-88-027Residential Cooling and Heating Load Calculations Based on ASHRAE Cooling & Heating Load Calculation Manual. Second Edition. Unit/ Area served: EXIST. AHU -1 (3.5TNS) Job Name: Date: Calculated by: Checked by: �Summer design: 91.0' F Summer Coincident W.B.: 77.0 ° F (Summer Daily range.: 11.0 ° F Data Source 2001 ASHRAE Hand Book _ ADDITION AREA 4301 SW 60th PLACE Miami, Fl 01/17/14 A.S. A.S. ITEM SOLAR 1.1 SHADE T. AREA BTU/HR ITEM LT 6.9 U T. AREA BTU/HR N. Glass 37 x x 30 = 1110 N. Wall 14 x 0.2 x; 390 = 1092.0 NE. Glass 66 x x 0 = 0 NE. Wall 20 x 0.2 x 0 = 0.0 E. Glass 91 x x' 60 = 5460 E. Wall 24 x 0.2 x` 380 = 1824.0 SE. Glass 82 x x 0 = 0 SE. Wall 22 x 0.2 x 0 = 0.0 S. Glass 56 x x' 30 = 1680 S. Wall 17 x 0.2 x, 390 = 1326.0 SW. Glass 82 x x 0 = 0 SW. Wall 22 x 0.2 x 0 = 0.0 W. Glass 91 x x; 66 = 6006 W. Wall 24 x 0.2 x. 374 = 1795.2 NW. Glass 66 x x 0 = 0 NW. Wall 22 x 0.2 x 0 = 0.0 Hor. Glass x x = 0 Knee wall x x = 0.0 T. Glass area = 186 Subtotal = 14256 T. Wall Area= 1534 Subtotal = 6037 ITEM LT U T. AREA BTU/HR ITEM BTU/Unit TOTAL BTU/HR Partition 13 x 0.09 x' 0 = 0.0 People 230 x 4 = 920 Roof 48 x 0.09 x! 1425 = 6156.0 Kitchen 1200 x: 0 = 0 Floor 13 x 0.09 x 1425 = 1667.3 Infil./Vent. = 1.1xQxDT = 96.9 x 16.5 = 1598.9 Ceiling x x = 0.0 Miscellaneous = 800.0 Subtotal = 7823 Subtotal = 3319 TOTAL SENS. GRAND TOTAL HEAT LOSS ITEM Walls Roof Floor Glass Ventilation= 1.1xDTxQ= Partition TOTAL KW = 31435 Btu/Hr = 40866 Btu/Hr (TOTAL SENSIBLE.+ LATENT) MAX. ALLOWED PER UNIT 1.15 % = 46995.77 Btu/Hr TONS = 3.4 USE _` 3.5 Tons T. AREA LT U BTU/HR Cfm 1400 1534 x 27 x 0.2 = 8283.6 Sq.Ft./T = 407.1 1425 x 27 x 0.09 = 3462.8 CFM /sq.ft = 1.0 1425 x 27 186 x 27 1.1 x 27 0 x 27 23611.2 Btu/hr 6.9 Kw x 0.09 = 3462.8 x 1.1 = 5524.2 x 96.9 = 2877.9 x 0.09 = 0.0 Q= ARCHxVOL. /60= 0.48 x 12113 / 60 = 96.9 Area A/C= 14215 Sq. ft. Volume A/C= ,`````xx�t, `tt►25c "S ��i$.5 = 12113 Cu. ft. V Gam- C •,, "G F , No 2 X233 -o % STATE OF ZONAL