08-1279(2)-010HEATING - VENTILATING & AIR CONDITIONING
NOTES AND SPECIFICATIONS
1— PROVIDE AND INSTALL A COMPLETE AIR CONDITIONING SYSTEM AS SHOW ON
PLANS WITH WORKMANSHIP TO MEET OR EXCEED ALL LOCAL CITY CODES. OR
F.H.C. CODES 2001 EDITION, AND INCLUDING THE LATEST EDITION OF
THE FLORIDA STATE ENERGY CODE REQUIREMENTS SUPERSEDE ALL OF THE
FOLLOWING.
2— ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST ISSUE
OF NFPA 90A, 90H, 70 SMACNA MANUALS.
3— IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY DETAILS OF
CONSTRUCTION. CONTRACTOR IS EXPECTED TO PROVIDE ALL ITEMS THAT ARE
REQUIRED FOR A COMPLETE AND WORKABLE HVAC SYSTEM TO THE EXTEND TO
WHICH THE PLANS INDICATE. IT IS THE CONTRACTOR RESPONSIBILITY TO
FURNISH ALL NECESSARY LABOR, MATERIALS AND MISCELLANEOUS ITEMS TO
PLACE ALL EQUIPMENT IN PROPER WORKING ORDER.
4— CONTRACTOR SHALL EXAM THE PLANS AND SPECIFICATIONS OF ALL TRADES
FOR PARTS OF WORK. IF ANY DISCREPANCIES EXIST BETWEEN DRAWINGS FOR
HIS WORK AND OR WORK OF OTHER TRADES, HE SHALL REPORT SUCH
DISCREPANCIES TO THE ENGINEER AND OBTAIN WRITTEN INSTRUCTION FOR
ANY CHANGES IN WORK COVERED BY THESE PLANS AND SPECIFICATIONS.
NEGLECT OR FAILURE OF CONTRACTOR TO REPORT SUCH DISCREPANCIES TO
THE ENGINEER PRIOR TO BIDDING SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
5— CONTRACTOR SHALL PROVIDE ALL FEES, PERMITS AND INSURANCE AND
SUBMIT TO THE OWNER AN UNCONDITIONAL WRITTEN GUARANTEE FOR THE
REPAIR OR REPLACEMENT OF DEFECTIVE WORKMANSHIP AND MATERIALS
PROVIDED UNDER THIS CONTRACT FOR A PERIOD OF ONE YEAR AFTER THE
DATE OF ACCEPTANCE BY THE OWNER.
6— CONTRACTOR SHALL SUBMIT TO THE OWNER THE FOLLOWING SHOP
DRAWINGS AND PRODUCT DATA PRIOR TO ORDERING OR COMMENCING WITH
THE WORK:
A— DUCT MATERIALS AND ACCESSORIES
B— DIFFUSERS, GRILLS AND REGISTERS.
C— FIRE DAMPERS.
D— ALL EQUIPMENT SUCH AS A.H.U., C.U., FANS, VAV'S, THERMOSTATS ETC.
7— THE FIVE YEAR FACTORY WARRANTY OF THE COMPRESSOR MOTORS SHALL
BE FILLED OUT IN THE NAME OF THE OWNER. THIS CONTRACTOR SHALL ALSO
FURNISH TO THE OWNER ALL CERTIFICATES OF FINAL INSPECTIONS AND
APPROVAL FROM THE INSPECTION AUTHORITIES HAVING JURISDICTION. THE
INSTALLATION ACCEPTANCE FORMAT WHICH ACCOMPANIES THE EQUIPMENT
FROM THE FACTORY SHALL BE FILLED OUT AND FURNISHED TO THE OWNER. /2\
8— THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING
THE NECESSARY CONDENSATE DRAIN LINE FROM THE APPARATUS TO THE
EXTERIOR OF THE BUILDING WHETHER SHOWN ON PLANS. UTILIZE PVC OR
COPPER MATERIAL DEPENDING THE CEILING FIRE RATING OR THE USE OF A
RETURN AIR PLENUM, CONSULT LOCAL CODE REQUIREMENTS. CONDENSATE
DRAIN PIPING SHALL BE INSULATED WITH FIRE RESISTIVE 3/4" THICK FOAM
PLASTIC INSULATION.
9— WHERE CALLED FOR ON PLANS OR THE USE OF FIBERGLASS IS APPROVED BY
LOCAL CODE REQUIREMENTS, FIBERGLASS DUCT SHALL BE 1 1/2 THICK RIGID
FIBROUS GLASS WITH ALUMINUM FOIL. GLASS SCRIM AND DRAFT OR PLASTIC
JACKET VAPOR BARRIER. THE "K" VALUE OF THE DUCT SHALL BE 0.23 BTU /IN /SQ.
FT. /DEG F /HR. MINIMUM RATING AT 75 DEGREES. R -6 MIN.
10— EXHAUST DUCTS SHALL BE GALVANIZED STEEL LOCK FORMING QUALITY,
HAVING ZINC COATING OF 1.26 OUNCES PER SQUIRE FOOT FOR EACH SIDE.
11— REFRIGERANT LIQUID LINES BELOW 5/8" O.D. SIZE TO BE ACR TYPE L. SOFT
COPPER LIQUID LINES 5/8" O.D. AND LARGER AND ALL SUCTION LINES SHALL BE
ACR TYPE L HARD COPPER, 15% SILFLOS TO BE USE FOR WELDING OF
REFRIGERANT PIPING ALL SUCTION LINES TO BE INSULATED WITH A MINIMUM
1/2 THICK ARMAFLEX OR EQUAL ROUGH —IN AND PRESSURE TEST ALL
REFRIGERANT LINES WITH A 75 PSI PRESSURE, PRIOR TO CLOSING OFF THE
REFRIGERANT LINES TO HOLD CHARGE FOR A MINIMUM OF 24 HOURS
SIZE OF REFRIGERANT LINES TO BE AS PER MANUFACTURER RECOMMENDATIONS
FOR THE ACTUAL LENGTH OF PIPE.
12— CONTRACTOR TO VERIFY EXISTING FIELD CONDITIONS BEFORE BIDDING THE
PROJECT, FAILURE TO DO WILL RESULT THAT NECESSARY FIELD
MODIFICATIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
13 -ALL EQUIPMENT SUPPORTS SHOWN ON PLANS ARE DIAGRAMMATIC AND
REQUIRE APPROVAL OF ARCHITECTS, STRUCTURAL ENGINEER AND EQUIPMENT
MANUFACTURER PRIOR TO HANGING.
14— CONTRACTOR TO VERIFY WITH THE ARCHITECT OF RECORD THE
CEILING /FLOOR FIRE RATING TO DETERMINE REQUIREMENTS FOR FIRE
DAMPERS, BEFORE BEGINNING WORK.
15— THERMOSTAT TO BE MANUFACTURED BY HONEYWELL OR EQ.
THERMOSTAT LOCATION TO BE APPROVED BY ARCHITECT PRIOR TO
INSTALLATION .
16 —A /C CONTRACTOR TO VERIFY WITH ARCHITECT THE UNITS EER RATING
REQUIRED BASED ON FLORIDA ENERGY CODE COMPLIANCE
HVAC SYMBOLS
125 CFM
C SUPPLY AIR DIFFUSER
EF -1
EXHAUST FAN
k,U SXB` =._ FIBERGLASS A/C DUCT
INSULATION NOTE:
PROVIDE MINIMUM
INSULATION OF
R -4.1 IN WALLS
R -30 IN CEILING.
FLEXIBLE A/C DUCT
Boo
OT PROGRAMABLE THERMOSTAT, INSTALL 48" A.F.F.
o- - - RL - - -o REFRIGERATION LINES. PROVIDE "L" COPPER LINES
FOR REFRIGERANT. PROVIDE 6" PVC SCH -40 SLEEVE.
PROVIDE A MIN. OF 3/4" PERMAFLEX INSULATION
SEE UNITS SCHEDULE FOR SIZE.
INTERLOCK CONTROL OF EACH EXHAUST FAN TO
LIGHT SWITCHES EACH BATHROOM. TERMINATE
W /GOOSNECK & INSERT SCREEN. INSTALL 6 "0 DUCT.
NOTES:
1.- PROVIDE THERMOSTAT WITH SUB -BASE.
2.- PROVIDE SOLENOID VALVES, ACCUMULATORS AND OTHER
ACCESSORIES RECOMMENDED BY MFGR. FOR PROPER
OPERATION.
3.- APPROVED EQUAL MANUFACT'URERS ARE ACCEPTABLE.
4.- PROVIDE ACRYLIC COATING ON ALL PARTS OF AHU'S
AND CU'S INCLUDING COILSi AND FINS.
SPECIAL NOTE:
1.— MAXIMUM LENGTH ON DRYER DUCTS TO BE 25' W/
2 ELBOWS MAXIMUM.
2.— PROVIDE 4" CLEARANCE IN ALL AHU ENCLOSURES.
HVAC DESIGN REQUIREMENTS
YES
NO
DUCT SMOKE DETECTORS
COMPRESSOR
X
FIRE DAMPERS
FLA
X
SMOKE DAMPERS
2.5
X
FIRE RATED ENCLOSURE
CEILING ASSEMBLY
1
X
FIRE STOPPING
0010.
X
SMOKE CONTROL
X
Q
h�
h
li V O
TEST AND BALANCE NOTE:
1. THIS CONTRACTOR SHALL PROVIDE A INDEPENDENT TEST AND BALANCE WHERE INDICATED
ON THIS DRAWING TO ASSURE THE REQUIRED AMOUNT OF "CFM" ARE PROVIDED AND NOTIFY
OF ANY CONFLICT TO REACH THE AMOUNT OF "CFM" REQUIRED.
STEEL COVER PLATE
U o p o p c
O O D
O O O O
o °
0
0
° ° o
o °
0 0
� p O
° o
v
o ° p
O p O
� ° O
� o
°
° o
0 0 0
0
0 0
0
GRADE
CONDENSATE DRAIN
LINE FROM BUILDING
SEE PLAN FOR SIZE.
24" DIAMETER CONCRETE
OR CLAY PIPE FILLED
WITH 3/4" CRUSHED ROCK
CONDENSATE SOAKAGE
PIT DETAIL
N.T.S.
SUPPLY D
STEM
SCHEDUI
AIR COOLED CONDENSIN(
CARRIER
MODEL
NUMBER
COMPRESSOR
NO.
TONS
FLA
fBR330A000
1
2.5
16.0
IBR31BA0013
1
1.5
7.00
1. PROVIDE FACTORY PRE - FABRICATED SOUND ATTENUATION ROOF CURB
2. PROVIDE DISCONNECT SWITCH
3. PROVIDE FAN SPEED CONTROLLER MOUNTED ON UNIT CASING
4. BACKDRAFT DAMPER
WALL
DRAIN FROM SECONDARY
DRAIN PAN LINE TO RESERVOIR
ATTACHED TO SIDE OF AHU.
PAN TO BE MIN. i -1d2' PEEP
AND CONSTR. OF 0.0 767
GALV. BHT METAL W/ FLOAT
SWITCH .
RETURN AIR
PLENUM
RETURN DUCT.
r
CEILING
�I
FLEX— CONNECTION
IAIR HANDLING UNIT
REFRIGERANT LINES
I CONDENSATE DRAIN
(CONDENSATE TRAP
NEOPRENE PAD
ANGLE1 F4RAMEEEL
ONLY ON SECOND FLOOR
AIRHANDLING UNIT
N.T.S.
1 -1/2 "X22 GAUGE METAL
STRAP ANCHORD TO SLAB
_W /SPANSION ANCH. ® 6FT.
MAX.
IMAX 8 FT. SPACING
BETW. SUPPORT
GAL. METAL STRAP
SUPPORT W /METAL
a
i
Y FIBER GLASS CLOSER MAXIMUM INTERVALS MAY
LOW VELOCITY
DUCT R -6 INS. MIN. BE SPECIFIED AS A CONDITION OF
U.L. LISTING, PARTICULARLY IN
FIRE RATED FLOOR- CEILING
ASSEMBLIES.
FIBER GLASS HANGERS FOR DUCTS DETAIL
1 -1/2 ' X22 GAUGE METAL
STRAP ANCHORD TO SLAB
W /SPANSION ANCH. ® 6FT.
MAX.
MAX 5 FT. SPACING
BETW. SUPPORT
7RIGID FIBERGLASS DUCT (R-
METAL ROUND FITTING
QUADRANT OPERATOR TO
OUTSIDE INSULATION
PROVIDE INSULATION GUA
WHERE NECESSARY
1" AUXILIARY PAN DRAIN
SEAL JOINT W/
DUCT SEALER AND
rAPE
SULATED FLEX. DUCT GI
IV2" WITH POLYETHYLE]
STEEL WIRE REINFOR
')EAL JOINT WITH DUCT
IEALER AND TAPE
;RFORATED DIFFUSER W,
'POSED BLADE DAMPER
IAPTER ROUND TO SQUA
(IF REQUIRED)
TYPICAL TURNINI
ON ALL ELBOWS
CORNER ANGLE
TYPICAL FIBERG...., L...,.
ELBOW TURNING VANE DETAIL
N_T_S_
GAL. METAL STRAP SUPPORT
W /METAL SCREW
�- -LOW VELOCITY FLEXIBLE DUCT
R -6 INS. MIN.
FLEXIBLE DUCT SUPPORT DETAIL
N.T.S.
V0 2 ELECTRICAL
DUIT BY OTHER
FAN COIL UNIT
8" (Typ) AT CEILING
n
L FLOAT SWITCH AUXILIARY DRAIN PAN
MADISON MODEL NO. 2XC13 GALVANIZED SHEET
SHUT -OFF FAN AT 1" WATER LEVEL METAL MIN. 0.0278'
AUXILARY DRAIN PAN DETAIL
N.T.S.
ALUM. WEATHER CAP
BIRDSCRF
AWED IS
VERT. 22 GA. C
SOLDER
FLEXIBLE DUCT CONNECTION DETAIL
N.T.S.
NOTE: ALL BRANCH DUCT TAKE -OFF SHALL HAVE
A LOW LOSS BRANCH CONNECTION.
T I
BATH EXHAUST
N.T.S. (BATH EXH. DUCT TERMINATION)
INSULATION
SLAB
w ,BATH EXH. DUCT
MECHANICAL GENERAL NOTES
SCALE: NTS
FAN SCHEDULE
1`
MODEL
CFM
ESP
AMPS
ELECTRICAL
DRIVE
RPM
TIP SP
BONES
REMARKS
MARK
NUMBER
_
v.
0010.
c
VOLTS -PH -HZ
Q
h�
h
li V O
EF -1
GREENHECK
50
0.125
0.80 A
120 -1 -60
DIRECT
1,500
- --
3.4
2,3,4
i
SP -8
Q
n M
a
1. PROVIDE FACTORY PRE - FABRICATED SOUND ATTENUATION ROOF CURB
2. PROVIDE DISCONNECT SWITCH
3. PROVIDE FAN SPEED CONTROLLER MOUNTED ON UNIT CASING
4. BACKDRAFT DAMPER
WALL
DRAIN FROM SECONDARY
DRAIN PAN LINE TO RESERVOIR
ATTACHED TO SIDE OF AHU.
PAN TO BE MIN. i -1d2' PEEP
AND CONSTR. OF 0.0 767
GALV. BHT METAL W/ FLOAT
SWITCH .
RETURN AIR
PLENUM
RETURN DUCT.
r
CEILING
�I
FLEX— CONNECTION
IAIR HANDLING UNIT
REFRIGERANT LINES
I CONDENSATE DRAIN
(CONDENSATE TRAP
NEOPRENE PAD
ANGLE1 F4RAMEEEL
ONLY ON SECOND FLOOR
AIRHANDLING UNIT
N.T.S.
1 -1/2 "X22 GAUGE METAL
STRAP ANCHORD TO SLAB
_W /SPANSION ANCH. ® 6FT.
MAX.
IMAX 8 FT. SPACING
BETW. SUPPORT
GAL. METAL STRAP
SUPPORT W /METAL
a
i
Y FIBER GLASS CLOSER MAXIMUM INTERVALS MAY
LOW VELOCITY
DUCT R -6 INS. MIN. BE SPECIFIED AS A CONDITION OF
U.L. LISTING, PARTICULARLY IN
FIRE RATED FLOOR- CEILING
ASSEMBLIES.
FIBER GLASS HANGERS FOR DUCTS DETAIL
1 -1/2 ' X22 GAUGE METAL
STRAP ANCHORD TO SLAB
W /SPANSION ANCH. ® 6FT.
MAX.
MAX 5 FT. SPACING
BETW. SUPPORT
7RIGID FIBERGLASS DUCT (R-
METAL ROUND FITTING
QUADRANT OPERATOR TO
OUTSIDE INSULATION
PROVIDE INSULATION GUA
WHERE NECESSARY
1" AUXILIARY PAN DRAIN
SEAL JOINT W/
DUCT SEALER AND
rAPE
SULATED FLEX. DUCT GI
IV2" WITH POLYETHYLE]
STEEL WIRE REINFOR
')EAL JOINT WITH DUCT
IEALER AND TAPE
;RFORATED DIFFUSER W,
'POSED BLADE DAMPER
IAPTER ROUND TO SQUA
(IF REQUIRED)
TYPICAL TURNINI
ON ALL ELBOWS
CORNER ANGLE
TYPICAL FIBERG...., L...,.
ELBOW TURNING VANE DETAIL
N_T_S_
GAL. METAL STRAP SUPPORT
W /METAL SCREW
�- -LOW VELOCITY FLEXIBLE DUCT
R -6 INS. MIN.
FLEXIBLE DUCT SUPPORT DETAIL
N.T.S.
V0 2 ELECTRICAL
DUIT BY OTHER
FAN COIL UNIT
8" (Typ) AT CEILING
n
L FLOAT SWITCH AUXILIARY DRAIN PAN
MADISON MODEL NO. 2XC13 GALVANIZED SHEET
SHUT -OFF FAN AT 1" WATER LEVEL METAL MIN. 0.0278'
AUXILARY DRAIN PAN DETAIL
N.T.S.
ALUM. WEATHER CAP
BIRDSCRF
AWED IS
VERT. 22 GA. C
SOLDER
FLEXIBLE DUCT CONNECTION DETAIL
N.T.S.
NOTE: ALL BRANCH DUCT TAKE -OFF SHALL HAVE
A LOW LOSS BRANCH CONNECTION.
T I
BATH EXHAUST
N.T.S. (BATH EXH. DUCT TERMINATION)
INSULATION
SLAB
w ,BATH EXH. DUCT
MECHANICAL GENERAL NOTES
SCALE: NTS
CONSULTING:
e�
1`
h
8
O
=M
E
o
W
N `?