05-1454-0171. Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2 -1/2 in. wide and spaced max 24 in. OC. B. Gypsum Board* -- 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 7 -1/2 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants -- One metallic pipe or tubing to be centered within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used: A. Steel Pipe Nom 4 in. diam (or smaller) Schedule 40 (or heavier) steel pipe. B. Copper Tubing - -- Nom 2 in. diam (or smaller) Type L (or heavier) copper tubing. C. Copper Pipe -- Nom 2 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Tube Insulation - Plastics+ - Nom 3/4 in. thick acrylonitrile butadiene /polyvinyl chloride (AB /PVC) flexible foam furnished in the form of tubing. An annular space of min 0 in. (point contact) to max 1 -1/2 in. is required within the firestop system. See Plastics+ (QMFZ2) category in the Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94 -5VA may be used. The hour T Rating of the firestop system is dependent on the hourly fire rating of the wall assembly in which it is installed, the size and type of through penetrant and the pipe covering thickness, as shown in the table below: Wall Assembly Rating Hr Type + hrough Penetrant Max Diam In. 1 A 4 1 A, BorC 2 2 A 4 2 A. BorC 2 +Indicates penetrant type as itemized in Item 2. 4. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location between pipe covering and gypsum wallboard, a min 1/2 in. diam bead of fill material shall be applied at the pipe covering /gypsum wallboard interface on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS -ONE Sealant *Bearing the UL Classification Mark System No, C -AJ -1152 F Rating - 2 Hr T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM /sq ft L Rating At 400 F - 4 CFM /sq ft SECTION A -A 1. Floor or Wall Assembly - Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete floor or min 4 in. thick reinforced lightweight or normal weight concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 6 in. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants - One metallic pipe or conduit to be installed within the firestop system. Pipe or conduit to be rigidly supported on both sides of floor or wall assembly. The annular space shall be min 3/4 in. to max 7/8 in. The following types and sizes of metallic pipes or conduits may be used: A. Steel Pipe - Nom 4 in. diam (or smaller) Schedule 40 (or heavier) steel pipe. B. Conduit - Nom 4 in. diam (or smaller) steel conduit. 3. Packing Material - Min 3 in. thickness of min 4.0 pcf mineral wool butt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. 4. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP -601S, CP606 FS -ONE Sealant (Note: L Ratings apply only when FS -ONE Sealant is used). *Bearing the UL Classification Marking PIPE PENETRATION FIRESTOP DETAIL SCALE: NTS System No, W -L -5028 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4 SECTION A -A System No, W -J -5041 F Ratings - 1 and 2 Hr (See Items 1) T Ratings - 3/4 Hr SECTION A -A 1. Wall Assembly Min 3 -3/4 in. and 5 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete for 1 and 2 h rated assemblies respectively. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 7 -1/2 in. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Through -- Penetrants One metallic pipe, conduit or tubing to be centered within the firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe Nom 4 in. diam (or smaller) Schedule 40 (or heavier) steel pipe. B. Conduit Nom 4 in. diom (or smaller) electrical metallic tubing or steel conduit. C. Copper Tubing Nom 2 in. diam (or smaller) Type L (or heavier) copper tubing. D. Copper Pipe Nom 2 in. diam (or smaller) regular (or heavier) copper pipe. 3. Tube Insulation - - Plastics+ Nom 3/4 in. thick acrylonitrile butadiene /polyvinyl chloride (AB /PVC) flexible foam furnished in the form of tubing. An annular space of min 0 in. (point contact) to max 1 -1/2 in. is required within the firestop system. See Plastics+ (QMFZ2) category in the Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94 -5VA may be used. The hour T Rating of the firestop system is dependent on the size and type of through penetrant and the pipe diam, as shown in the table below: +- Indicates penetrant type as itemized in Item 2. 4. Fill, Void or Cavity Material*- -Sealant Min 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location between pipe covering and wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe covering /wall interface on both surfaces of wall HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI IIIC -- FS611A or FS -ONE Sealant *Bearing the UL Classification Mark PLUMBING FIXTURE CONNECTION SCHEDULE Through Penetrant Max. Diameter, In. WATER 4 OA 2 +- Indicates penetrant type as itemized in Item 2. 4. Fill, Void or Cavity Material*- -Sealant Min 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location between pipe covering and wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe covering /wall interface on both surfaces of wall HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI IIIC -- FS611A or FS -ONE Sealant *Bearing the UL Classification Mark PLUMBING FIXTURE CONNECTION SCHEDULE MARK WATER CONN. SIZE OA No DESCRIPTION DRAIN COLD HOT SLOPE REMARKS FU WC WATER CLOSET 4" V2" N/A 3 " &4 " @1 /8 " /FT FO 3 L LAVATORY 1 -1/2" Vi" '' /z" 1- 1 /2 " @1 /4 " /FT CONDENSATE DRAINAGE LINE 1 TUB TUB 2" V2" 'h" 2" @1 /4 97FT w/AN'rI - SCALD VALVES 2 BT BATHTUB 2" Vx" 'W' 2" @1 /4 "/FT W /ANTI -SCA VALVES LD 2 SH SHOWER 2" V2" Vz" 2" ° 1 /4 "/FT � w /AN'rt SCALD VALVES 2 BD BIDET 2" Vz" Vz" 2" @1 /4 "/FT PROVIDE VACCUM BREAKER 2 SK 2 COMP. SINK 1 -1/2" Us" ' /z" 1- 1/2 " @1 /4 " /FT SWKW /DISP. 2 LS LAUNDRY SINK 1 -1 /2" Vz" ' /z" 1-1/2"@1/4"/FT 3 D/W DISHWASHER 1" N /A" ' /z" N /A" CONNECT TO G.D. N/A WM CLOTHES WASHER 2" 'h" Uz" 2" @1 /4 " /FT PROVIDE wM BOX W1 (2)1/2" IIB & 2" DRAIN 2 REF. REFRIGERATOR NA V2" N/A N/A ICE MAKER CONNECTION N/A EWH ELECTRIC WATER HEATER N/A 3/4" 3/4" N/A 6.OKW/ 240/ 1/ 60 N/A WATER HAMMER ARRESTER SCHEDULE MARK *P.D.I SIZE CONN. SIZE OA A(1 -11 F.U.) 1/2" BO B (12 - 32 F.U.) 3/4" O C (33 - 60 F.U.) 1" OD D (61 - 113 F.U.) 1" EO E (114 - 154 F.U.) 1" FO A (155 - 330 F.U.) 1" (a FD FLOOR DRAIN. J I L VTR DISCNARCZ 12 " PfROM BUILDI 6 NOTES: A. SLOPE DRAIN LINE TO CONDENSATE RECEPTOR (MIN 318 PER FOOT) B. DRAIN LINE SHALL BE COPPER TYPE "L" AND INSULATED C. TSP = FAN TOTAL STATIC PRESSURE D. PROVIDE CONDENSAT OVERFLOW SAFTEY SWITCH TO TURN OFF THE UNIT IF DRAIN PAN APPROACHES OVERFLOW. *PLUMBING AND DRAINAGE INSTITUTE STANDARD WH -201 r)17'017_/I0AT17_r'\ % /r'KIT f�An PLUMBING GENERAL NOTES: 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE INSTALLATION OF A COMPLETE PLUMBING SYSTEM IN ACCORDANCE WITH THESE DRAWINGS, THE APPLICABLE EDITION OF THE FLORIDA BUILDING 2001 CODE, ALL OTHER APPLICABLE STATE, COUNTY AND LOCAL CODES AND ORDINANCES. 2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL OTHER COST INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK, UPON FINAL ACCEPTANCE, A CERTIFICATE FROM THE LOCAL INSPECTION AUTHORITY SHALL BE FURNISHED TO THE OWNER. 3. ALL MATERIALS AND EQUIPMENTS SHALL BE NEW, OF U.S. MANUFACTURER AND OF GOOD QUALITY OF RESPECTIVE KIND AND GRADE, AND MUST BE FURNISHED SO AS TO PREVENT ANY DEALAY IN THE PROGRESS OF THE WORK. ALL WORK THOUGHOUT SHALL BE PERFORMED IN A WORKMANLIKE MANNER BY SUFFICIENT NUMBER OF SKILLED WORKMEN. 4. CONTRACTOR SHALL VISIT THE SITE AND REVIEW ALL PERTINENT UTILITY DRAWINGS TO FAMILIARIZE HIMSELF WITH THE LOCATION OF ALL EXISTING AND OR PROPOSED UTILITY STUB OUTS, PIPING, EQUIPMENT, ETC., AND MAKE DUE ALLOWANCES FOR ANY CONDITION AFFECTING HIS WORK. 5. ALL UNDERGROUND SANITARY & STORM DRAINAGE PIPING AND FITTINGS SHALL BE PVGDWV (ASTM D- 2662/D- 3034). 6. ALL ABOVE GROUND SANITARY & STORM DRAINAGE BRANCH & VENT PIPES AND FITTINGS SHALL BE PVGDWV (ASTM D- 2662/D - 3034). 7. ALL UNDERGROUND WATER PIPING SHALL BE COPPER TYPE "K" (ASTM B -306). ALL ABOVE GROUND PIPING SHALL BE COPPER TYPE "L" (ASTM B -306). S. ALL HOT WATER PRESSURE AND TEMPERATURE RELIEF PIPING SHALL BE COPPER TYPE "K" (ASTMB -306). 9. ALL AIR CONDITIONING CONDENSATE DRAINAGE PIPING SHALL BE SCH. 40 PVC (ASTM D- 2662). EXCEPT WHEN INSTALED IN RETURN AIR PLENUM WHERE COPPER TYPE "DWV" OR EQUIVALENT MUST BE USED. 1 O.ALL PLUMBING FIXTURES SHALL BE PROVIDED WITH ALL NECESSARY ACCESSORIES SUCH AS STOP VALVES "P" TRAPS, SUPPORTS, P &T VALVES, ETC., AS REQUIRED. ALL EXPOSED PIPING AT FIXTURES AND EQUIPMENT SHALL BE CHROME PLATED BRASS PIPE OR TUBE. PROVIDE SHUT OFF VALVES AND UNIONS TO ALL FIXTURES, ETC., REQUIRING WATER SUPPLY. PROVIDE DIELECTRIC COUPLINGS AS REQUIRED. FOR ALL COPPER- PIPING CONTRACTOR MUST USE 95/5 SOLDER PROVIDE WATER HAMMER ARRESTER TO EACH FIXTURE AS REQUIRED. I I .PROVIDE CLEANOUTS (WITH CHROME PLATED WALL OR FLOOR ACCESS FRAMES AND COVERS AS REQUIRED) AT THE BASE OF ALL WASTE AND /OR VENT S TAKS. PROVIDE PITCH PANS & LEADS FLASHING FOR ALL SANITARY SYSTEM VENTS. 12.ALL HORIZONTAL WASTE PIPING SHALL BE SLOPED AT 1/8 PER FOOT, UNLESS OTHER WISE NOTED. 11CONTRACTOR SHALL VERIFY SLOPE AND DEPTHS AND LOCATIONS OF CONNECTION POINTS TO EXISTING PRESSURE OR DRAINAGE LINES BEFORE STARTING WORK. NOTE - SPECTIC TANK INLET CONDENSATE TRAP DETAIL SCALE: NT5 ' DRAIN RELIEF VALVE 3/4" HOT WATER HEAT TRAP WATER HEATER DRAIN VALVE FLOOR PLUMBING LEGEND: SYMBOL DESCRIPTION- Uj SANITARY PIPE. - - - - - _ - - - - - VENT LINE. = - - COLD WATER LINE. - • - • - - - - - HOT WATER LINE. CTG 0- CLEAN OUT TO GRADE. FCO -® FLOOR CLEAN OUT*, WCO 0a1 WCO WALL CLEAN OUT Ir PRESS. & TEMP. RELIEF VALVE - PT - PRESS. & TEMP. RELIEF LINE. `-MM , UNION. (a FD FLOOR DRAIN. J I L VTR VENT THRU ROOF. -0 - CONDENSATE DRAINAGE LINE -fla- GATE VALVE ��-- CHECK VALVE • F.EX FIRE EXTINGUISHER ON WALL BRACKET (2A -IOBC) HB +-) HOSE BIBB W/ VACUUM BRAKER FEC FIRE ESTINGUISHER 11 'CABINS T (2A l OBC) T PIPE FLOOR PENETRATION VB VACUUN BREAKER VIV VALVE IN VERTICAL VTR VENT THRU ROOF AFF ABOVE FINISHED FLOOR LEVEL ` E�T-C WATER HAMMER ARRESTOR w NOTES: 1. RUN 1 -1/2" PIPE @' /4" FT. FIXTURE ARM 2. RUN 2" PIPE @'/4" FT. , 3. RUN 3" PIPE @ 1/8" F. 4. RUN 4" PIPE @ 1/8" FT. 5. PROVIDE CLEANOUT AT BASE OF EACH SO11° AND u1GASTE STACK. "* 6. SHOWERS & TUBS VALVES TO BE ANTI -SCALD TYPE. 7. INSTALL %" CW AT RIGHT SIDE OF FIXTURES. PROVIDE AIR CHAMBER 8. INSTALL %" HW AT LEFT SIDE OF FIXTURES. PROVIDE AIR CHAMBER. .. f, Y Al VACUUM RELIEF VALVE...- „ WATTS # 36 A 3/4" COLD WATER 3/4" SHUT -OFF VALVE FIXED AIR GAP ZURN # 1024 3/4" P & T RELIEF PIPE r NOTE: 6" ABOVE GRADE EWH -1: ELECTRIC WATER HEATER "LOCHINVAR" (OR APPROVED EQUIVALENT) ENERGY SAVER TALL MODEL NO. ET4050PP, 6.0 KW, 24011160. RECOVERY 35 GPN AT 70" RISE. STORAGE 50 GAL. GLASS -LINED TANK, 5 YEAR WARPENTY. ENERGY FACTOR 0.86. TANK SIZE 20' DIA X 46" 14EIG14T WATER HEATER PIPING DIAGRAM SCALE: NT5 A NOTE AS PER FRCP 2004 502.3: WATER HEATERS INSTALLED IN GARAGES SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, WHICH SHALL BE AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTION. f y { f' L COLTRAIN AND JONES ARCHfTECTURE, PA DESIGN f CAD PRODUCTION CONSTRUCTION ADMINISTRAMON BUILDING INSPECTIONS '4:' TEII-005) 285-6723. 285722 535 SW 8 ST. SUITE 100 KkAMI,. FL' 30 REVISIONS /COMMENTS: BUILDING DEPT. COMMENT SEAL 4, MARK A. COLTRAIN AR 001338E RICHARD K. JONES, AIA ;AR 001575 SHEET TITLE: PLUMBING SCHEDULES NOTES /DATES: T ..................................................-..---------......_.- _...........------ ............. JOB NO.: SHE 2005 -12 CARBONELL PERMIT SUBMITTAL DATE: I ' 9/29/05 DATE PRINTED: P 02/07/06 SCALE: AS NOTED DRAWN BY- M.R. ' a Uj Z W Q Q Cl) W `-MM , �- W M w�. J W > Q 0 UJ O 0 (0 U 10 N (0 W� rter^^ V, SEAL 4, MARK A. COLTRAIN AR 001338E RICHARD K. JONES, AIA ;AR 001575 SHEET TITLE: PLUMBING SCHEDULES NOTES /DATES: T ..................................................-..---------......_.- _...........------ ............. JOB NO.: SHE 2005 -12 CARBONELL PERMIT SUBMITTAL DATE: I ' 9/29/05 DATE PRINTED: P 02/07/06 SCALE: AS NOTED DRAWN BY- M.R.