06-1457-014FIRE ALARM NOTES 1. CONDUITS TO BE 3/4" MINIMUM AND SIZED BY THE ELECTRICAL CONTRACTOR AS PER THE N.E.C. AND FILLED TO A 40 % MAXIMUM. 2. ALL FIRE ALARM INITIATING, SIGNAL AND CONTROL CIRCUITS ARE POWER LIMITED. 3. ALL FIRE ALARM DEVICES ARE U.L. LISTED AND COMPATIBLE. 4. THIS SYSTEM IS AN INTELLIGENT ANALOG /DIGITAL MULTIPLEX SYSTEM BY EDWARD'S SYSTEMS TECHNOLOGY. 5. WIRE MANUFACTURERS AND SPECIFIC CABLE NUMBERS TO BE APPROVED BY THE ENGINEER OF RECORD. 6. INSTALL A COMPLETE FIRE ALARM SYSTEM IN ACCORDANCE WITH THE SOUTH FLORIDA BUILDING CODE, NFPA CODES AND ALL LOCAL ORDINANCES. 7. MOUNT AL STROBE UNITS AT 80" A.F.F. TO MEET A.D.A. CODES. 8. UPON SUBMITTAL PROVIDE BATTERY CALCULATIONS FOR EACH POWER SUPPLY (24 HOURS OF STANDBY AND 15 MINUTES OF ALARM) AND VOLTAGE DROP CALCULATIONS FOR EACH SIGNAL CIRCUIT. 9. PROVIDE AS PART OF CONTRACT 5 YEARLY COMPLETE SYSTEM RECERTIFICATIONS AND 1 YEAR OF WARRANTY FROM DATE OF FINAL ACCEPTANCE BY THE CITY AND OWNERS. 10. ALL STROBES TO BE SELF — SYNCHRONIZED BY CIRCUIT TO AVOID EPILEPTIC SEIZURES ON PHOTOSENSITIVE PERSONS. 11. ALL AUDIBLE SIGNALS TO BE THE AMERICAN NATIONAL STANDARD EMERGENCY EVACUATION SIGNAL (3 -3 -3 TEMPORAL PATTERN). 12. ALL POWER SUPPLY OUTPUTS, INTELLIGENT LOOPS AND SIGNAL CIRCUITS TO BE LOADED A MAXIMUM OF 75 TO ALLOW FOR FUTURE CHANGES OR EXPANSIONS. 13. PROVIDE 4 DRY CONTACT CIRCUITS FOR ALARM MONITORING SERVICE (ALARM, SYSTEM TROUBLE, SUPERVISORY AND WATERFLOW). w i� o- s 0 Li[ 3 uJ i c� z CODE SECTION 4.28.3(8) MOUNTING HEIGHT OF VISUAL APPLIANCES, WALL MOUNT 1 or 2 Hour Fire Rated Through (\''g9jffpy Penetration Firestop for Single �L Metallic Pipe through sYstetQ Gypsum Walls using TREMstop IA. WL 1158 F- Rating = 1 and 2 Hr. T- Rating =1/4 Hr. 3735 Green Rd. Beachwood, OH, 44122 Drawing not to scale 10 Pre -Rated Gypsum Wallboard/Stud Wall Assembly 20 Metallic Pipe - A) Steel Pipe - 12" diam. (or smaller) Sch. 10 (or heavier) steel pipe. B) Iron Pipe - 12" diam. (or smaller) cast or ductile iron pipe. C) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. D) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. The annular space shall be min. 0" to max. 1" within the firestop system. 30 TREMstop IA - Min. 1/2" thickness of sealant applied within opening. Min. 1/4" cant bead of sealant to be applied at point contact. Project: Location: Installer: Signature: The Tremco products used above have been tested in accordance with the following: . ASTM E814 (LTU479) Standard Test Method for Through Penetration Firestopping. : 12/08198 1 Drawing: TW -1158 •oved by: M. Starr The above described assembly has been tested and is based on both past and antici- pated performance criteria. Tremco shall not be liable for any damages, direct or con- sequential, resulting from use of this material or design. Tremco shall only be responsible for replacing material found to be defective. • i _ ! • ! a) • • r a r ••• a � _ a • s s � ) • s a • • • a ilsa �a ••• r•a• ! a • • • a raas la • ••• a !•a• a _ MMO O _- p O 5 'FAL N- R --H 21 Q F, YJ AKA TicN Q (D O i9UPP.Y 5Y O7ntw5i a �"_ FA `J o 0 A, CD 'd; A.0 1Y .Y�.ER t7 Y_UL:.EI:Y O p 0 00 O 0 0 6:0 A 0 � '_jr1[ -J OFFIC D f RE ALARMM fLOOK PLAN s IN f FIRE ALARM LEGEND N STROBE LIGHT 75CD CD NMEELOK 75 CANDELA FE1 STROBE LIGHT 110CD jibCD WHEELOCK 110 CANDELA M< SPEAKER STROBE 75CD 75 CD WHEELOK 75CD Pp I f 't All R� 1?�p Q) QSZ 4 ON P pptl Q�KQR vat o r,5 $Na NI) pa`d �.�, I NS q 1+�lyp��5 DA x..� o R�l�,,�Rr °�� $y .3 +y5�c/f llff WV O N W 09 W M O I� W ai _ +o 00 N � O Cx O ad 6 Q d O INC a < a a � 4,• C » _ V a to v m cc o� £o < M W 4, t J_ U L ■ O < W I ce) O I < o a W o N N < O t o .� QUm t J_ U 11 W �U zl—m QUm >Z_� I- ZL2 U>J Q 2 d�- 1 = Jm Z LLJ OZm 00� OQQ W zza , _(S) U_J J; U - d Fz- w Dz t t zzz �, O o D _• � �. ZN a/ N Z O N O N� C� v LL_U l�