PLUMBING GENERAL. NOTES:
U
��v t Jas
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT
NECESSARY FOR THE INSTALLATION OF A COMPLETE PLUMBING SYSTEM IN
ACCORDANCE WITH THESE DRAWINGS, THE APPLICABLE EDITION OF THE
FLORIDA BUILDING CODE 2001, ALL OTHER APPLICABLE STATE, COUNTY
AND LOCAL CODES AND ORDINANCES.
2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND
ALL OTHER COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS
WORK. UPON FINAL ACCEPTANCE, A CERTIFICATE FROM THE LOCAL
INSPECTION AUTHORITY SHALL BE FURNISHED TO THE OWNER.
3. ALL MATERIALS AND EQUIPMENTS SHALL BE NEW, OF U.S. MANUFACTURER
AND OF GOOD QUALITY OF RESPECTIVE KIND AND GRADE, AND MUST BE
FURNISHED SO AS TO PREVENT ANY DEALAY IN THE PROGRESS OF THE
WORK. ALL WORK THROUGHOUT SHALL BE PERFORMED IN A WORKMAN— , 1'Cr
f
LIKE MANNER BY SUFFICIENT NUMBER OF SKILLED WORKMEN.
4. CONTRACTOR SHALL VISIT THE SITE AND REVIEW ALL PERTINENT UTILITY
DRAWINGS TO FAMILIARIZE HIMSELF WITH THE LOCATION OF ALL EXISTING -
AND /OR PROPOSED UTILITY STUB OUTS, PIPING, EQUIPMENT, ETC., AND
MAKE DUE ALLOWANCES FOR ANY CONDITION AFFECTING HIS WORK.
�".
5. ALL UNDERGROUND SANITARY & STORM DRAINAGE PIPING AND FITTINGS
SHALL BE PVC -DWV (ASTM D- 2662/D- 3034).
6. ALL ABOVE GROUND SANITARY & STORM DRAINAGE BRANCH & VENT
PIPES AND FITTINGS SHALL BE PVC —DWV (ASTM D- 2662/D -- 3034).
7. ALL UNDERGROUND WATER PIPING SHALL BE COPPER TYPE "K" ASTM
B -306), ALL ABOVE GROUND PIPING SHALL BE COPPER TYPE 'L"
(ASTM Ba -306).
8. ALL HOT WATER PRESSURE AND TEMPERATURE RELIEF PIPING SHALL BE
;
COPPER TYPE "K" (ASTM 8 -306), A� zl
9. ALL AIR CONDITIONING CONDENSATE DRAINAGE PIPING SHALL BE SCH. 40
PVC (ASTM D- 2662), EXCEPT WHEN INSTALLED IN RETURN AIR PLENUM p,..% ...%
WHERE COPPER TYPE "DWV OR EQUIVALENT MUST BE USED.
10. ALL PLUMBING FIXTURES SHALL BE PROVIDED WITH ALL NECESSARY
ACCESSORIES SUCH AS STOP VALVES, P TRAPS, SUPPORTS, P & T
VALVES, ETC., AS REQUIRED. ALL EXPOSED PIPING AT FIXTURES AND ! �t
EQUIPMENT SHALL BE CHROME PLATED BRASS PIPE OR TUBE. PROVIDE `R I
SHUT OFF VALVES AND UNIONS TO ALL FIXTURES, ETC., REQUIRING
WATER SUPPLY. PROVIDE DIELECTRIC COUPLINGS AS REQUIRED, FOR
ALL COPPER PIPING CONTRACTOR MUST USE 95/5 SOLDER. PROVIDE
WATER HAMMER ARRESTOR TO EACH FIXTURE AS REQUIRED." �
:.... j
11. PROVIDE CLEANOUTS (WITH CHROME PLATED WALL OR FLOOR ACCESS �
FRAMES AND COVERS AS REQUIRED) AT THE BASE OF ALL WASTE t
AND /OR VENT STACKS. PROVIDE PITCH PANS & LEADS FLASHING FOR
ALL SANITARY SYSTEM VENTS,
12. ALL HORIZONTAL WASTE PIPING SHALL BE, SLOPPED AT 1/8 PER FOOT,
.... %,d .
UNLESS OTHERWISE .NOTED.
13. CONTRACTOR SHALL VERIFY SLOPE AND DEPTHS AND LOCATIONS OF {
CONNECTION POINTS TO EXISTING PRESSURE OR DRAINAGE LINES
BEFORE STARTING WORK.
� NT
y,✓ w4§
.i.
.w.. —v..
1
NOTES,,
1. RUN 1 -1/2" PIPE @ 1/4' FT. FIXTURE ARM'-
- s
2. RUN 2" PIPE @ 1/4!' FT.
{
3, RUN 3 PIPE. C 1/8" hiXJ G:, 1
?A'
RUN 4 P
I
5. PROVIDE CLEANOUT AT BASE OF EACH SOIL - 4I::
AND WASTE STACK.
I
'•'1
6. SHOWERS & TUBS VALVES TO BE ANTI-SCALD _
TYPE.
7. INSTALL 1 /2" CW AT RIGHT SIDE OF FIXTURES..
PROVIDE WATER HAMMER ARRESTORS.
8. INSTALL 1 /2" HW AT LEFT SIDE OF FIXTURES.
PROVIDE WATER HAMMER ARRESTOR.