06-847-021TYPE PANEL BOARD » » MAIN BUS 200 A.
SERVICE 30, 4W PANEL C MAINS M.C.B.
VOLTAGE 120/240 A.I.C. 10,000
CONNEC.
KVA
POLE
TRIP
DUIT
WIRE
REMARKS
CKT.
NO.
CKT.
NO.
REMARKS
WIRE
CON
DUIT
TRIP
POLE
CONNEC.
KVA
0.48
1
20
1/2"
#12
WALK -IN- COOLER
1
'k 'I`
*
c *
c *
*
�k *
*
2
4
ICE MACHINE
#12
1/2"
20
2
4.80
2.49
1
20
1/2"
#12
DISHWASHER MACHINE
3
6.00
2
40
3/4'
#6
HIGH LEG
5
6
HIGH LEG
20
1/2"
#12
EXIST. LOAD
9
11
1.20
1
20
1/2"
#12
REFRIGETATOR
7
8
POS PRINTER
#12
1/2"
20
1
1.00
1.50
1
20
1/2"
#12
CAPUCHINO
9
10
POS PRINTER
#12
1/2"
20
1
1.00
12
EXIST. LOAD
#12
1/2"
20
HIGH LEG
11
12
HIGH LEG
20
1/2"
#12
EXIST. LOAD
13
1.00
1
20
1/2"
#12
IPOS PRINTER
13
14
16
18
FUTURE
EQUIP.
20
1/2"
#12
EXIST. CU LOAD
6.24
1.20
1
20
1 2"
12
HOT TOWEL HEATER
15
18
EXIST. LOAD
#12
1/2"
1 20
HIGH LEG
17
1.20
1
20
1/2"
#12
COFFE MAKER
19
20
HIGH LEG
#12
1/2"
20
1
0.72
1.20
1
20
1/2-
#12
SODA DISPENSER
21
22
24
FUTURE EQUIPMENT
#12
1/2"
20
1
11.78
1.00
1
20
1/2"
#12
HIGH LEG
23
6.65
3
40
3/4"
#8
NEW RTH
25
27
29
26
HIGH LEG
20
1/2"
#12
EXIST. LOAD
25
28
GEN. OUTLETS
#12
1/2"
20
1
1.08
30
GEN. OUTLETS
#12
1/2"
20
1
0.72
28
EXIST. LOAD
#12
1/2"
20
HIGH LEG
31
32
HIGH LEG
20
1/2"
#12
JEXIST. LOAD
29
1.44
1
20
1/2"
#12
WALK -IN- FREEZER
33
34
GEN. OUTLETS
#12
1/2"
20
1
0.72
1.00
1
20
1/2-
#12
POS PRINTER
35
36
COND. COOLER
#12
1/2"
20
1
0.96
34
EXIST. LOAD
#12
1/2"
20
HIGH LEG
37
38
SPACE
40
3/4'
#6
EXIST. LOAD
35
37
0.62
1
20
1/2"
#12
COND. FREEZER
39
40
EXIST. CU LOAD
#12
1/2"
20
2
2.00
39
40
SPACE
41
42
_±L]
42
TOTAL LOAD : 37,560 VA
LOAD CALCULATIONS:
KITCHEN EQUIP.(35.39 KVA)240 10: 85 VA
KITCHEN EQUIP.(12.89 KVA)240 30: 31 VA
TOTAL DEMAND LOAD : 116 A
FEEDER:4 # 4/0 CU,THW IN 2.5" CONDUIT.
* - KITCHEN LOADS I
I
EXISTING
3 # 4/0 CU, .6W IN 2.5" COND.
r- ------- a---- - - - - -�
- - - - - - - - - - I
EXISTING LINE GUTTER I I EXISTING
L----- --T - -J
250A MCB I I rEXISTING rEXISTINO
EXISTING I
3 # I I I PANEL "A' I I PANEL "B' 1
400 CU,1TiW /
IN 3' COND. -, I I I I 1200 A. ML01 1150 A. ML01
_L 1 1 120/240 1 1 110,3w 1 110.3w 1
METER
I T I 1 1 PH.,3W I I 1120/24-OV I 1120/240V I
I M 1 I - - - -� A.I.c00.000 I I L -_ -J L_ _J
1 " -/ I I I I T
L EXISTTNGJ L _NE 3R J I
- MA - I I
EXISTING
F' - - I 3 # 4/0 CU. THW I EXISTING I
I I IN 2.5" COND. I 4 # 210 CU THW IN 2' COND. -J
IF- ------------------------ - - - -
I I I
L _ _ J GROUND FLOOR /EXTERIOR ( GROUND FLOOR /INTERIOR
I
EXISTING
150 A -2P
EXISTING ELECTRICAL RISER DIAGRAM
EXISTING 10 3W SERVICE
SERVICE
FROM
UTILITY
COMPANY
NEW 4 #4/0 THW, CU.
WIRES IN 2.5 "C. OVERHEAD
SERVICE FROM FP &L
FP&L DROP TO BE AT
EXISTING DROP LOCATION.
METER TO BE SET IN
PHASE 2 ON A SUNDAY
4 # 4/0 CUJH IN 2.5' COND.
4 # 4/0 CU,
IN 2.5' CONO.
150A MCB
r�
120/240 PANEL "C'
METER 3 PH.,4W 200 A, MLO
30,4W
120/24-OV
O A. I.C.: 10,000
NEMA 3R
GROUND FLOOR /EXTERIOR GROUND FLOOR /INTERIOR
#4 CU.
GROUND
M.C.W.P.
r1
WATER PIPE e
(MIN.)
GROUND WIRE �- 3/4 "0x10' -0 "L COOPER CLAD
TIED TO STRUCTURAL GROUND RODS DRIVEN INTO GROUND
STEEL IN FOUNDATION.
NEW ELECTRICAL RISER DIAGRAM
NEW 30 4W SERVICE
I
(EXISTING PANEL)
TYPE PANEL BOARD » » MAIN BUS 200 A.
SERVICE 10, 3W PANEL A MAINS M.C.B.
VOLTAGE 120/240 (EXISTING PANEL) A.I.C. 10,000
CONNEC.
KVA
POLE
TRIP
DUIT
WIRE
(REMARKS
CKT.
NO.
CKT.
NO.
REMARKS
WIRE
DUIT
TRIP
POLE
CONNEC.
KVA
6.00
2
40
3/4'
#6
EXIST. A,HU LOAD
1
3
*
'k
*
2
EXIST. SPACE
#8
3/4"
40
2
8.00
4
EXIST. SPACE
30
3/4"
#10
EXIST. LOAD
5
6.00
2
40
3/4'
#6
EXIST. A,HU LOAD
5
7
6
EXIST. SPACE
20
1/2"
#12
EXIST. LOAD
9
11
8
EXIST. SPACE
#12
1/2"
20
1
1.00
1.00
1
20
1/2"
#12
EXIST. LOAD
9
10
EXIST. LOAD
#12
1/2"
20
1
1.00
1.00
1
20
1/2"
#12
EXIST. LOAD
11
12
EXIST. LOAD
#12
1/2"
20
1
0.72
1.00
1
20
1/2"
#12
EXIST. LOAD
13
14
EXIST. LOAD
#12
1/2"
20
1
1.50
2.00
2
20
1/2"
#12
EXIST. CU LOAD
15
17
16
EXIST. LOAD
#12
1/2"
20
1
1.00
18
EXIST. LOAD
#12
1/2"
1 20
1
1.00
1.00
1
20
1/2"
#12
EXIST. LOAD
19
20
EXIST. LOAD
#12
1/2"
20
1
0.72
1.00
1
20
1/2"
#12
EXIST. LOAD
21cc
22
EXIST. LOAD
#12
1/2"
20
1
1 1.50
1.00
1
20
1/2"
#12
EXIST. LOAD
23
24
EXIST. LOAD
#12
1/2"
20
1
1.00
1.00
1
20
1/2"
#12
EXIST. LOAD
25
26
EXIST. LOAD
#12
1/2"
20
1
1.00
1.00
1
20
1/2"
#12
EXIST. LOAD
27c
28
EXIST. LOAD
#12
1/2"
20
1
0.72
1.00
1 1
20
1/2"
#12
JEXIST. LOAD
29
30
EXIST. LOAD
#12
1/2"
20
1
1.50
1.00
1
20
1/2"
#12
JEXIST. LOAD
31
32
EXIST. LOAD
#12
1/2"
20
1
1.00
1.00
1
1 20
1/2"
#12
EXIST. LOAD
33
34
EXIST. LOAD
#12
1/2"
20
1
1.50
5.00
2
40
3/4'
#6
EXIST. LOAD
35
37
36
EXIST. LOAD
#12
1/2"
20
1
1.00
38
40
EXIST. CU LOAD
#12
1/2"
20
2
2.00
39
40
39
_±L]
42
41
42
TOTAL LOAD: 47,160 VA - -- 197 AMPS.
LOAD CALCULATIONS:
BALANCE(25.94 KVA) 0100% : 25.940 VA
KITCHEN EQUIP. (21,220 KVA) 065% : 13,793 VA
TOTAL DEMAND LOAD :39,733 VA - -- 165 AMPS.
FEEDER:4 # 4/0 CU,THW IN 2.5" CONDUIT.
' - KIIL;HtN LUAUS
(EXISTING PANEL)
TYPE PANEL BOARD » » MAIN BUS 150 A.
SERVICE 10, 3W PANEL B MAINS M.o.B-
VOLTAGE 120/240 (EXISTING PANELS A.I.C. 10,000
CONNEC.
KVA
POLE
TRIP
DUIT
WIRE
(REMARKS
CKT.
NO.
CKT.
NO.
REMARKS
WIRE
CON DUIT
TRIP
POLE
CONNEC.
KVA
2.50
2
20
1/2"
#12
EXIST. LOAD
3
r
4
EXIST. CU LOAD
#8
3/4"
40
2
8.00
4.18
2
30
3/4"
#10
EXIST. LOAD
5
6
EXIST. AHU LOAD
#12
1/2"
20
2
2.50
1.00
1
20
1/2"
#12
EXIST. LOAD
9
11
10
EXIST. LOAD
#12
1/2"
20
1
1.00
12
EXIST. LOAD
#12
1/2"
20
1
0.72
1.00
1
20
1/2"
#12
EXIST. LOAD
13
14
16
EXIST. LOAD
#12
1/2"
20
2
2.40
1.60
1
20
1/2"
#12
NEW LIGHTING
15
1.60
1
20
1/2"
#12
NEW LIGHTING
17
18
20
EXIST. LOAD
#8
3/4"
40
2
5.50
o co
Sushi Maki
EXIST. SPACE
19
5812 S.W. 72nd
St.
"
South Miami Florida
21
22
EXIST. SPACE
Date
Dig t�ibution
'rro
23
24
•-
PERMIT SET 04 -17 -06
a.
N1..ti►j!
25
26
f ..
27
28
29
30
a ,
r
ENERGY SCIENCES INC
CONSULTING ENGINEERS
+!'
31
32
ESBER ANDIROGLU, P.E.
MECR /ELEC. - J42454 '
2821 DOUGLAS ROAD
J
t4
"
b
s +
MIAMI, FL 33133 I
TEL 305- 448 -8828
33
34
FAX 305 -448 -7375
e -mail energys®bellsouth.net
y
35
36
Sheet
37
38
39
40
41
42
TOTAL DEMAND LOAD 29,800 VA - -- 124 AMPS.
FEEDER:4 # 1/0 CU,THW IN 1 1/2" CONDUIT.
r'F
h
c �
ELECTRICAL NOTES
1. General
A. All work performed under this contract shall comply with
all national, state and local codes having jurisdiction
and with, the requirements of the utility companies whose
services shall be used. All modifications required by
these codes shall be made by this contractor without
additional charge.
B. Drawings: Refer to all drawings for coordination of the
electrical work.
C. Arrange and pay for all permits, licenses, inspections
and tests. Obtain the required certificates and present
to owner.
D. Guarantee: The completed installation shall be fully
guaranteed against defective materials and /or improper
workmanship for minimum of one year for material and labor.
2. Contractor is directed to review the building plans and
specifications for limitations of constructions,
identifications of materials and products, definition of
workmanship. This contractor shall include his bid
proposal all costs necessary for a complete and operational
installation and shall visit the job site prior to a bid date.
3. Contractor needs to establish a field liason with project
supervisor, prior to commencing work.
4. All required insurance shall be provided for protection
against public liability and property damage for duration
of the work.
5. It shall not be the intent of these plans and /or specifica-
tions to show every minor detail of construction. The
electrical contractor shall be expected to furnish and install
all items for a complete electrical system and provide all
requirements necessary for equipment to be placed in proper
working order.
6. Electrical contractor shall not scale drawings. Contractor
shall refer to architectural plans and elevations for exact
locations of all equipment unless otherwise noted.
7. All conduit runs are shown diagram mactically. Exact routing
shall be determined in the field, unless otherwise noted.
8. Electrical contractor shall visit the job site and verify all
conditions, locations, dimensions and counts as shown and /or
noted on the drawings. This shall include any and all
fabrications prior to installations.
9. As a minimum, all equipment shall meet applicable standards,
for the type of equipment and intended use, of the following:
C1. American National Standards Institute (ASTM).
b. Illuminating Engineers Society (IES).
C. American Society for Testing and Materials (ASTM)
d. National Electrical Manufacturers Association (NEMA).
Note: These standards are subordinate to codes, and
standards set by UL.
10. All electrical equipment, devices, wire, ect. shall be
listed, for the intended use, with Underwriter
laboratories, Inc. (UL), where standards have been
established by UL.
11. As -built drawings shall be furnished to the owner upon
completion of work.
12. Wiring devices to be spec. grade.
13. Where more than one devices is indicated at any location,
these shall be ganged under one common cover plate.
14. Contractor shall coordinate with electric and telephone
utility for service entrance location and any other require-
ments.
15. All connections to ground rods shall be made with UL approved
welded connections, unless noted otherwise.
16. Provide a fuse holder and fuse in the primary side of each
ungrounded conductor for all ballasts.
17. Unless noted as existing, all equipment, wiring, devices,
etc. shall be new.
Contractor shall guarantee all materials and workmanship free
from defects for a period of not less than (1) year from date
of acceptance, unless indicated of specified otherwise.
19. Correction of any defects shall be completed without
additional charge and shall include replacement or repair of
any other phase of the installation which may have been
damaged thereby.
20. Electrical contractor shall provide temporary service for use
of all trades as required for construction.
21. Temporary wiring to be removed by contractor.
22. Electrical contractor shall verify requirements, exact
location and type or outlet for all electrical fixtures,
appliances and equipment.
23. Shop Drawings: Coordinate requirements with architect.
24. All wiring to have 600 volt insulation, type TW, THW, THWN,
for branch circuits and type THW, THN for main feeders or as
specified.
25. Design is based on copper conductor. Wire size #10 and
smaller type "TW ", wire size #8 and larger type "THW" or
as specified.
26. Wire ways shall be sized as required, per NEC, unless
otherwise noted.
27. All feeder, subfeeder and branch circuits shall be properly
phase balanced.
28. All conductors shall be in conduits. All conduits shall be
intermediate (IMC) or rigid galvanized steel (RGS) except
that: (a) poly vinyl chloride (PVC) conduits may used in
concrete slabs at underground provided elbows and riser are
RGS; (b) electrical metallic tubing (EMT) may be used in or
on walls or ceilings where not subject to mechanical damage,
damp conditions or corrosive conditions; (c) liquid tight
flexible conduits where required; (d) flexible metallic
conduit where required in dry locations. All conduit
hazardous areas (per NEC) shall meet the requirements of NEV
Chapter. I t
29. Apply bitumostic coating to all metallic conduits in slabs +
or underground. >
30. Electrical contractor shall verify circuit protective device
rating for equipment prior to construction.
31. Provide fuse recommended by equipment manufacturer.
32. Furnish and install disconnect switches and wiring for air'>f
conditioning systems as per manufacturer recommendations. U -
Controls are to be supplied by air conditioning contractor.
33. Install power and control wiring and required control
components for air condition systems as shown /noted on �.
these drawin s and per other applicable drawings/instruc-
tions see A�C drawings.
34. Electrical contractor to run control wires for HVAC system
as per HVAC drawings.
35. No conduits to be run in ductwork.
36. All electrical wiring must be in conduit (no Romex, BX, etc.
is permitted unless specific permission is obtained from s+"',- .
owner, engineering or local inspector).
37. All light switches shall be white "Decora" �T
38. All switches shall be ganged
N�k
3
ELECTRICAL RISER & DIAGRAM `[
ARCHITECTURE PLANNING INTERIORS
U
H E , F. S H`
VI T'
At
C ORAZZI NJ!
300 ARAGON AVENUE -)#SUITE
CORAL GABLEP, FLORIDA
TEL• 305- 567 -6602,
FAX: 305 - 446 -3197 *;
FLORIDA REGISTRATION,'AA C2194,
cfl
r
Burton H. Hersh, AIA , ,p
Au -onAn „ r
f. 9a
Luigi Vitalini
AR -13513
Pablo Corazzini
AR -91716
t at
E-j3
H:,Curnm1,N.j.1 D, Rykm Plalrg,u3
U
cfl
r
co
4-J
O
.,
o
•, � Z '
s
O-
p�
Cd
o co
Sushi Maki
5812 S.W. 72nd
St.
"
South Miami Florida
&' Ject No. 04033
Date
Dig t�ibution
'rro
4
•-
PERMIT SET 04 -17 -06
a.
N1..ti►j!
f ..
a ,
r
ENERGY SCIENCES INC
CONSULTING ENGINEERS
+!'
"
ESBER ANDIROGLU, P.E.
MECR /ELEC. - J42454 '
2821 DOUGLAS ROAD
J
t4
"
b
s +
MIAMI, FL 33133 I
TEL 305- 448 -8828
4
tj k
FAX 305 -448 -7375
e -mail energys®bellsouth.net
y
Sheet
E-j3
H:,Curnm1,N.j.1 D, Rykm Plalrg,u3