Loading...
05-1465-0257"RElll CO F- RATING = 2 HR. T- RATING = O HR, Q PRE -RATED CONCRETE FLOORS OR BLOCK WALLS = MIN. 4 -1/2" THICK, WITH ANNULAR SPACE RANGE OF O" TO 7/8 ". ® CONDUIT - NOM. 4' DIA. (OR SMALLER) STEEL CONDUIT OR EMT. Q PACKING MATERIAL - MINERAL WOOL (MIN. 4 PCF) COMPRESSED MIN. 50% AND INSTALLED INTO THE OPENING TO OBTAIN MIN. 4" THICKNESS. ® T12EMCO u T12EMSTOP ACRYLIC - MIN. 1/2" SEALANT APPLIED WITHIN ANNULUS, AND A MINIMUM 1/4" SEALANT APPLIED AT POINT CONTACT: AT THE FLOOR SURFACE FOR FLOORS, OR BOTH SURFACES FOR WALLS. F- RATING - I AND 2 HR. T- RATING - ^ ' '� UL tt WLI( 401 TREIIlCO, (DI OR 2 - HOUR FIRE RATED GYPSUM WALLBOARD /STUD ASSEMBLY (ANGULAR SPACE RANGE, MIN. 1/4" TO MAX. 5/8 ") Q CONDUIT - 4" DIAM.(OR SMALLER) EMT OR RIGID STEEL © T12EMCO U FIRE - SHIELD - MIN. 112" THICKNESS OF SEALANT INSTALLED WITHIN OPENING WITH A MIN. OF 1/4" CROWN AROUND GROUND THE PENETRATING ITEM APPLIED FLUSH WITH BOTH SIDE OF WALL ASSEMBLY. F- RATING = 2 HR. T- RATING = CHI �m TREI11CO3 IQ WALL ASSEMBLY = 5" THICK CONCRETE, WITH MAX AREA OF OPENING 35.75 SO. IN. Q 6TEEL PIPE - 2" DIAM. (OR SMALLER) SCH. 5 OR HEAVIER. CONDUIT - 2" DIAM. (OR SMALLER) EMT. MAX. 5 PIPES OR CONDUITS. Q A) STEEL SLEEVE - NO. 30 MSG GALV. SHEET FITTED WITHIN OPENING AND SECURED TO BOTH SIDES OF WALL. B) PACKING MATERIAL - MIN. 4" THICKNESS CERAMIC FIBER INSULATION (6 PCF) FRICTION FITTED. C) MIN. '' - HICKNESS FIRE - SHIELD OR FIRE -SEAL, WITH i CROWN FORMED AROUND PENETRATING ITEMS. TYPE: QO LOAD CENTER VOLTS: 120/24OV, 10. 3W MTG: SURFACE PANEL "A" 135K AICI BUS: 2P-150A M.C.B. CU BUS/GND. BUS (2181 SQ. LOAD COND. WIRE TRIP POLE DESCRIPTION- CKT No. CKT No. POLE TRIP WIRE COND. LOAD . : ®NIM 6 ' SSW 2 AHU #2 ( * *) 1 2 CU #2 ( * *) 2 40 8 3/4" 4320 1500 1/2" 12 �� 1 WASHER ©0 6 DRYER WE �0� 10 3/4" mmmmm 1/2" 12 20 1 LAUNDRY RECS. oa 8 mmmm� * 12 20 SMALL APPLIANCES BATH RECS. 9 REFRIGERATOR GEN LTS / RECS. 1 15 14 1/2" * 1 11 12 ■■■■■■■■■■ * GEN LTS / RECS. ®� 14 GARBAGE DISPOSAL 0101 ■1■ ■ ■■ ' * GARAGE DOOR GENERAL LTS/RECS. 15 16 GARAGE DOOR 17 18 SMALL APPLIANCES * 19 © ®m ®0101 ®® ■■■■■■■■© * ©■■■■■■■■ 21 22 =�INIMEIM 01110■■■■■© 1600 ©■■■■■■■■ WHIRLPOOL (GFI) 23 24 ®� 101101101■■© * 1/2" 10 20 1 FLOOD LTS O■■■■■■■■ 26 ®� * 011101011010 10 20 1 FLOOD LTS. 27 28 WATER HEATER 1001 ©■■■■■■■■ 10 3/4" 4500 * 3/4" 12 20 1 L. SCAPE J. BOXES 29 ICN�1010010 1010111011001001 * 3/4" 12 20 1 O■■■■■■■■ 31 32 POOL PUMP 2 30 10 3/4" 2800 * 1/2- ®® 20 BAT HROOM Om®®© 33 34 O■■■■■■■■ -- -- -- -- -- SPACE 35 ®� REFRIGERATOR GENERAL RECS. Om 12 ®®© 1400 ©■■■■■■■■ ®m 38 • ' mmMMIIMMMMI 20 12 1/2" IIMMMMIMMIMMIMMI ++ 39 40 SPACE -- -- -- -- -- 41 42 NOTES: 1. ( *) PART OF THE 3W /SQ.FT. LOAD 2. ( * *) PROVIDE HACR TYPE BREAKER 3. (o) PROVIDE AFCI TYPE BREAKERS TYPE: SQ'D QO LOAD CENTER VOLTS: 120/24OV, 0, 3W MTG: SURFACE PANEL •B° I35K AIC) BUS: 2P -150A M.C.B. CU BUS /GND. BUS (1890 SQ. FT.) LOAD: (SEE LOAD ANALYSIS) LOAD COND. WIRE TRIP POLE DESCRIPTION CKT No. CKT No. POLE TRIP WIRE COND. LOAD 11175 1" 6 60 2 AHU #2 ( * *) 1 2 CU #2 ( * *) 2 40 8 3/4" 4320 1500 1/2" 12 20 1 WASHER 5 6 DRYER 2 30 10 3/4" 5000 1600 1/2" 12 20 1 LAUNDRY RECS. 7 8 * 12 20 1 BATH RECS. 9 10 GEN LTS / RECS. 1 15 14 1/2" * 1 11 12 * GEN LTS / RECS. 13 14 * 15 16 * 17 18 * 19 20 * 21 22 1600 WHIRLPOOL (GFI) 23 24 * 1/2" 10 20 1 FLOOD LTS 25 26 * 1/2" 10 20 1 FLOOD LTS. 27 28 WATER HEATER 2 30 10 3/4" 4500 * 3/4" 12 20 1 L. SCAPE J. BOXES 29 30 * 3/4" 12 20 1 31 32 POOL PUMP 2 30 10 3/4" 2800 * 1/2- 10 20 1 1 POOL LTS (GFI) 33 34 -- -- -- -- -- SPACE 35 36 REFRIGERATOR 1 20 12 1/2" 1400 37 38 BAR RECS. 1 20 12 1/2" ++ 39 40 SPACE -- -- -- -- -- 41 42 FIRE AND /OR SMOKE RATED WALL OR FLOOR PENETRATION DETAILS NOTES: 1. ( *) PART OF THE 3W /SQ.FT. LOAD 2. ( * *) PROVIDE HACR TYPE BREAKER 3. PROVIDE AFCI TYPE BREAKERS "SUBJECT TO. FIELD INSPECTION'► NEW FPL DOUBLE LUG METER EXTERIOR GARAGE 001 O (3R) SMW Na NEW PANEL M E -3 0 NEW PANEL =4--2,.4,—.w 2P -150A M.C.B. SERVICE RATED FOR 35K AIC 3 #1/0 & 1 #6(G) — 2 "C �J_t— 1 #2 (G) — 3/4 "C TO _ (2) 5/8" DIA. X 10 FT LONG COPPER 3# 250 MCM — 3 "C GND STEEL GND DRIVEN RODS SPACED TO FPL SERVICE 6 FT APART, C.W.P. AND FOUNDATION POINT STEEL ELECTRICAL RISER DIAGRAM KTA NOTES: 1. ENGINEER ASSUMED A FAULT CURRENT OF 35K AIC. CONTRACTOR SHALL COORDINATE WITH FPL FOR ACTUAL FAULT CURRENT. EQUIPMENT INSTALLED SHALL WITHSTAND FPL'S AVAILABLE FAULT CURRENT. 2. ALL EQUIPMENT AND DEVICES SHALL BE MOUNTED ABOVE FLOOD CRITERIA. LOAD ANALYSIS BASED ON 120/24OV, 10, 3W I.) PANEL "A" 2181 SQ.FT. X 3W /SQ.FT. OTHER LOADS DEMAND LOAD (NEC 220 -30) 1ST 10KVA ® 100% 24,743 VA ® 40% A/C ® 65% HEAT NEW PANEL "B" 1890 SQ.FT. X 3W /SQ.FT. OTHER LOADS DEMAND LOAD (NEC 220 -30) 1ST 10KVA ® 100% 9,470 VA ® 40% A/C ® 65% HEAT SERVICE LOAD BASED ON 120/24OV, 0, 3W =6,543 VA 2BIQ VA 10,000 VA 9,897 VA 8,156 VA 28,053 VA /240V = 116.9 A 5,670 VA 13,800 VA 19,470 VA 10,000 VA 3,788 VA 8,156 VA 21,944 VA /240V = 91.4 VA PANEL "A" 28,100 VA PANEL "B" 21,944 VA 50,044 VA /240 V = 208.5 A N 0) �O G � ~'� �� .` rT Esc, • • rI•����/ / /� /' / /� //�' I i L1�1��1 i•'r?�a`TC] v�1il:I.l�lii;� -?TA7 YO Q VOR�1 A I �lA7183'�Wi�`: =F� 1,q 1y*.t Ijq JMM Consulting Engineers LLC Certificate OF Authorization #9692 Jose M. Martinez, P.E. #56018 7985 S.W. 136th STREET TEL (305) 255 -1621 Miami, Florida 33156 FAX (305) 255 -1732 TO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF 'JMM CONSULTING ENGINEERS LLC* AND IS AN INSTRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF JMM CONSULTING ENGINNERS, LLC. _ J LLI 09, Li w U Z w rrww V, V H 1�1 x V PEVEr 1181' RflVl�B AM 1ff SMW Na E -3 0 FM =4--2,.4,—.w