07-421-009LEGEND
SYMBOL DESCRIPTION MOUNTING
HEIGHT
LIGHTING
F5
NUMBER DESIGNATES FIXTURE TYPE - SEE LIGHTING FIXTURE
SCHEDULE
SYSTEM
F5
ALL FIXTURES IN THIS SPACE SHALL BE THE SAME TYPE INDICATED
EXTENT OF
CONDUITe
O
®SURFACE
3' -10'
AFF TO CL
OR RECESSED FLUORESCENT
FIXTURE (TYPE DETERMINES MOUNTING)
FIRE ALARM MANUAL PULL STATION - KEY OPERATED
3' -10'
AFF TO CL
®SURFACE
FIRE ALARM 10' BELL
OR RECESSED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT FIXTURE (TYPE DETERMINES MOUNTING)
FD
FIRE ALARM CHIME WITH LIGHT
®SURFACE
®
OR RECESSED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT W/ BATT. BACKUP. FIXTURE (TYPE DETERMINES MOUNTING)
VENDOR
O4
0
0
SURFACE OR RECESSED FLUORESCENT
FIXTURE (TYPE DETERMINES MOUNTING)
FIRE ALARM SPEAKER
THROUGHOUT
®
®
CIRCUIIT FIXTURE (TYPE FLUORESCENT E DETERMINES OUNTING)TED TO EMERGENCY
"E
® ®
SURFACE OR RECESSED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT W/ BATT. BACKUP. FIXTURE (TYPE DETERMINES MOUNTING)
OH
®
SURFACE OR SUSPENDED FLUORESCENT FIXTURE (TYPE DETERMINES
MOUNTING)
is
®
SORFACE OR SUSPENDED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT. FIXTURE (TYPE DETERMINES MOUNTING)
EDR
®
SURFACE OR SUSPENDED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT W/ BATT. BACKUP. FIXTURE (TYPE DETERMINES MOUNTING)
RI
[ Q
WALL BRACKET FIXTURE
FS-A-11
SMOKE DETECTOR ALARM REMOTE INDICATOR /TEST SWITCH
CIRCUIT RACKET FIXTURE CONNECTED TO EMERGENCY
SPRINKLER SYSTEM VALVE STATUS SWITCH
WALL BRACKET FIXTURE CONNECTED TO EMERGENCY
CIRCUIT W/ BATT. BACKUP.
Fs
®�
EXIT LIGHT, PROVIDE DIRECTIONAL ARROWS AS INDICATED
ON PLANS
FACP I
'D
POLE MOUNTED LIGHT FIXTURE
FAAN
SWITCHES
S
SINGLE POLE SWITCH - IVORY TOGGLE
3' -10'
AFF TO CL
SINGLE POLE SWITCH - RED TOGGLE
3' -10'
AFF TO CL
S2
DOUBLE POLE SWITCH - CENTER OFF
3' -10'
AFF TO CL
S3
THREE WAY SWITCH - IVORY TOGGLE
3' -10'
AFF TO CL
$T
MOTOR RATED SWITCH WITH THERMAL OVERLOAD
SD
DIMMER SWITCH
3' -10'
AFF TO CL
$IT
INTERVAL TIMER SWITCH
3' -10'
AFF TO CL
POWER - RECECPTACLES
AS NOTED
SEE SPECS.
120V. DUPLEX RECEPTACLE - IVORY (REFER TO RECEPTACLE
ABBREVIATIONS FOR EXCEPTIONS)
1' -6'
AFF TO CL
V -6'
AFF TO CL
120V. DUPLEX RECEPTACLE - IVORY - SPECIAL MOUNTING HEIGHT
(REFER TO RECEPTACLE ABBREVIATIONS FOR EXCEPTIONS)
AS NOTED OR
SEE SPECS
AS NOTED
SEE SPECS.
120V. OUADPLEX RECEPTACLE - IVORY (REFER TO RECEPTACLE
ABBREVIATIONS FOR EXCEPTIONS)
V -6'
AFF TO CL
120V. OUADPLEX RECEPTACLE - IVORY - SPECIAL MOUNTING HEIGHT
(REFER TO RECEPTACLE ABBREVIATIONS FOR EXCEPTIONS)
AS NOTED OR
SEE SPECS
e--
SPECIAL RECEPTACLE (TYPE AS NOTED)
AS NOTED OR
SEE SPECS
�--
120V. GFI RECEPTACLE (SPECIAL MOUNTING HEIGHT)
AS NOTED OR
SEE SPECS
O—
120V. GFI RECEPTACLE
V -6'
AFF TO CL
Q
JUNCTION BOX
GB
GROUNDING COLLECTION BUS
- - --
EXPOSED CONDUIT ON WALL OR CEILING
SOUND SYSTEM
Ps
CEILING PAGING SPEAKER
CEILING MTD.
NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED
(AMP RATING /POLES)
FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
CEKh
COMBINATION MOTOR STARTER
®
FACTORY WIRED CONTROLLER OR EQUIPMENT
MOTOR CONNECTION (NUMER INSIDE SYMBOL INDICATES HP)
0
UNIT HEATER CONNECTION
DUCT HEATER CONNECTION
=
PANELBOARD - FLUSH MOUNTED
PANELBOARD - SURFACE MOUNTED
GAP I
GENERATOR ANNUNCIATOR PANEL
a
PULL BOX
®
EMERGENCY LIGHTING TRANSFER RELAY
LEGEND - --
SYMBOL DESCRIPTION MOUNTING
HbGffT -
FIRE ALARM
,F
FIREFIGHTER'S TELEPHONE JACK
SYSTEM
E>
FIRE ALARM VISUAL STATION - LIGHT ONLY
EXTENT OF
CONDUITe
O
FIRE ALARM MANUAL PULL STATION
3' -10'
AFF TO CL
OK
FIRE ALARM MANUAL PULL STATION - KEY OPERATED
3' -10'
AFF TO CL
F •
FIRE ALARM 10' BELL
7' -0'
AFF TO CL
FD
FIRE ALARM CHIME WITH LIGHT
VENDOR
®
FIRE ALARM CHIME
VENDOR
O4
FIRE ALARM HORN
FIRE ALARM
®
FIRE ALARM SPEAKER
THROUGHOUT
Q
MAGNETIC DOOR HOLDER
11-09
BELOW CLG
"E
FIRE ALARM SMOKE DETECTOR ('E' INDICATES ELEVATOR RECALL)
CEILING
OH
HEAT DETECTOR
is
DUCT SMOKE DETECTOR - SUPPLY DUCT
EDR
DUCT SMOKE DETECTOR - RETURN DUCT
RI
SMOKE DETECTOR REMOTE INDICATOR
FS-A-11
SMOKE DETECTOR ALARM REMOTE INDICATOR /TEST SWITCH
SPRINKLER SYSTEM VALVE STATUS SWITCH
Fs
SPRINKLER SYSTEM FLOW SWITCH
FACP I
FIRE ALARM CONTROL PANEL
FAAN
FIRE ALARM ANNUNCIATOR PANEL
®
FIRE ALARM RELAY
❑z
FIRE ALARM ZONE ADDRESSABLE MODULE
NOTES:
EC= ELECTRICAL CONTRACTOR
O2 NOT USED
STUB -UP TO ABOVE ACCESSIBLE CEILING SPACE IN CORRIDOR, TERMINATE WITH PLASTIC
BUSHING.
Q VENDOR CONTRACTED DIRECTLY BY OWNER.
TELEPHONE /DATA
TELEPHONE OUTLET WITH PLATE
1
AFF TO CL
W
WALL TELEPHONE OUTLET WITH PLATE
4'-6'
AFF TO CL
TELEPHONE OUTLET WITH PLATE (SPECIAL MOUNTING HEIGHT)
AS NOTED
SEE SPECS.
44
COMBINATION DATA /TELEPHONE OUTLET WITH PLAT
V -6'
AFF TO CL
COMBINATION DATA /TELEPHONE OUTLET WITH PLATE
(SPECIAL MOUNTING HEIGHT)
AS NOTED
SEE SPECS.
Q
DATA OUTLET WITH PLATE
V -6'
AFF TO CL
Q-
DATA OUTLET WITH PLATE (SPECIAL MOUNTING HEIGHT)
AS NOTED
SEE SPECS.
PBX
TELEPHONE SWITCHBOARD CONSOLE
CABLE /MAN SYSTEM
a
MATV OUTLET FOR WALL MOUNTED TV
(ANTENNA,& REMOTE CONTROL SEE MANUFACTURERS DETAIL)
88'AFF
MISCELLANEOUS
CONDUIT CONCEALER
CONDUIT BELOW GRADE - ON SITE
HOMERUN CONDUIT (QUANTITY OF ARROWS DETERMINES
NUMBER OF CIRCUITS)
- - --
EXPOSED CONDUIT ON WALL OR CEILING
CAPPED CONDUIT
=b
NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED
(AMP RATING /POLES)
FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
CEKh
COMBINATION MOTOR STARTER
®
FACTORY WIRED CONTROLLER OR EQUIPMENT
MOTOR CONNECTION (NUMER INSIDE SYMBOL INDICATES HP)
0
UNIT HEATER CONNECTION
DUCT HEATER CONNECTION
=
PANELBOARD - FLUSH MOUNTED
PANELBOARD - SURFACE MOUNTED
GAP I
GENERATOR ANNUNCIATOR PANEL
a
PULL BOX
®
EMERGENCY LIGHTING TRANSFER RELAY
LEGEND
SYMBOL DESCRIPTION MOUNTING
- ---- - HEIGHT
ABBREVIATIONS
ABC
ABOVE COUNTER
SYSTEM
AFF
ABOVE FINISHED FLOOR
EXTENT OF
CONDUITe
AFG
ABOVE FINISHED GRADE
NOTES:
C
RED - EMERGENCY POWER
VENDOR
CLG
CEILING
VENDOR
FBO
FURNISHED BY OTHERS
VENDOR
IG
ISOLATED GROUND
VENDOR
S
SAFETY TYPE
FIRE ALARM
SMH
SPECIAL MOUNTING HEIGHT - AS NOTED OR SEE SPECS
THROUGHOUT
TV
TELEVISION
WP
WEATHERPROOF
BID NOTE
IT SHALL BE THE RESPONSIBILITY OF THE CONSTRUCTION MANAGER (CM), GENERAL CONTRACTOR
(GC), AND THE SUB - CONTRACTORS (SO TO STUDY ALL THE DRAWINGS AND DETAILS SO THAT THE
INSTALLATION OF ALL NEW WORK CAN BE FULLY COORDINATED. THE CM, GC, AND SC SHALL VISIT
THE SITE, INCLUDING DOING AN ABOVE CEILING INSPECTION, DURING BIDDING TO SATISFY HIMSELF
THAT ALL PROVISIONS HAVE BEEN MADE FOR ALL ASPECTS OF THIS PROJECT. IF DISCREPANCIES
EXIST BETWEEN DRAWINGS AND /OR SITE CONDITIONS, THE CONTRACTOR SHALL NOTIFY THE
GENERAL CONTRACTOR IN WRITING PRIOR TO BID DUE DATE. FAILURE TO DO SO WILL NOT BE
ALLOWED ON A BASIS FOR ADDITIONAL COMPENSATION TO CORRECT A DIFFICULTY OF DIFFERENCE
FROM CONDITIONS INFERRED OR INDICATED ON THE DRAWINGS.
SYSTEMS
RESPONSIBILTY SCHEDULE
SYSTEM
INTERIOR CABLE
FURNISHED BY:
INTERIOR CABLE
INSTALLED BYi
EXTENT OF
CONDUITe
EQUIPMENT
FURNISHED BY:
EQUIPMENT
INSTALLED BY:
NOTES:
TELEPHONE /DATA
VENDOR
VENDOR
Q
VENDOR
VENDOR
0
COMPUTER
VENDOR
VENDOR
3
VENDOR
VENDOR
4
FIRE ALARM
EC
EC
THROUGHOUT
EC
EC
NOTES:
EC= ELECTRICAL CONTRACTOR
O2 NOT USED
STUB -UP TO ABOVE ACCESSIBLE CEILING SPACE IN CORRIDOR, TERMINATE WITH PLASTIC
BUSHING.
Q VENDOR CONTRACTED DIRECTLY BY OWNER.
BID NOTE
IT SHALL BE THE RESPONSIBILITY OF THE CONSTRUCTION MANAGER (CM), GENERAL CONTRACTOR
(GC), AND THE SUB - CONTRACTORS (SO TO STUDY ALL THE DRAWINGS AND DETAILS SO THAT THE
INSTALLATION OF ALL NEW WORK CAN BE FULLY COORDINATED. THE CM, GC, AND SC SHALL VISIT
THE SITE, INCLUDING DOING AN ABOVE CEILING INSPECTION, DURING BIDDING TO SATISFY HIMSELF
THAT ALL PROVISIONS HAVE BEEN MADE FOR ALL ASPECTS OF THIS PROJECT. IF DISCREPANCIES
EXIST BETWEEN DRAWINGS AND /OR SITE CONDITIONS, THE CONTRACTOR SHALL NOTIFY THE
GENERAL CONTRACTOR IN WRITING PRIOR TO BID DUE DATE. FAILURE TO DO SO WILL NOT BE
ALLOWED ON A BASIS FOR ADDITIONAL COMPENSATION TO CORRECT A DIFFICULTY OF DIFFERENCE
FROM CONDITIONS INFERRED OR INDICATED ON THE DRAWINGS.
BERMELLO AJAMIL & PARTNERS, INC.
Architecture Engineering Planning
Interior Design Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
ENGINEER:
ENGINEER INFORMATION
Smith
SS11 Secan
Reid, Inc.
600 West Hillsboro, Suite 300
Deerfield Beach, FL 33441
(954) 421 -1260
FAX- (954) 421 -1466
www.ssr - inc.com
Firm Certification - EB- 0000857
Alfred Eequivel PE - 46863
Bruoe W. Peek PE - 36901
Donald Netinho PE-48464
Nelson R. Long PE - 62294
John E. Moulder PE - 33200
SSR JOB # 0632086.0
!.
REVISIONS:
PROJECT NAME:
SMH - ADVANCE TOWER OFFICES - 2ND FLOOR
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
COMM. NO. 40030.100
SCALE:
DATE: OCTOBER 16,20W
DRAWN:
CHECKED:
CADD FILE:
DRAWING TITLE:
LEGEND, SCHEDULES,
& DRAWING INDEX
SHEET NO.
ELECTRICAL DRAWING
INDEX
SHEET
NO.
DESCRIPTION
E -0.1
LEGEND, SCHEDULES, AND DRAWING INDEX
- ELECTRICAL
E -1.1
2ND FLOOR PLAN - DEMOLITION - PHASE
A - ELECTRICAL
E -2.1
2ND FLOOR PLAN - NEW WORK - PHASE
A - LIGHTING
E -3.1
2ND FLOOR PLAN - NEW WORK - PHASE
A - POWER
E -4.1
2ND FLOOR PLAN - NEW WORK - PHASE
A - SYSTEMS
E -5.1
PARTIAL POWER RISER DIAGRAM & PANEL SCHEDULES
E -6.1
ELECTRICAL SPECIFICATIONS
BERMELLO AJAMIL & PARTNERS, INC.
Architecture Engineering Planning
Interior Design Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
ENGINEER:
ENGINEER INFORMATION
Smith
SS11 Secan
Reid, Inc.
600 West Hillsboro, Suite 300
Deerfield Beach, FL 33441
(954) 421 -1260
FAX- (954) 421 -1466
www.ssr - inc.com
Firm Certification - EB- 0000857
Alfred Eequivel PE - 46863
Bruoe W. Peek PE - 36901
Donald Netinho PE-48464
Nelson R. Long PE - 62294
John E. Moulder PE - 33200
SSR JOB # 0632086.0
!.
REVISIONS:
PROJECT NAME:
SMH - ADVANCE TOWER OFFICES - 2ND FLOOR
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
COMM. NO. 40030.100
SCALE:
DATE: OCTOBER 16,20W
DRAWN:
CHECKED:
CADD FILE:
DRAWING TITLE:
LEGEND, SCHEDULES,
& DRAWING INDEX
SHEET NO.