Loading...
06-2055-01215010 - BASIC MECHANICAL REQUIREMENTS A. CODES & REFERENCES 1. FLORIDA STATE BUILDING CODE 2004. 2. SMACNA 3. NFPA 101 (2003) 4-NFPA 90A (2002) 5. NFPA 99 (2002) B. SCOPE OF WORK 1. PROVIDE ALL REQUIRED PERMITS, LABOR, MATERIAL AND EQUIPMENT REQUIRED TO COMPLETE THE SCOPE OF THE PROJECT SHOWN ON THE DRAWINGS COMPLETE AND READY FOR OCCUPANCY AND USE BY OWNER. THE WORK SHALL INCLUDE BUT IS NOT LIMITED TO: a. REMOVAL. RELOCATION AND RE- INSTALLATION OF EXISTING EQUIPMENT AND SYSTEM. b. CONNECTIONS TO EXISTING OR NEW EQUIPMENT AND SYSTEMS. c. CUTTING AND PATCHING TO REMOVE EXISTING OR INSTALL NEW WORK. d• CLEANING AND TESTING. e. INSTRUCTION TO OWNER'S PERSONNEL. 2. PROVIDE ALL BUILDING PENETRATIONS REQUIRED TO COMPLETE PROJECT. ALL PENETRATIONS TO BE PATCHED AND SEALED TO BE WATERTIGHT. MAINTAIN FIRE RATINGS OF EXISTING STRUCTURE. 3. PROVIDE ALL NECESSARY DUCT, EQUIPMENT AND PIPE SUPPORTS AND MATERIALS REQUIRED FOR INSTALLATION. PER THE REQUIREMENTS OF LOCAL, STATE OR FEDERAL CODES. C. REQUIRED SHOP DRAWINGS 1. INSULATION. 2. AIR DEVICES. 3. DUCTWORK COORDINATION DRAWINGS. 4. AIR HANDLING EQUIPMENT. 5. FANS. D. MAINTENANCE MANUALS 1. PROVIDE MAINTENANCE MANUALS FOR ALL NEW EQUIPMENT CONTAINING ALL OPERATING AND MAINTENANCE DATA, SUBMITTALS, WARRANTEES, DIAGRAMS, INSPECTION REPORTS AND VALVE LISTS IN A 3 RING BINDER WITH POCKETS FOR DRAWINGS. PROVIDE OWNER WITH MINIMUM OF 2 COPIES. E. SUBSTITUTIONS 1. EQUIPMENT AND DESIGN OF SYSTEMS INDICATED ON THE DESIGN DRAWINGS AND WITHIN THESE SPECIFICATIONS SHALL BE CONSIDERED AS 'SPECIFIED STANDARD' OF QUALITY. NO SUBSTITUTIONS SHALL BE MADE WITHOUT PRIOR WRITTEN APPROVAL OF THE ENGINEER 10 DAYS PRIOR TO BID DATE. 2 -ANY DEVIATION FROM SPECIFIED EQUIPMENT THAT AFFECTS THE ELECTRICAL REQUIREMENTS SHALL BE COORDINATED BY THE MECHANICAL CONTRACTOR AND EQUIPMENT VENDOR WITH THE ELECTRICAL CONTRACTOR PRIOR TO SUBMITTING BIDS. 15050 - BASIC MATERIALS AND METHODS A. ACCESS PANELS - FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED BY GENERAL CONTRACTOR. 1. PROVIDE FOR ACCESS TO ALL SERVICEABLE EQUIPMENT IN WALLS AND CEILINGS. 2. MICOR STYLE M FOR DRYWALL. 3. MICOR STYLE K FOR PLASTER. 4. MINIMUM SIZE 16'x16' . 5. NYSTROM, KARP, J.L. INDUSTRIES OR WILLIAMS PAINT. B. LABELING 1. PROVIDE RIGID PLASTIC EMBOSSED EQUIPMENT NAME TAGS FOR ALL NEW EQUIPMENT AND DISCONNECTS. SETON NAMEPLATE CORPORATION. C. HANGERS AND SUPPORTS 1. PROVIDE ALL NECESSARY DUCTWORK, PIPE SUPPORTS, HANGERS, RODS, CLAMPS AND ATTACHMENTS TO PROPERLY INSTALL AND SUPPORT DUCTWORK, PIPING AND EQUIPMENT FROM THE BUILDING STRUCTURE. 2. PROVIDE ANY ANGLE IRON OR UNISTRUT AND SUSPENSION RODS REQUIRED TO INSTALL EQUIPMENT, PIPING AND DUCTWORK. 3. ALL SUPPORTS EXPOSED TO OUTDOORS SHALL BE CLEANED, PRIMED AND PAINTED TO PREVENT RUSTING. FINISH COLOR AS SELECTED BY OWNER. 4. THE USE OF BAILING WIRE OR PERFORATED METAL STRAPPING IS NOT PERMITTED FOR SUPPORTS. D. WARRANTY /GUARANTEE 1. THE CONTRACTOR SHALL WARRANTY /GUARANTEE AND MAINTAIN THE STABILITY OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION OF THE PERIOD OF ONE YEAR. 2. DEFECTS OF ANY KIND DUE TO THE FAULTY WORK OR MATERIALS APPEARING DURING THE ABOVE MENTIONED PERIOD MUST BE IMMEDIATELY MADE GOOD BY THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION OF THE OWNER AND ENGINEER. SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE DAMAGE TO THE FINISH OR FURNISHING OF THE BUILDING RESULTING FROM THE ORIGINAL DEFECT OR REPAIR THERETO. 15103 - SLEEVES A. SLEEVES TO BE 18 GAGE SHEET METAL OR SCHEDULE 40 PIPE. SLEEVE THE FOLLOWING: 1. MASONRY WALLS SLEEVE ALL PIPE PENETRATIONS. 2. NON -FIRE RATED PARTITIONS NO SLEEVES REQUIRED. SEAL WALL TO INSULATION. 3. USE U.L. LISTED ASSEMBLY FOR ALL PENETRATIONS THROUGH RATED CONSTRUCTION. 15242 - VIBRATION ISOLATION A. ACCEPTABLE MANUFACTURERS: 1. MASON INDUSTRIES. 2. KINETICS NOISE CONTROL. 3. KORFUND. 4. AMBER BOOTH. B. MASON SUPER W RUBBER PAD FOR CONDENSER UNITS. C. MASON TYPE HS CEILING FOR SUSPENDED FAN COIL UNITS. 15250 - INSULATION A. INSULATION, ADHESIVES, COATINGS, SEALERS, TAPES, ETC. SHALL HAVE A FLAME SPREAD OF 25 OR LESS AND SMOKE DEVELOPMENT OF 50 OR LESS IN ACCORDANCE WITH ASTM E -84, NFPA 225, UL 723 AND MEET THE REQUIREMENTS OF NFPA 90A. ALL INSULATING R- VALUES TO MEET THE REQUIREMENTS OF THE FLORIDA ENERGY CODE. B. FLEXIBLE ELASTOMERIC INSULATION. ARMSTRONG 'AP ARMAFLEX'. MITCHEL, RUBATEX : 1. CONDENSATE DRAINS - 314 THICK. 2. REFRIGERATION SUCTION LINES: 314 THICK 15530 - REFRIGERANT PIPING A. REFRGERANT PIPING: COPPER, DEHYDRATED. WITH HIGH TEMPERATURE SOLDERED JOINTS AND WROUGHT COPPER (400 PSIG) FITTINGS, TYPE -K. B. SIZE REGRIGERANT LINES IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED TABLES USING PRESSURE OR TEMPERATURE DROPS AS FOLLOWS: - SUCTION LINES 2 -F - LIQUID LINES 1 ° F OR 2 PSI. -HOT GAS LINES :1 ° F OR 3.6 PSI. -SIZE DISCHARGE AND HOT GAS RISERS FOR POSITIVE OIL RETURN TO COMPRESSORS. C. ASSEMBLY AND TESTING 1. THOROUGHLY CLEAN PIPING OF DIRT AND GREASE ON INSIDE WITH A SUITABLE CLEANING SOLUTION JUST BEFORE SOLDERING. 2. POLISH AND OF TUBES AND INSIDE OF FITTINGS. 3. PURGE REFRIGERANT PIPING OF AIR WHILE CONNECTIONS ARE BEING MADE. 4. TEST REFRIGERANT PIPING TO HOLD A PRESSURE TWICE NORMAL WORKING PRESSURE FOR A PERIOD OF 72 HOURS BEFORE REFRIGERANT IS ADDED. 15890 - SHEET METAL DUCTWORK A. ALL DUCT TO BE INSTALLED ACCORDING TO 1985 EDITION OF SMACNA STANDARDS. B. ALL DUCT EXCEPT THAT SPECIFICALLY SHOWN IS TO BE GALVANIZED. RETURN, EXHAUST AND DUCT DOWNSTREAM OF CV BOXES TO BE 0 -2' PRESSURE CLASS. SUPPLY DUCT FROM FAN TO CV OR VAV BOX TO BE 4' CLASS. C. ALL SYSTEMS TO BE LEAKAGE TESTED. D. DUCTWORK ROUTED PARALLEL TO A WALL, RATED OR CORRIDOR SHALL BE INSTALLED WITH MINIMUM 6' CLEARANCE TO ALLOW FOR INSPECTION OF WALL PENETRATIONS. CONTRACTOR SHALL PROVIDE 12' CLEARANCE WHERE POSSIBLE, COORDINATE. E. BUTTON SNAPLOCK JOINTS OR SEAMS ARE NOT PERMITTED. 15910 - SHEET METAL ACCESSORIES A. AIR INLETS AND OUTLET. 1. REFER TO SCHEDULE. 2. ALL ALUMINUM CONSTRUCTION. 1 ACCEPTABLE MANUFACTURERS: TITUS, PRICE. METAL -AIRE. CARNES, ANEMOSTAT, NAILOR, POTTORFF. B. FLEXIBLE DUCTWORK (NON- HOSPITALS) 1. TO BE FLEXMASTER TYPE 3. WIREMOLD TYPE WCK OMNIAIR 1200, OR THERMAFLEX. 2. FLEXIBLE DUCTWORK SHALL BE ACOUSTICAL LOW PRESSURE TYPE WITH INTERIOR LINER, METAL HELIX, FIBERGLASS INSULATION WITH AN R VALUE OF 6.0 OR GREATER AND COPOLYMER SEAMLESS OUTSIDE SLEEVE. THE ENTIRE FLEXIBLE DUCT ASSEMBLY SHALL BE LISTED IN ACCORDANCE WITH UL -181 CLASS 1 AIR DUCT MATERIAL. THE MAXIMUM LENGTH OF ANY FLEX DUCT SHALL BE 6' -01. FLEXIBLE DUCTWORK SHALL MEET THE FLORIDA MODEL ENERGY EFFICIENCY CODE. ALL JOINTS AT CONNECTIONS TO DIFFUSERS AND DUCTWORK SHALL BE SEALED WITH GLASS, FABRIC AND MASTIC. 3. USE METAL LINED DUCT IN OPERATING ROOMS, RECOVERY, ICU AND TRAUMA ROOMS, 4 FEET MAXIMUM LENGTH. 15990 - TEST AND BALANCE A. PROVIDE COMPLETE TEST AND BALANCE OF ALL WATER AND AIR SYSTEMS IN ACCORDANCE WITH NEBB (NATIONAL ENVIRONMENTAL BALANCING BUREAU) OR AABC (ASSOCIATED AIR BALANCE COUNCIL) STANDARDS. B. TEST AND BALANCE FIRM SHALL BE: 1. TOTAL DYNAMIC BALANCE - (954) 425 -0764. 2. EARL HAYGOOD. INC. - (305) 266 -7070. C. CONTRACTOR SHALL: 1. VISIT SITE AT START OF PROJECT AND COORDINATE REQUIRED BALANCING EQUIPMENT AND DAMPERS WITH MECHANICAL CONTRACTOR. 2. AIR SYSTEMS: a. MAKE CHANGES TO DAMPERS, VOLUME BOXES, ETC. TO OBTAIN DESIGN CONDITIONS AS REQUIRED BY TAB PROCEDURES. b. BALANCE SUPPLY, RETURN AND EXHAUST AIR OUTLETS WITHIN 10% OF DESIGN WHILE MAINTAINING REQUIRED PRESSURE RELATIONSHIPS. RECORD DESIGN AND ACTUAL TOTALS. c. ACTUAL AND DESIGN NAMEPLATE AMPERAGE ON FAN MOTORS. d. ADJUST FANS FOR LOWEST STATIC PRESSURE REQUIRED TO DELIVER TO OUTLETS AS NOTED IN NEBB OR AABC PROCEDURES. i me - 12' -i v CONDENSING UNIT CKET INTS CONDENSING UNIT MOUNTING DETAIL CONDENSING UNIT SCHEDULE RUBBER-IN-SHEAR ISOLATORS 02 =POWER CIRCUIT FEEDS CONDENSING UNIT FIRST WHICH THEN West Hillsboro, Suite 300 FEEDS THE FAN COIL UNIT. PROVIDE 3 -POLE DISCONNECT QI PROVIDE WITH: REMOTE CONTROLLER AT EACH UNIT. COORDINATE WITH ELECTRICAL DIVISION. � I HIGH EFFICIENCY MOTOR (SEE SPECS.) 0 PROVIDE WITH: MANUFACTURER TOTAL OUTSIDE MINIMUM COOLING COIL FAN Bruce W. Peet PE - 36901 (DENT. TYPE &MODEL N0. CAPACITY DESIGN OB OPERATING REFRIG. ELECT. MOUP REMARKS TYPE MODEL N0. OUTSIDE AIR BTU /HR REMARKS TEMP.OSUB NON- SPARKING WHEEL CU -239 AIR - COOLED MITSUBISHI PUY- A18NHA 18,000 95 117 0'F R410p 208/1 15 - SOLID STATE SPEED SWITCH FAN C i Sm th SCHEDULE FAN NOTES: West Hillsboro, Suite 300 T A =THROW AWAY QI PROVIDE WITH: REMOTE CONTROLLER PAR -21MAA � I HIGH EFFICIENCY MOTOR (SEE SPECS.) 0 PROVIDE WITH: MANUFACTURER & FAN MINIMUM = EMERGENCY POWER COOLING COIL FAN Bruce W. Peet PE - 36901 CFM EXT. SENSIBLE TOTAL REFRIG. PIPE CONNECTION H.P. TYPE ELEC. (DENT. TYPE MODEL N0. OUTSIDE AIR FILTERS REMARKS BVS = BELTED VENT SET NON- SPARKING WHEEL S.P. CAPACITY CAPACITY - SOLID STATE SPEED SWITCH REVI FCU -239 DR- CEILING PLASABBAA TIO 0 0 TA - 18,000 R410A 1/2 �/j 70W - 208/1 O • AJAMIL & PARTNERS, INC. Architecture Engineering Planning Interior Design Landscape Architecture 2601 South Bayshore Drive 1 Oth Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 EP �NGINEER: EP ENGINEER INFORMATION i Sm th SecPnan FAN SCHEDULE West Hillsboro, Suite 300 PRE =POWER ROOF EXHAUSTER C.T. = CONTROL TRANSFORMER � I HIGH EFFICIENCY MOTOR (SEE SPECS.) 0 PROVIDE WITH: -DESIGNER GRILLE - NEMA-I SWITCH WITH PILOT LIGHT PRS =POWER ROOF SUPPLY FAN E.P. = EMERGENCY POWER Alfred F.squivel PE - 46869 Bruce W. Peet PE - 36901 SWSI = SINGLE WIDTH, SINGLE INLET C.E. = CEILING EXHAUST (2) - INCLUDES WEIGHT OF INERTIA BASE John E. Moulder PE - 39200 -TIME DELAY SWITCH (MODEL GTDI DWDI = DOUBLE WIDTH, DOUBLE INLET EXP. = EXPLOSION PROOF MOTOR & - ISOLATION KIT BVS = BELTED VENT SET NON- SPARKING WHEEL -MOTOR WITH THERMAL OVERLOADS - SOLID STATE SPEED SWITCH REVI IONS: PRO. IECT NAME: SMH - &DVANCE TOWER OFFICES - 2ND FLOOR PR - UL LISTING (DENT. SYSTEM TYPE MANUFACTURER MODEL N0. CFM S.P. MOTOR N ROOF OPENING OPERATING WEIGHT (2) REMARKS MIN. RPM ELECT. H.P. x_241 TOILET EXHAUST CE GREENHECK SP -A200 100 0.25 48W 900 IIS -I N/A 21 • AJAMIL & PARTNERS, INC. Architecture Engineering Planning Interior Design Landscape Architecture 2601 South Bayshore Drive 1 Oth Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 EP �NGINEER: EP ENGINEER INFORMATION i Sm th SecPnan Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr - inc.com Firm Certification - EB- 0000857 Alfred F.squivel PE - 46869 Bruce W. Peet PE - 36901 Donald NeEinho PE - 48464 Nelam B. Long PE - 62294 John E. Moulder PE - 39200 SSR JOB # 0632086.0 US REVI IONS: PRO. IECT NAME: SMH - &DVANCE TOWER OFFICES - 2ND FLOOR PR ECT ADDRESS: 7400 S1W. I 62nd Ave. South Miami, Florida 33143 I� PLAN N COMM. NO. 40030.100 SCALE: DATE: NOVEMBER 9, 2006 DRA L ": CHE L KED: CAD FILE: DRA NG TITLE: HV C SCHEDULES, SPtCIFICATIONS, AND DETAILS NO M-0.2