05-192-012I , f� D 4 '11D ELECTRICAL SPECIFICATIONS 27 WIRING DEVICES SHALL BE FLUSH MOUNTED, SPECIFICATION GRADE, PART I - GENERAL MANUFACTURER SHALL BE LEVITON. A. SWITCHES: 20A 120/277V, SINGLE POLE, THREE -WAY WHERE NOTED. SWITCHES IN THE SAME AREA SHALL BE GANGED TOGETHER IN THE SAME BOX. 1,1 GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE CONTRACT AND B. RECEPTACLES! 20A 120V GROUNDING TYPE DUPLEX, SPECIAL OUTLETS RATED TO MATCH SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND TRADES SHALL CIRCUIT BREAKERS AS NOTED ON PLANS, QUADRUPLEX OUTLETS AND SWITCH /OUTLET APPLY AND BE PART OF THE WORK HEREBY SPECIFIED, THESE SPECIFICATIONS AND THE COMBINATIONS SHALL HAVE THE SAME FACE PLATE„ ISOLATED GROUND TYPE SHALL BE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION PROVIDED WITH SEPARATE ISOLATED GROUND WIRE. OF THE ELECTRICAL SYSTEMS. "PROVIDE" MEANS "CONTRACTOR SHALL FURNISH AND INSTALL ". C. TELEPHONE AND DATA OUTLETS: TELEPHONE /DATA JACKS AND WIRING AS SELECTED BY USER UNLESS OTHERWISE NOTED, OTHERWISE, PULL WIRE WITH 12" SLACK AT EACH END, RUN IN 1.2 COMPLIANCE WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH 3/4" EMPTY CONDUIT, WHERE PREVIOUSLY APPROVED BY RULING AUTHORITIES AND THE LATEST EDITION OF NFPA, NEMA, NEC, ASTM, OSHA, PPS, HEALTH AGENCIES, AND ENGINEER, RACEWAYS MAY BE INDIVIDUALLY TERMINATED ABOVE DROP CEILING WITH OTHER APPLICABLE NATIONAL, STATE, AND LOCAL CODES AND PERTAINING REGULATIONS ESTABLISHED BY SMOOTH 90 BEND AND PLASTIC BUSHING. RULING AUTHORITIES HAVING JURISDICTION. CONTRACTOR SHALL ALSO MEET OTHER RECOGNIZED D. MOUNTING HEIGHTS, S, WHERE NOT ESTABLISHED ON PLANS OR LEGEND, MOUNTING HEIGHT STANDARDS AND REQUIREMENTS, WHERE SUCH ARE MORE STRINGENT THAN THOSE CITED ABOVE. SHALL BE AS FOLLOWS OR TO MATCH HEIGHTS ESTABLISHED BY EXISTING DEVICES. MH = 18 "AFF - GENERAL AREA RECEPTACLES, TELEPHONE AND DATA OUTLETS. 1.3 WORKMANSHIP ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN THEiR RESPECTIVE MH = 42 "AFF - COUNTER RECEPTACLES, TELEPHONES AND DATA OUTLETS, " DISCIPLINES, WORK SHALL BE DONE IN A FIRST CLASS MANNER, FULLY OPERATIVE, AND TO THE MH . 52 "AFF - WALL MOUNTED PHONES ACCEPTANCE OF THE ARCHITECT /ENGINEER. CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR MH - 48 "AFF - SWITCHES AND MATERIALS REQUIRED FOR COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO MH SHALL BE CONSIDERED TO THE BOTTOM OF EACH OUTLET JUNCTION BOX CONNECTIONS TO RELATED WORK SUCH AS CONNECTION TO EXISTING SYSTEMS, EXCAVATIONS AND BACKFILLING. 2.8 TELEPHONE CABINET /BOARD SHALL BE PROVIDED WITH A 3/4" THICK EXTERIOR GRADE PLYWOOD IA MATERIALS- CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN MANUFACTURE, BEARING BACKBOARD PAINTED WITH TWO COATS OF FIRE RETARDANT PAINT ON ALL SIDES AND EDGES. UNLESS THE UNDERWRITER'S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE ACCEPTABLE AND OTHERWISE NOTED, BOARD SIZE SHALL BE 4'W X 8'H. PROVIDE DEDICATED 20A DUPLEX AND x6 ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON PLANS. GROUNDING ELECTRODE. SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, 2.9 LIGHTING FIXTURES SHALL BE COMPLETE WITH ALL NECESSARY LAMPS, BALLASTS, WIRING, LAMP SHALL BE PROVIDED BY CONTRACTOR AS REQUIRED FOR COMPLETION OF THE WORK AT NO ADDITIONAL HOLDERS REFLECTORS, GLASSWARE, POLES, BASES AND MOUNTING ACCESSORIES AS REQUIRED TO COST TO THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND COORDINATION OF PROVIDE FORA COMPLETE INSTALLATION. INTERIOR FIXTURES SHALL HAVE 100% VIRGIN ACRYLIC DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING SHIPMENT OR INSTALLATION SHALL BE TOUCHED PRISMATIC DIFFUSERS. LIGHTING FIXTURES SHALL BE SELECTED BY ARCHITECT /OWNER AND OWNER, UP AND REFINISHED TO FACTORY FINISH, REPLACED WHERE NOT ACCEPTABLE. PROVIDED BY CONTRACTOR, REFER TO ARCHITECTURAL DRAWINGS FOR COLOR, FINISH AND EXACT MOUNTING DETAILS. ALL FIXTURES SHALL BE ENERGY SAVING ELECTRONIC BALLAST AND LAMPS. 1.5 PERMITS E INSURANCE! CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE PARS EXECUTION FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 3,1 TESTS PROVIDE ALL NECESSARY INSTRUMENTS AND SPECIAL APPARATUS TO CONDUCT ANY TESTS THAT MAY BE REQUIRED TO INSURE SYSTEM IS FREE OF ALL IMPROPER GROUNDS AND SHORT CIRCUITS AND 1.6 EXISTING CONDITIONS: BEFORE BIDDING CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL THAT ALL FEEDERS ARE PROPERLY BALANCED. SYSTEM SHALL BE CHECKED FOR QUALITY, CAPACITY AND EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS COMPLETENESS TO CONFORM WITH THE FULL REQUIREMENTS AND INTENT OF THE DRAWINGS AND A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIAL SPECIFICATIONS. OR LABOR. ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT /ENGINEER. CORRECTION 3,2 CONDUIT RUNS, RACEWAYS AND PIPING SHALL BE CONCEALED IN WALLS, CEILINGS, SLABS AND OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE PARTITIONS, NO RACEWAY SHALL BE EXPOSED WITHIN INTERIOR SPACES. ALL OUTLETS AND WIRING REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DEVICES SHALL BE FLUSH MOUNTED, DAMAGED THEREBY, 3.3 GROUNDING AND BONDING SHALL COMPLY WITH NEC 250. ALL METALLIC RACEWAYS SHALL BE 1.7 UTILITY COMPANIES' BEFORE SUBMITTING BiD CONTRACTOR SHALL CHECK WITH WATER, SEWER, GAS, GROUNDED AND BONDED PER NEC 250. NON - METALLIC RACEWAYS SHALL BE PROVIDED WITH A ELECTRICAL, TELEPHONE, CABLE TV AND OTHER UTILITY COMPANIES SUPPLYING SERVICE TO THIS GROUNDING CONDUCTOR SIZED PER NEC 250 -122 INSTALLATION TO DETERMINE INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COSTS TO BE INCLUDED IN THE BID. EXCEPT WHERE UTILITY REQUIREMENTS CHANGE AFTER SUBMITTAL, NO 3.4 ELECTRICAL EQUIPMENT SPACE AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC 110 -16A AND EXTRA PAYMENT WILL BE MADE TO THE CONTRACTOR FOR SUCH ITEMS. PROVIDE TEMPORARY 384 -2. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH NEC ELECTRICAL SERVICES FOR ALL TRADES AS REQUIRED. 1.8 PLANS DRAWINGS ARE GENERALLY DIAGRAMMATIC, INTENDED TO SHOW APPROXIMATE EQUIPMENT 3.5 PANELBOARDS, SWITCHES, CONTROLLERS, CONTROL PANELS, TIMECLOCKS, AND OTHER ELECTRICAL LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL. PLANS SHALL NOT BE SCALED COMPONENTS SHALL BE CLEARLY AND PERMANENTLY IDENTIFIED. INDICATE PANELBOARDS CIRCUITS ON TO DETERMINE EXACT LOCATION AND DIMENSIONS. UPDATED TYPED DIRECTORY CARD HOLDERS WITH PLASTIC COVER AND METAL FRAME INSTALLED ON INSIDE OF PANELBOARD DOOR. MARK CONDUCTORS WITH PREPRINTED ADHESIVE MARKERS AS MANUFACTURED 1.9 INTERFERENCE: CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES SO THAT BY W.H. BRADY CO, OR THOMAS E BETTS. INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL, ^ STRUCTURAL MEMBERS WILL BE AVOIDED. 3.6 CONTRACTOR SHALL MAKE ALL NECESSARY EXCAVATIONS, CUTTING AND REPATCHING AS REQUIRED FOR THE PROPER EXECUTION OF THIS WORK. 1.10 SHOP DRAWINGS PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION, SUBMIT FOR REVIEW PROPERLY IDENTIFIED AND BOUND SHOP DRAWINGS AND MANUFACTURER'S LITERATURE GIVING 3,7 CONTRACTOR SHALL FIELD SPOT LOCATION OF WIRING DEVICES TO VERIFY AND GET APPROVAL FROM SPECIFICATIONS, DETAILS, COMPLIANCE, UL APPROVAL, MATERIALS, FINISHES, ACCESSORIES AND THE ARCHITECT BEFORE INSTALLATION. INSTALLATION DIRECTIONS WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. FACTORY CERTIFIED PRINTS 3.8 UNLESS OTHERWISE NOTED AS EXISTING TO REMAIN OR BE RELOCATED, ALL MATERIALS AND EQUIPMENT SHALL BE FURNISHED FOR ALL MAJOR ITEMS OF EQUIPMENT AND SPECIFIED, SUBMISSION OF SHALL BE NEW AND PROVIDED BY THIS CONTRACTOR. EXISTING EQUIPMENT TO BE REMOVED NOT EQUIPMENT FOR APPROVAL SHALL BE MADE COMPLETE AND ALL AT THE SAME TIME. CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE JOB SITE AS DIRECTED, FIELD VERIFY BEFORE REMOVAL. 1.11 SUBSTITUTIONS, PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE, PERFORMANCE AND DIMENSION, CONTRACTOR SHALL 3.9 WHERE WORK ON EXISTING EQUIPMENT IS REQUIRED, SPECIAL ATTENTION SHALL BE GIVEN TO BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF CONDITIONS OF PANELS AND SWITCHING EQUIPMENT. MODIFY EXISTING PANELS AND EQUIPMENT BY BIDDING. REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING TO THE THE ADDITION OF CIRCUIT BREAKERS, WIRING, AND OTHER EQUIPMENT AS REQUIRED IN ORDER TO ARCHITECT /ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN, PROVIDE A COMPLETE AND OPERATING SYSTEM. CIRCUIT BREAKERS AND SWITCHES INSTALLED IN CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT EXISTING PANELBOARDS AND SWITCHING DEVICES SHALL BE OF THE SAME MANUFACTURER AND FULLY CAUSE EXTRA WORK FOR OTHER TRADES, CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY COMPATIBLE WITH THE COMPONENTS PROVIDED, EXISTING EQUIPMENT OR DEVICES INADVERTENTLY OF SUBSTITUTIONS, ARCHITECT /ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE DE- ENERGIZED OR DISCONNECTED SHALL BE RE- ENERGIZED AND MADE OPERABLE AT NO ADDITIONAL SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT /ENGINEER EXPENSES COST. INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR SUBSTITUTIONS SHALL BE PAID BY CONTRACTOR. 1.12 GUARANTEES, AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE ARCHITECT /OWNER, ENTIRE ELECTRICAL INSTALLMENT AND WORK, INCLUDING PARTS AND LABOR, SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION AND WORKMANSHIP WHERE APPLICABLE LONGER GUARANTEES FOR CERTAIN COMPONENTS SHALL APPLY AS REQUIRED AND NOT BE REDUCED IN ANY WAY. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE TO THE OWNER AND SHALL INCLUDE REPLACEMENTS AND /OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY, 1.13 RECORD DRAWINGS' MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES. USE COLORED PENS TO MARK CHANGES AT THE TIME OF EXECUTION AND DELIVER THE SET TO ARCHITECT /ENGINEER UPON COMPLETION. CONTRACTOR SHALL STAMP "AS BUILT" ON PRINTS AND PLANS, DATE AND SIGN IN INK, WORK SHALL NOT BE CONSIDERED COMPLETED UNTIL SUCH PLANS ARE REVIEWED AND APPROVED BY ARCHITECT /ENGINEER. PART 2 - PRODUCTS 2.1 SHOP DRAWINGS- SUBMIT SHOP DRAWINGS OF THE FOLLOWING PRODUCTS, A. SWITCHGEAR, PANELBOARDS, OVERCURRENT PROTECTION DEVICES, CIRCUIT BREAKERS, SWITCHES. FUSES. B. WIRING, CABLING, CONDUITS, RACEWAYS, FLOOR AND OUTLET BOXES, C. WIRING DEVICES, RECEPTACLES, OUTLETS, LIGHT SWITCHES. PLATES, D. LIGHTING FIXTURES, LAMPS AND RELATED HARDWARE. E. TIMECLOCKS AND CONTACTORS. F. MISCELLANEOUS SYSTEMS: FIRE ALARM, CONTROLS. 2.2 SWITCHGEAR' PANELBOARDS SHALL BE OF THE CIRCUIT BREAKER TYPE. CIRCUITS BREAKERS SHALL BE MOLDED CASE, BOLT -ON TYPE, OF QUICK -MAKE ACTION, THERMAL MAGNETIC TRIP, FULL SIZE DEVICES. LOAD CENTER TYPE PANELBOARDS SHALL NOT BE USED. EXCEPT WHERE SPECIFICALLY NOTED. UNLESS OTHERWISE NOTED ON PLANS, MINIMUM EQUIPMENT AIC RMS SYM RATING SHALL BE 10,000 AT 120/240V OR TO MATCH EQUIPMENT IN WHICH CIRCUIT BREAKER IS BEING INSTALLED, WHICHEVER IS GREATER. PHASES SHALL BE BALANCED WITHIN 10 PER CENT. MANUFACTURER SHALL BE GE, SQUARE -D OR WESTINGHOUSE. PROVIDE LIGHTNING ARRESTOR AT EACH PANELBOARD AND SERVICE DISCONNECTS, 2.3 DISCONNECTS: SWITCHES SHALL BE QUICK -MAKE QUICK -BREAK ACTION, LOCKABLE TYPE, SERVICE DISCONNECT SHALL BE SERVICE RATED, HEAVY -DUTY TYPE. PROVIDE DUAL ELEMENT FUSES FOR MOTOR DRIVEN MECHANICAL EQUIPMENT SIZED PER MANUFACTURER'S RECOMMENDATION. FIELD COORDINATE FUSE SIZE WITH EQUIPMENT NAMEPLATE BEFORE ACTUAL INSTALLATION. MANUFACTURER SHALL BE GE, SQUARE -D OR WESTINGHOUSE. 2.4 RACEWAYS, A. RGS AND IMC; NOT - DIPPED GALVANIZED INCLUDING THE THREADS. PROVIDE FOR EXTERIOR LOCATIONS, WHERE EXPOSED TO PHYSICAL DAMAGE AND FOR ELBOWS, ELLS AND RISERS INTO GROUND AND SLAB INSTALL ELLS AND RISERS STUBBED UP 6 INCHES FROM 2 Hour Fire Rated Through U L/tSL�® WUL as`lp,b Penetration Firestop for ULn�L�ULILg w 51ngle Metal Pipe through 3133Graw,Aa. Concrete floors or block wa Its e.aclwood, oµ, 44122 using TREMstop Acrylic. +tie I Drawing not to ocile CAJ1205 F-rating - 2 Hr. T- rating = 0 Hr. Q Pre -Rated Concrete Floors or Block Walls = Min. 4 -1/2' thick, with annular space range of 0' to i /t9'. (2) Steal Pipe - 4' dfa. (or smaller) 5c4-L 40 (or heavier) steal. Conduit - Nom. 4' dfa. (or smaller) steel conduit or EMT, Copper pipe,- 3' dfa. (or smaller) Regular (or heavier) copper, Cast Iron Pipes - 4' dia, for smaller) cast or ductile Tron. Copper Tubing - 3' dra_ (or smaller) Type L. (or heavier) copper. Q Packing Material - Mineral wool (min. 4 pcf) compressed min. 50% and installed into the opening to obtain min. 4' thickness. O TREMstop Alcrylic - Min. 1/2' sealant applied within annulus, and a minimum 1/4' sealant applied at point contact: at the Floor surface For floors, or both surfaces For walls. n. T,a"w'rrai,aN wad aW~ I.- I.- R•Oj /t1 • �� M ..___'__- ulw• w M,i.dy TM aF.vw /rM/ awa"ily and • AM U14 NLMTU su,,.lard »W ?w 7w, M"4sJ «u w Locatloq, um m� P L w "n.',r "'"•• " a. t • "•• •�:n as.xlld Gw.,nicuan b.l,•iH"rYIL W I,WL far ",y /nr +r. W,tiwl Irutallsr' - ' Dateln2I Drawi _Tm -12G5 W,ia "yMr..rrar *��, s,gruturs: wunat . w rr�.5,w roved b . pitcal� CONCEALED SLAB RUNS, 48" ABOVE GROUND WHERE EXPOSED ON WALL. PAINT RACEWAYS 7 BELOW O NT LAB R EIS ABED EXTERIOR GRADE: WITH TWO (2) COATS OF BITUMASTIC PAINT UP TO FIRE PENETRATION DETAILS B. EMTt MAY BE USED FOR INTERIOR SPACES IN DRY LOCATIONS, WHERE NOT EXPOSED TO PHYSICAL DAMAGE. FITTINGS SHALL BE STEEL, C. PVC SCHEDULE 40 SHALL NOT BE USED, EXCEPT FOR RUNS UNDER OR WITHIN SLAB. D. FLEXIBLE METALLIC CONDUIT, LIGHTING FIXTURES, MOTORS, TRANSFORMERS AND VIBRATING EQUIPMENT CONNECTIONS IN LENGTHS NOT TO EXCEED 18 ". PVC JACKETED FLEXIBLE METAL CONDUIT FOR LOCATIONS OUTSIDE AND /OR EXPOSED TO MOISTURE, GREENFIELD OR APPROVED EOUAL, E. RUNS BELOW SLAB SHALL BE PROVIDED WITH A YELLOW RIBBON TAPED ALONG TRENCH 6" BELOW GRADE FOR RACEWAY IDENTIFICATION. 2.5 CONDUCTORS, SOFT -DRAWN 98% CONDUCTIVITY COPPER INSTALLED IN CONDUIT. MINIMUM SIZE SHALL BE x12 FOR POWER WIRING, 1*16 FOR CONTROL CIRCUITS. PROVIDE 1*10 WIRES FOR 120V POWER CIRCUIT HOMERUNS LONGER THAN 100 FEET. INSULATION SHALL BE 600V THHN /THWN FOR GENERAL USE, THW IN SIZES x6 AND ABOVE, COLOR CODED THROUGHOUT PER NEC AND TRADE STANDARDS. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH NEC 300 -22. 2.6 SPLICES SHALL BE MADE WITH UL LISTED MECHANICAL PRESSURE SOLDERLESS CONNECTORS, BURNDY SERVITS TYPE OR APPROVED EQUAL, FEEDER SPLICES AND TERMINATIONS SHALL BE MADE MECHANICALLY USING COMPRESSION TYPE SLEEVES OR LUGS AND CONNECTION TO PANELS AND SWITCHES AS MANUFACTURED BY BURNDY OR THOMAS E BETTS. "SUBJECT TO FiELD INSPECTIOIN It e 240V IP 3W R, 3R ;I_IIi MF.NT 1101 ,ra [3 CORRi?C(' %A /I[RE S!z -s ........................................................... ., }.Rt err n 1 i Q � AT T -S ANT 7'x:07 i C . �"TUS1, F PANEL 'A" 200 B,3R O CB I v4 GROUNDING ELECTRODE TO (2)5/8'D X 10'L COPPERCLAD GROUND RODS SPACE 6' APART, SUPPLY SIDE OF MAIN CWP, AND BUILDING FOUNDATION STRUCTURAL REBARS 20' MINIMUM LENGTH SERVICE RUN UNDERGROUND TO FPL POINT OF CONNECTION AT PROPERTY LINE. RISER DIAGRAM GRADE I ")UC„ i TF K .S 7 "F�iv I ry v.J