06-2055-014LEGEND
SYMBOL DESCRIPTION MOUNTING
HEIGHT
LIGHTING
F5
NUMBER DESIGNATES FIXTURE TYPE - SEE LIGHTING FIXTURE
SCHEDULE
SYSTEM
F5
ALL FIXTURES IN THIS SPACE SHALL BE THE SAME TYPE INDICATED
EXTENT OF
CONDUITi
Q
®SURFACE
3' -10'
AFF TO CL
OR RECESSED FLUORESCENT
FIXTURE (TYPE DETERMINES MOUNTING)
FIRE ALARM MANUAL PULL STATION - KEY OPERATED
3' -10'
AFF TO CL
®SURFACE
OR RECESSED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT FIXTURE (TYPE DETERMINES MOUNTING)
7' -0'
AFF TO CL
F�
®SURFACE
VENDOR
OR RECESSED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT W/ BATT. BACKUP. FIXTURE (TYPE DETERMINES MOUNTING)
FIRE ALARM CHIME
VENDOR
04
0
SURFACE OR RECESSED FLUORESCENT
FIXTURE (TYPE DETERMINES MOUNTING)
®
®®
CIRCUIT FIXTURE (TYPE DETERMINES MOUNTING) ED TO EMERGENCY
Q
® ®
SURFACE OR RECESSED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT W/ BATT. BACKUP. FIXTURE (TYPE DETERMINES MOUNTING)
WP
®
SURFACE OR SUSPENDED FLUORESCENT FIXTURE (TYPE DETERMINES
MOUNTING)
OH
®
CIRCUIT. OR SUSPENDED FLUORESCENT CONNEC D TO EMERGENCY
FIXTURE (TYPE DETERMINES MOUNTING)
DS
❑
®
SURFACE OR SUSPENDED FLUORESCENT CONNECTED TO EMERGENCY
CIRCUIT W/ BATT. BACKUP. FIXTURE (TYPE DETERMINES MOUNTING)
OR
Q
WALL BRACKET FIXTURE
®
SMOKE DETECTOR REMOTE INDICATOR
CIRCUIT RACKET FIXTURE CONNECTED TO EMERGENCY
rS_A11
SMOKE DETECTOR ALARM REMOTE INDICATOR /TEST SWITCH
WALL BRACKET FIXTURE CONNECTED TO EMERGENCY
CIRCUIT W/ BATT. BACKUP.
®+
EXIT LIGHT, PROVIDE DIRECTIONAL ARROWS AS INDICATED
ON PLANS
®
SPRINKLER SYSTEM FLOW SWITCH
POLE MOUNTED LIGHT FIXTURE
FRCP
SWITCHES
S
SINGLE POLE SWITCH - IVORY TOGGLE
3' -10'
AFF TO CL
SINGLE POLE SWITCH - RED TOGGLE
3' -10'
AFF TO CL
S2
DOUBLE POLE SWITCH - CENTER OFF
3' -10'
AFF TO CL
S3
THREE WAY SWITCH - IVORY TOGGLE
3' -10'
AFF TO CL
$T
MOTOR RATED SWITCH WITH THERMAL OVERLOAD
W
SD
DIMMER SWITCH
3' -10'
AFF TO CL
$IT
INTERVAL TIMER SWITCH
3' -10'
AFF TO CL
POWER - RECECPTACLES
1' -6'
AFF TO CL
120V. DUPLEX RECEPTACLE - IVORY (REFER TO RECEPTACLE
ABBREVIATIONS FOR EXCEPTIONS)
V -6'
AFF TO CL
8'
120V. DUPLEX RECEPTACLE - IVORY - SPECIAL MOUNTING HEIGHT
(REFER TO RECEPTACLE ABBREVIATIONS FOR EXCEPTIONS)
AS NOTED OR
SEE SPECS
11-61
AFF TO CL
120V. OUADPLEX RECEPTACLE - IVORY (REFER TO RECEPTACLE
ABBREVIATIONS FOR EXCEPTIONS)
1' -6'
AFF TO CL
AS NOTED
SEE SPECS.
120V. OUADPLEX RECEPTACLE - IVORY - SPECIAL MOUNTING HEIGHT
(REFER TO RECEPTACLE ABBREVIATIONS FOR EXCEPTIONS)
AS NOTED OR
SEE SPECS
8—
SPECIAL RECEPTACLE (TYPE AS NOTED)
AS NOTED OR
SEE SPECS
�-
120V. GFI RECEPTACLE (SPECIAL MOUNTING HEIGHT)
AS NOTED OR
SEE SPECS
Q-
120V. GFI RECEPTACLE
V -6'
AFF TO CL
JUNCTION BOX
GB
GROUNDING COLLECTION BUS
HOMERUN CONDUIT (QUANTITY OF ARROWS DETERMINES
NUMBER OF CIRCUITS)
SOUND SYSTEM
Ps
CEILING PAGING SPEAKER
CEILING MTD.
CAPPED CONDUIT
NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED
(AMP RATING /POLES)
E=h
FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
®+
COMBINATION MOTOR STARTER
®
FACTORY WIRED CONTROLLER OR EQUIPMENT
,1
MOTOR CONNECTION (NUMER INSIDE SYMBOL INDICATES HP)
UNIT HEATER CONNECTION
DUCT HEATER CONNECTION
=
PANELBOARD - FLUSH MOUNTED
PANELBOARD - SURFACE MOUNTED
FG—A
GENERATOR ANNUNCIATOR PANEL
Q
PULL BOX
®
EMERGENCY LIGHTING TRANSFER RELAY
LEGEND
SYMBOL DESCRIPTION MOUNTING
HEIGHT
FIRE ALARM
,F
FIREFIGHTER'S TELEPHONE JACK
SYSTEM
AFF
FIRE ALARM VISUAL STATION - LIGHT ONLY
EXTENT OF
CONDUITi
Q
FIRE ALARM MANUAL PULL STATION
3' -10'
AFF TO CL
❑ K
FIRE ALARM MANUAL PULL STATION - KEY OPERATED
3' -10'
AFF TO CL
00
FIRE ALARM 10' BELL
7' -0'
AFF TO CL
F�
FIRE ALARM CHIME WITH LIGHT
VENDOR
®
FIRE ALARM CHIME
VENDOR
04
FIRE ALARM HORN
FIRE ALARM
®
FIRE ALARM SPEAKER
THROUGHOUT
Q
MAGNETIC DOOR HOLDER
1' -0'
BELOW CLG
WP
FIRE ALARM SMOKE DETECTOR ('E' INDICATES ELEVATOR RECALL)
CEILING
OH
HEAT DETECTOR
DS
❑
DUCT SMOKE DETECTOR - SUPPLY DUCT
OR
DUCT SMOKE DETECTOR - RETURN DUCT
®
SMOKE DETECTOR REMOTE INDICATOR
rS_A11
SMOKE DETECTOR ALARM REMOTE INDICATOR /TEST SWITCH
SPRINKLER SYSTEM VALVE STATUS SWITCH
®
SPRINKLER SYSTEM FLOW SWITCH
FRCP
FIRE ALARM CONTROL PANEL
FAAN
FIRE ALARM ANNUNCIATOR PANEL
®
FIRE ALARM RELAY
�z
FIRE ALARM ZONE ADDRESSABLE MODULE
NOTESi
O EC= ELECTRICAL CONTRACTOR
O2 NOT USED
Q3 STUB -UP TO ABOVE ACCESSIBLE CEILING SPACE IN CORRIDOR, TERMINATE WITH PLASTIC
BUSHING.
Q VENDOR CONTRACTED DIRECTLY BY OWNER.
TELEPHONE/DATA
TELEPHONE OUTLET WITH PLATE
V -6'
AFF TO CL
W
WALL TELEPHONE OUTLET WITH PLATE
41-61
AFF TO CL
�-
TELEPHONE OUTLET WITH PLATE (SPECIAL MOUNTING HEIGHT)
AS NOTED
SEE SPECS.
COMBINATION DATA /TELEPHONE OUTLET WITH PLATE
1' -6'
AFF TO CL
a.
COMBINATION DATA /TELEPHONE OUTLET WITH PLATE
(SPECIAL MOUNTING HEIGHT)
AS NOTED
SEE SPECS.
Q
DATA OUTLET WITH PLATE
11-61
AFF TO CL
Q-
DATA OUTLET WITH PLATE (SPECIAL MOUNTING HEIGHT)
AS NOTED
SEE SPECS.
®
TELEPHONE SWITCHBOARD CONSOLE
CABLE /MAN SYSTEM
a
MATV OUTLET FOR WALL MOUNTED TV
(ANTENNA,& REMOTE CONTROL SEE MANUFACTURERS DETAIL)
88'AFF
MISCELLANEOUS
CONDUIT CONCEALER
CONDUIT BELOW GRADE - ON SITE
HOMERUN CONDUIT (QUANTITY OF ARROWS DETERMINES
NUMBER OF CIRCUITS)
- - --
EXPOSED CONDUIT ON WALL OR CEILING
CAPPED CONDUIT
NON- FUSIBLE SAFETY SWITCH, SIZE AS NOTED
(AMP RATING /POLES)
E=h
FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
®+
COMBINATION MOTOR STARTER
®
FACTORY WIRED CONTROLLER OR EQUIPMENT
,1
MOTOR CONNECTION (NUMER INSIDE SYMBOL INDICATES HP)
UNIT HEATER CONNECTION
DUCT HEATER CONNECTION
=
PANELBOARD - FLUSH MOUNTED
PANELBOARD - SURFACE MOUNTED
FG—A
GENERATOR ANNUNCIATOR PANEL
Q
PULL BOX
®
EMERGENCY LIGHTING TRANSFER RELAY
LEGEND
SYMBOL DESCRIPTION' - _ _ _ F*OUN ,, ING
HEIGHT
ABBREVIATIONS
ABC
ABOVE COUNTER
SYSTEM
AFF
ABOVE FINISHED FLOOR
EXTENT OF
CONDUITi
AFG
ABOVE FINISHED GRADE
NOTESe
C
RED - EMERGENCY POWER
VENDOR
CLG
CEILING '
VENDOR
FBO
FURNISHED BY OTHERS
VENDOR
IG
ISOLATED GROUND
VENDOR
S
SAFETY TYPE
FIRE ALARM
SMH
SPECIAL MOUNTING HEIGHT - AS NOTED OR SEE SPECS
THROUGHOUT
TV
TELEVISION
WP
WEATHERPROOF
BID NOTE
IT SHALL BE THE RESPONSIBILITY OF THE CONSTRUCTION MANAGER (CM), GENERAL CONTRACTOR
(GC), AND THE SUB - CONTRACTORS (SC) TO STUDY ALL THE DRAWINGS AND DETAILS SO THAT THE
INSTALLATION OF ALL NEW WORK CAN BE FULLY COORDINATED. THE CM, GC, AND SC SHALL VISIT
THE SITE, INCLUDING DOING AN ABOVE CEILING INSPECTION, DURING BIDDING TO SATISFY HIMSELF
THAT ALL PROVISIONS HAVE BEEN MADE FOR ALL ASPECTS OF THIS PROJECT. IF DISCREPANCIES
EXIST BETWEEN DRAWINGS AND /OR SITE CONDITIONS, THE CONTRACTOR SHALL NOTIFY THE
GENERAL CONTRACTOR IN WRITING PRIOR TO BID DUE DATE. FAILURE TO DO SO WILL NOT BE
ALLOWED ON A BASIS FOR ADDITIONAL COMPENSATION TO CORRECT A DIFFICULTY OF DIFFERENCE
FROM CONDITIONS INFERRED OR INDICATED ON THE DRAWINGS.
SYSTEMS
RESPONSIBILTY SCHEDULE
SYSTEM
INTERIOR CABLE
FURNISHED BYo
INTERIOR CABLE
INSTALLED BYt
EXTENT OF
CONDUITi
EOUIPMENT
FURNISHED BYi
EQUIPMENT
INSTALLED BYe
NOTESe
TELEPHONE /DATA
VENDOR
VENDOR
Q
VENDOR
VENDOR
- POWER & SYSTEMS
COMPUTER
VENDOR
VENDOR
3
VENDOR
VENDOR
4
FIRE ALARM
EC
EC
THROUGHOUT
EC
EC
NOTESi
O EC= ELECTRICAL CONTRACTOR
O2 NOT USED
Q3 STUB -UP TO ABOVE ACCESSIBLE CEILING SPACE IN CORRIDOR, TERMINATE WITH PLASTIC
BUSHING.
Q VENDOR CONTRACTED DIRECTLY BY OWNER.
BID NOTE
IT SHALL BE THE RESPONSIBILITY OF THE CONSTRUCTION MANAGER (CM), GENERAL CONTRACTOR
(GC), AND THE SUB - CONTRACTORS (SC) TO STUDY ALL THE DRAWINGS AND DETAILS SO THAT THE
INSTALLATION OF ALL NEW WORK CAN BE FULLY COORDINATED. THE CM, GC, AND SC SHALL VISIT
THE SITE, INCLUDING DOING AN ABOVE CEILING INSPECTION, DURING BIDDING TO SATISFY HIMSELF
THAT ALL PROVISIONS HAVE BEEN MADE FOR ALL ASPECTS OF THIS PROJECT. IF DISCREPANCIES
EXIST BETWEEN DRAWINGS AND /OR SITE CONDITIONS, THE CONTRACTOR SHALL NOTIFY THE
GENERAL CONTRACTOR IN WRITING PRIOR TO BID DUE DATE. FAILURE TO DO SO WILL NOT BE
ALLOWED ON A BASIS FOR ADDITIONAL COMPENSATION TO CORRECT A DIFFICULTY OF DIFFERENCE
FROM CONDITIONS INFERRED OR INDICATED ON THE DRAWINGS.
•
AJAMIL & PARTNERS, INC.
Arc hitecture Engineering Planning
Interic ir Design Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(3051859-2050 Fax (305) 860 -3700
EER:
INFORMATION
Sm r
Sec
an
Reid, Inc.
West Hillsboro, Suite 300
:er6eld Beach, FL 33441
(954) 421 -1260
FAX- (954) 421 -1466
www.ssr - inc.com
rtn Certification - EB -000W7
Alff ed Ewpgvel PE - 46889
Bruce W. Peet PE - 56901
Donald NoUnho PE - 48464
Nelson B. Img PE - 52284
John E. Moulder PE - 35200
SSR JOB # 0642086.0
No. ,4556
TAI ;
PRO.IECT NAME:
SMH - ADVANCE TOWER OFFICES - 2ND FLOOR
PR ECT ADDRESS:
7400 S 62nd Ave.
South '. Florida 33143
PLAN
. NO. 40030.100
DATE: NOVEMBER 9. 2006
DRAWN:
CHE KED:
CAD FILE:
DRA NG TITLE:
LE END, SCHEDULES
& DRAWING INDEX
NO.
E -0.1
ELECTRICAL DRAWING
INDEX
SHEET
NO.
DESCRIPTION
E -0.1
LEGEND, SCHEDULES, AND DRAWING INDEX -
ELECTRICAL
E -1.1
2ND FLOOR PLAN - DEMOLITION - PHASE B - ELECTRICAL
E -2.1
2ND FLOOR PLAN - NEW WORK - PHASE B
- LIGHTING
E -3.1
2ND FLOOR PLAN - NEW WORK - PHASE B
- POWER & SYSTEMS
E -4.1
PARTIAL POWER RISER DIAGRAM & PANEL
SCHEDULES
E -5.1
ELECTRICAL SPECIFICATIONS
•
AJAMIL & PARTNERS, INC.
Arc hitecture Engineering Planning
Interic ir Design Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(3051859-2050 Fax (305) 860 -3700
EER:
INFORMATION
Sm r
Sec
an
Reid, Inc.
West Hillsboro, Suite 300
:er6eld Beach, FL 33441
(954) 421 -1260
FAX- (954) 421 -1466
www.ssr - inc.com
rtn Certification - EB -000W7
Alff ed Ewpgvel PE - 46889
Bruce W. Peet PE - 56901
Donald NoUnho PE - 48464
Nelson B. Img PE - 52284
John E. Moulder PE - 35200
SSR JOB # 0642086.0
No. ,4556
TAI ;
PRO.IECT NAME:
SMH - ADVANCE TOWER OFFICES - 2ND FLOOR
PR ECT ADDRESS:
7400 S 62nd Ave.
South '. Florida 33143
PLAN
. NO. 40030.100
DATE: NOVEMBER 9. 2006
DRAWN:
CHE KED:
CAD FILE:
DRA NG TITLE:
LE END, SCHEDULES
& DRAWING INDEX
NO.
E -0.1