Loading...
08-1279-020I CD CO C: r_ I .y x h ELECTRICAL NOTES: PART 1 - GENERAL: 1.- THE GENERAL AND SPECIAL CONDITION AND REQUIREMENTS OF THE CONTRACT AND SPECIFICATION AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND TRADES SHALL APPLY AND BE PART OF THE WORK HEREIN SPECIFIED. THESE SPECIFI- CATION AND THE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. 2.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WIITH THE LATEST EDITION OF 2004 FBC 2004 NEC NFPA NEMA IEEE• OTHER APPLICABLE NATIONAL, STATE k LOCAL CODES, AND PERTAININU REGULATIdNS ESUBLISRED B$ AUTHORITIES HAVING JURISDICTION, AND SHALL MEET THE REQUIREMENTS OF OTHER RECOGNIZED STANDARDS WHERE "PART 1 - GENERAL" THE REQUIREMENTS ARE MORE STRINGENT THAN THOSE CITED ABOVE. 3.- WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS MANNER AND SHALL BE COMPLETED AND FULLY OPERATIVE TO THE ACCEPTANCE OF THE ARCHITECT /ENGINEER. 4.- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS, BEARING THE UNDER - wRI'IR S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE ACCEPTABLE AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON PLANS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE DELIVERY SCHEDULES OF MATERIALS. 5.- DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL; PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. PROVIDE ALL OFFSETS, FITTINGS AND ACCESORIES REQUIRED FOR A COMPLETE, ACCEPTABLE, WORKING INSTALLATION. 6.- SUPPLEMENTAL MATERIALS OR MANUFACTURED PRODUCTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED AS REQUIRED TO COMPLETE THE INATALLATION AT NOT ADDITIONAL COST TO THE OWNER. 7.- EXISTING CONDITION: BEFORE BIDDING CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL EXISTING CONDITIONS, WfHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIAL OR LABOR. ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIA- TELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT /ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 8.- UTILITY COMPANIES: BEFORE SUBMITTING BID CONTRACTOR SHALL CHECK WITH ELECTRICAL, TELEPHONE, CABLE TV AND OTHER UTILITY COMPANIES SUPPLIYING SERVICE TO THIS INSTALLATION TO DETERMINE INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COST TO BE INCLUDED IN THE BID. EXCEPT WHERE UTILITY REQUIREMENTS CHANGE AFTER SUBMITTAL, NO EXTRA PAYMENT WILL IRE MADE TO THE CONTRACTOR FOR SUCH ITEMS, PROVIDE TEMPORARY ELECTRICAL SERVICES FOR ALL TRADES. 9.- PERMITS: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES. TAXES, INSPECTION, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF A COMPLETE ELECTRICAL SYSTEM AS OUTLINED HERE IN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 10.- INTERFERENCE: PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL COORDINATE HIS WORK WIITH THE WORK OF OTHER TRADES, SO THAT INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL. STRUCTURAL AND WORK WITH OTHER TRADES WILL BE AVOIDED. 11.- SUBMITTAL: PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION, SUBMIT FOR REVIEW PROPERLY IDENTIFIED AND BOUND, SHOP DRAWINGS AND MANUFACTURER'S LITERATURE GIVING SPECIFICATIONS, DETAILS, COMPLIANCE, UP APPROVAL, MATERIALS, FINISHES, ACCESORIES AND INSTALLATION DIRECTIONS WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE, PERFORMANCE AND DIMENSION. CONTRACTOR SHALL BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING. REQUEST FOR SUBSTITU- TIONS SHALL BE SUBMITTED IN WIRITING TO THE ARCHITECT /ENGINEER, DEMOSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN, CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK FOR OTHER TRADES, CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY OF SUBSTITUTIONS; ARCHITECT /ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM.. CONTRACTOR SHALL PAY FOR ARCHITECT /ENGINEER EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR SUBSTITUTIONS. 3,- GUARANTEES: AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE OWNER. ENTIRE ELECTRICAL WORK, INCLUDING PARTS AND LABOR, SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION AND WORKMANSHIP. WHERE APPLICABLE, LONGER GUARANTEED FOR CERTAIN COMPONENTS SHALL APPLY AS REQUIRED AND NOT IRE REDUCED IN ANY WAY. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS AND /OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 1 KAIC NOTE: THIS CONTRACTOR SHALL COORDINATE WITH FPL THE KAIC AVAILABBLE AND INCREASE OR DECREASE THE KAIC ACCORDINGLY IN ALL DISCONNECTS, BREAKERS, ETC. PART 2 -- PRODUCTS: SHOP DRAWINGS: SUBMIT SHOP DRAWINGS OF THE FOLLOWING PRODUCTS: A. WIRING, CABLING, CONDUITS, RACEWAYS, FLOOR AND OUTLET BOXES. B. WIRING DEVICES: RECEPTACLES, OUTLETS, LIGHTSWITCHES, PLATES, TIME CLOCKS, PHOTOCELLS. DIMMERS, PLUGMOLD. C. LIGHTING FIXTURES. LAMPS, POLES AND BASES. r DISCONNECT SW ►ITCHES SHALL BE CONTINOUS DUTTY, QUICK -MADE, QUICK -BRAKE ACTION, LOCKABLE TYPE, AS MANUFACTURED BY GE, SQUARE -D. PROVIDE CURRENT LIMITING BUSS FUSES FOR MAIN SERVICE, DISCONNECTS DUAL ELEMENT FUSES FOR MOTOR DRIVEN MECHANICAL EQUIPMENT SIZED PER NAMEPLATE SIZING WITH EQUIPMENT BEFORE ACTUAL INSTALLATION. CONDUCTORS SHALL BE THWf /THWPN SOFT-DRAWN 98% CONDUCTIVITY COPPER INSTALLED IN CONDUIT, COLOR CODED PER "NEC" AND TRADE STANDARDS. MINIMUM SIZE SHALL RE #12 FOR POWER WIRING AND #14 FOR CONTROL CIRCUITS. PROVIDE #10 WIRES FOR 120V POWER CIRCUIT HOMERUNS LONGER THAN 100 FEET. 4 CONDUIT SHALL BE "RGS" OR "IMC" HOT- DIPPED GALVANIZED FOR ALL EXTERIOR LOCATIONS, WHERE EXPOSED TO PHYSICAL DAMAGE. ALL FITTING SHALL BE STEEL. "PVC" SCHEDULE 40 SHALL RE USED WHERE CONDUIT IS RUN IN CONCRETE SLABS; "PVC" MAY BE RUN UNDERGROUND WHERE BURIED 18" BELOW FINISHED GRADE, 24" UNDER VEHICULAR TRAFFIC AREAS. GREENFIELD TYPE FLEXIBLE METALLIC CONDUIT SHALL BE USED FOR MOTORS AND VIBRATING EQUIPMENT CONNECTIONS, NOT TO EXCEED 18 "; PROVIDE "PVC" JACKETED TYPE FOR EXTERIOR AND /OR MOISTURE EXPOSED LOCATIONS. 5 WIRING DEVICES SHALL BE SPECIFICATION GRADE, FLUSH MOUNTED, AS MANUFACTURED BY HUBBELL OR SLATER. DIMMERS SHALL BE LUTRON OR APPROVED EQUAL, 600Wf MINIMUM. SWITCHES SHALL BE GANGED TOGETHER IN THE SAME BOX. DIMMERS SHALL BE GROUPED TOGETHER IN SEPARATE BOXES; 60OW DIMMERS MAY BE GANGED TOGETHER NO MORE THAN TWO IN A BOX WHERE PREVIOUSLY APPROVED BY MANUFACTURER AND ENGINEER. 6.LIGHTING FIXTURES SHALL BE COMPLETE WITH ALL NECESSARY, BALLAST, WIRING, LAMP HOLDERS REFLECTORS, GLASSWARE, POLES AND MOUNTING ACCESSORIES AS REQUIRED TO PROVIDE A COMPLETE INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS FOR COLOR, FINISH AND EXACT MOUNTING DETAILS. 7•THIS CONTRACTOR SHALL COORDINATE WITH FP&L THE CONNECTION FOR THIS SERVICE AND REVISE INTERRUPTING CAPACITY AVAILABLE PRIOR INSTALLATION OF ALL DISCONNECTING DEVISES, AND INCREASE THE INTERRUPTING CAPACITY IN PANELS AND DISCONNECTING DEVISES [F REQUIRED. PART 3 - EXECUTION: 1.- CONDUIT RUNS, RACEWAYS AND PIPING SHALL DE CONCEALED IN WALLS, CEILINGS, SLABS AND PARTITIONS; NO RACEWAYS SHALL DE EXPOSED WITHIN INTERIOR SPACES EXCEPT FOR OPEN CEILING AREAS. 2.- ALL FEEDER SPLICES AND TERMINATIONS SHALL DE MADE MECHANICALLY USING COMPRESSION TYPE SLEEVES OR LUGS AND CONNECTION TO PANELS AND SWITCHES AS MANUFACTURED BY BUMDY SERVITS TYPE OR APPROVED EQUAL. ALL CABLES SHALL BE COPPER. 3,- GROUNDING AND BONDING SHALL COMPLY WITH "NEC 250 ". ALL METALLIC RACEWAYS SHALL BE GROUNDED AND BONDED PER "NEC 250 ". NON- METALLIC RACEWAYS SHALL BE PROVIDED WITH A GROUNDING CONDUCTOR SIZED PER "NEC 250.122 ". 4.- MOTORS, TRANSFORMERS AND MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH GREENFIELD FLEXIBLE CONNECTIONS, WfATERLIGHT WHERE EXPOSED TO MOISTURE AND WEATHER CONDITIONS. 5.- ELECTRICAL EQUIPMENT SPACE AND INSTALLATION SHALL BE ACCORDANCE WITH "NEC 110.26 AND 408 ". WIRING IN DUCTS, PLENUM AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH "NEC 300.22 ". 6.- ELECTRICAL COMPONENTS AND EQUIPMENT SHALL BE CLEARLY AND PERMANENTELY IDENTIFIED BY CONTRACTOR, USING THE UNIT OR APARTMENT NUMBER. INDICATE CIRCUIT DESIGNATION ON GLASS COVERED TYPED DIRECTORY HOLDER INSIDE ON PANELBOARD DOOR. MARK CONDUCTORS WITH PREPRINTED ADHESIVE MARKERS AS MANUFACTURED BY W.H. BRADY Co. OR THOMAS Jc BETTS. 7.- CONTRACTOR SHALL MAKE ALL NECEESSARY EXCAVATIONS, CUTTING AND REPATCHING AS REQUIRED FOR THE PROPER EXECUTION OF THIS WORK. PROVIDE PACKING AND FIRE RATED RETARDANT SEALER IN JOINTS AROUND SLEEVES, PIPING AND CONDUITS PENETRATING FIRE RATED FLOORS AND WALLS. 8.- TELEPHONE, SPEAKER AND OTHER SYSTEMS: PROVIDE PULL WIRE IN EMPTY CONDUIT AS NOTED ON PLANS. COORDINATE INSTALLATION WITH OWNER TO ASSURE INSTALLATION MEETS EQUIPMENT VENDOR'S REQUIREMENTS. 9.- OUTLETS AND ANY OTHER EQUIPMENT INSTALLED IN DEMISED FIRE RATED PARTITIONS, CAN NOT INSTALLED BACK -TO -BACK, BUT MUST BE MINIMUM 24" APART. 10.- RECEPTACLES SHALL BE GROUNDED TYPE. CONTRACTOR SHALL GROUND ALL RECEPTACLES AS PER 2004 NEC CODE SECTION 250.130 . GENERAL NOTE: I ELECTRICAL OUTLETS ON FIRE RATED AND /OR 4" PARTITION WALL SHALL BE POSITIONED SO THEY ARE NOT BACK --TO -BACK. INSTALL OUTLETS WITH A MINIMUM DISTANCE OF 24" BETWEEN EACH BOX. 1 � R CONN SMOKE DETECTOR NOTE ALL SMOKE DETECTORS SHALL BE 110V WITH BATTETY BACK UP AND INTERCONNECTED FROM AFCI (ARC FAULT CIRCUIT) AHEAD OF ALL SWITCHES. SMOKE DETECTORS MAY BE WITHIN 20FT OF A COOKING APPLIANCE AND NOT CLOSER THAN 3FT FROM THE DOOR TO BATHROOM[, WASHER /DRYER, KITCHEN AND A /C. THE ACTIVATION OF ANY SMOKE DETECTOR SHALL ACTIVATE THE OTHERS. . - / 1 T1lT n A T TT T NOTE SMOKE DETECTOR SHALL BE HARDWIRE (110 VOLT TYPE) TO A NON - SWITCHABLE AFCI (ARC FAULT CIRCUIT CIRCUIT WITH BATTERY BACK -UP AND SHALL NO BE CONNECTED ONTO THE LOAD SIDE OF GROUND FAULT CIRCUIT SHALL BE INTERCONNECTED AS SHOWN IN PARALLEL UNIT SMOKE DETECTOR CONNECTION DETAIL SCALE : N.T.O. ELECTRICAL RISER DIAGRAM NO SCALE ELECTRICAL GENERAL NOTES SCALE: NTS r • iC' • U • • 4 • v Y r . ,...� 4 • • U • • V r i � V • i V V • • v r •ii f f r • r • i i G • f • i u •i • w • • • . V v i Yur ••• r•• • s 1 .(Y 4 .•r• UiU.0 ar• •�,� • .+a•r . rufFU • vv• . cn ci- F CONSULTING: t u 0 a �y1 Z M Q T�Thh tz; a 4 M A o N 4 W CONSULTING: `�f u �y1 h M T�Thh tz; a 4 M A CD .0 I: a L� rz a P � � W � z a g o IL IL M O J � 4 to m W co V O n cc cc � �r� 4c va so q 03 LO sa R• `�f r1(�•IIII.r� row SCAU AN SHOM BRAvm DFG rM 2m MTE 11-W-0t SHEET: E-3 3 OF:3