Loading...
07-1421-001y r 1 PROVIDE, INSTALL, CONNECT & TEST FIRE ALARM EQUIPMENT INCLUDING CONTROL PANELS, VISUAL & AUDIBLE INDICATING APPLIANCES, MANUAL FIRE ALARM PULL STATIONS & SMOKE DETECTORS, 2 PROVIDE P.O.C. TO DUCT - MOUNTED SMOKE DETECTORS & AHU SHUTDOWN RELAYS TO FIRE ALARM CONTROL PANEL, 3 PROVIDE & INSTALL ALL WIRE & CABLE NECESSARY FOR A COMPLETE FIRE ALARM SYSTEM, INCLUDING CONNECTION TO DEVICES PROVIDED BY OTHERS. a. SPRINKLER WATERFLOW SWITCH b. SPRINKLER VALUE TAMPER SWITCH. 4 PROVIDE & INSTALL, 55 DEVICES & 1 FIRE ALARM CONTROL PANEL USE PLENUM RATED CABLE WITH STUB -UPS CKT#4 0.492A ® iiHliil- ' ss 11 75 I N tw 75 109 c ZONE /4 EOL� (Y--ZEOL ZONE/5 7 8 FLOOR PLAN SCALE: 1/8" = 1' -0" i 0.88�4� w4 CASHIER WOMEN ( MEN ?75 07 � 108 75 EOL CKT RT RI 0.82 A RT RTS � � � �- � ��� RT5 T T RT J \ WP �_7518 DINING AREA ! o , ,CR ®DD 17 1 \ / DINING AREA e, ! ' I ��4 W 102 g S 95 02 D(? -D— EOL ONE /7 :3 C" t — 106 - is ir3 f' � �` 7 C � t � wAtnNC ARE t tw CR n �%, //Z F '� 1 CR2 2p2o! j / f > �- ITO P /SX3 �_- ! ` DINING AREA \ ! RT3 RT RT RP4 �� __�; I ` 4EOL ZONE/2 SIGH 1 j — Cs C2 P CEILING HEIGHT V — ,,\ t v 3 75 P /S#C3 11 S THIS IS A SPRINKLED BUILDING 115 1W FIRE ALARM 71v017E& 1. THIS IS A POWER LIMITED FIRE ALARM SYSTEM. 6LL DEVICES OR KNITS„ SHALL BE INSTALLED USING APPROVED MATERIALS AND WIRING PRACj%; 11J ACCURD44410E W.TH THE NATIONAL ELECTRICAL CODE #70 AND THE NATIONAL FIR • ROTESTION -` A�SWIATION. ARTICLE #760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL WIRING CRII'f4ANCts" 2. CONDUCTORS AND CABLES FOR USE WITH THIS POWER LIMITED FIRE ALARM SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELVC i R!CAL• CUD1 : #766 P,OWE21 LIMITED SECTION AND SHALL BE LISTED FOR THIS USE. CONDUCTORS 6Ai,L HAVr' MINIIIUM RAIL "JG Of 304V AND SHALL BE OF FIRO I SOLID COPPER OR BUNCH - TINNED STRAN,,)EQ iOPP ONDUCTO2S. 1'HESIt CONDUCTORS OR CABLES SHALL BE FPLP OR FPLR IN ACCORDANCE WITH N �ARTICLE'7610 AJD NEC ARTICLE 725 CLASS 2 OR 3 CIRCUITS. A E 3. CONDUCTORS OR CABLES USED IN DUCTS OR PLENUM TYPE CEILING FOR ENVIRONMENT' AIR SHALL EMPLOY THE USE OF ELECTRICAL METAL TUBING OR PLENUM RATED INSULATED TYPE CABLE (FPLP). THE CABLE SHALL BE UL LISTED FOR SUCH USE AND MEET ALL THE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION. 4. ALL INDICATING DEVICES SHALL BE MOUNTED AT 80' A.F.F. FROM THE FLOOR TO THE BOTTOM OF THE LENS UNLESS OTHERWISE NOTED, AND SHALL BE UL LISTED 1971 ADA 75 CANDELA MINIMUM. 5. ALL MANUAL - INITIATING DEVICES SHALL BE MOUNTED AT 48' TO CENTER A.F.F. UNLESS OTHERWISE NOTED. 6. CUSTOMER TO PROVIDE (2) PHONE LINES FOR CERTIFICATED CENTRAL STATION MONITORING WITH DIFFERENT LONG DISTANCE CARRIERS, 10 WATT TOTAL 7. ELECTRICAL CONTRACTOR TO PROVIDE 110V DEDICATED CIRCUIT WITH 2OAMP CIRCUIT BREAKER, SPEAKER CKTJ1 USING 12AWG THHN TYPE WIRE WITH 600V MINIMUM INSULATION. IN 1/2' MINIMUM CONDUIT. THE 0 75 75 EOL PS(IC3 CKT #4 0.492A THE CIRCUIT BREAKER NUMBER AND PANEL SHALL BE NOTED AND MARKED IN ACCORDANCE 116 117 VOLTAGE DROP 0.45v TO NFPA 72, AND ANY LOCAL ORDINANCE. 3A PER CKT It 11 105 1W ilc;�kl FPLP FCPS -24FS8 POWER SUPPLY (2) 7AM BATTERIES C3 SEE NOTE%7 2Awc PANEL -B CKT112 2C 16AWG FPLP VOICE EVAC PANEL SP40S SPEAKER CKT 12 SPARE (2) 12AH BATTERIES C4 MIC C5 SEE NOTE(? 2Awc PANEL-8 CKT#12 0 E0L ZONE#10 SPARE EOL ZONE#9 SPARE 0 RT7 RT8 RT9 RT10 106 6AWG z D 2 D � ,p #Ea ZONE#8 SH fpLP 18 19 20 21 RT1 RT2 RT3 RT4 RTS RT6 2C /14AWG HUT 75 Y3 • FPIP 12 13 14 15 18 17 5m__ 11► X109 c ZONE13 6 (EH EOLNC MECH ROOM C� TO P/SJC3 101 T__IrltrlrIr- 1nriri .. . 1-­ ..ai -- .r- - Et BAR M1AI14i -DADS CO. FLiE DEPARThIENT APPLICATION #073:Xo-GI o'ag FIRE ALARM sHALL 13E A CENTRAL ,'NATION SeRVICB. A CERTIFICATE ,OR t�- D('.rICiJ, A5 P� h'�RA 72 1~'1RE AI ARNI SY51EM TO BE INSTALLED IN ACCORDANCE W11111 NF`PA72; 74;101 - a..:°rA / /�_1��.•o�•Yav+ +mow :-al..�.•1 -s: \w /�rn��. ty�)s w-a���� % % %.. 41..rV,a/`��1.7rSts.P�WY� MIAMI.OADE COUNTY EIRE DEPARTM! FT OLDO. PERMI FIRL ALARM FIRE 3UPPRE3SIQId Y MAIN EXT. €TY: ANSUL A EOL ZONE JS RT RTt 1 I n DINING AREA (2) 7AH BATTERIES SEE NOTE /7 PANEL-8 CKT/12 �/Y 0 8. ALL INITIATING AND INDICATING CIRCUITS SHALL BE STYLE Y (CLASS B) UNLESS OTHERWISE SPECIFIED. 75 JEOL PSJC3 CKT/3 0.936A VOLTAGE DROP 0.4SV TOTAL EOL ZONE/�5 I 114 3A PER CKT 8A MAX ANY TROUBLE CONDITION WILL BE ANNUNCIATEIAT THE MAIN PANEL, AND ANNUNCIATOR, ALSO SHUTDOWN A/C UNIT 10. ANY DUCT DETECTOR ALARM SHALL CAUSE THE AIR HANDLERS TO SHUT DOWN, P%3 CKT�2 0.828A g VOLTAGE DROP 0.41V 3A PER CKT 11. THIS SYSTEM WILL BE CERTIFICATED AS A CENTRAL STATION SERVICE FIRE ALARM SYSTEM. 12. ALLOWABLE AMPACITY ACCORDING TO CONDUCTOR SIZE. EOL ZONE /4 SIZE(AWG) ALLOWABLE AMPACITY VOLTAGE DROP 8 n 0 18 6 3A PER CKT 16 8 14 17 12 23 10 28 13. MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METAL TUBING. TYPE CONDUCTOR TRADE SIZES IN INCHES 7 TEN, TFFN 18AWG 22 38 63 108 148 244 TFN, TFFN 16AWG 17 29 48 83 113 186 THHN 14AWG 12 22 35 61 84 138 241 THWN 12AWG 09 16 26 45 61 101 176 THWN -2 IOAWG 05 10 16 28 38 63 111 ff EOL ZONEjF3 WIRE LEGEND CHART TYPE. CONDUCTORS/ DESCRIPT ION _ MARKINGS A 2 COND 18 AWG SOLID ADT493490 2C /18AWG TYPE FPLP /CMP(UL) B 4 COND 18 AWG SOLID ADT494449 4C /18AWG TYPE FPLP /CMP(UL) C 2 COND 14 AWG SOLID ADT493491 2C /14AWG TYPE FPLP /CMP(UL) 6 D 2 COND 18 AWG SOLID SHLD 860830A 2C /18AWG TYPE FPLP /CMP(UL) E 4 COND 18 AWG SOLID SHLD 860836 4C /18AWG TYPE FPLP /CMP(UL) F 4 COND 22 AWG SOLID ADT494468 4C /22AWG TYPE FPLP /CMP(UL) G 12 COND 22 AWG SOLID ADT494469 12C /22AWG TYPE FPLP /CMP(UL) H 2 COND 18 AWG SOLID BLACK BURIAL 180010 2C /18AWG TYPE FPLP /IRR(UL) 2 P JEOL ZONE12 5 r 40% FILL FOR ALL CONDUIT. 15. THE DESIGN INSTALLATION COMPLIES WITH FBC 11- 4.28.3 SEQUENCE OF OPERATION ANY INITIATING DEVICE ACTIVATED SHALL CAUSE THE FIRE ALARM PANEL TO GO INTO ALARM CONDITION, • • • 0 JEOL ZONE #1 2C /18AWG FPLP OR ZONE ON THE FRONT PANEAS WELL AS ANY REMOTE ANNUNCIATORS CONNECTED TO SYSTEM. ACTIVATE INDICATING DEVICES, TRANSMIT SIGNAL TO OFFSITE LISTED CENTRAL STATION AND ACTIVATE OR OPERATE OPERATE ANY AUX. RELAYS OR FUNCTONSAS NOTED ON FLOOR PLAN, 1 2 3 4 SEE SEQUENCE OF OPERATION MATRIX AS SHOWN ON PLANS. FIRE ALARM LEGEND CONTRACTOR SHALL COORDINATE ALL MOUNTING HEIGHTS AND FINAL LOCATIONS OF DEVICES WITH A REPRESENTATIVE (PRIOR TO ROUGH -IN). 2C /18AWG FPLP �AWC SHUTDOWN DESCRIPTION PART # CATALOG # MANUFACTURER 1, ,. .. CR2 CR1 ADT U N I M O D E 10 LED-10 REMOTE POWER SUPPLY - CIRCUIT EXPANDER CRIS CR5 CR4 CR3 ADT VEP FSA ALL I CR CR Fm —1c I REMOTE MICROPHONE CR WHEELOCK CR CR �• FIRE ALARM MANUAL PULL STATION F A C P C2 AND MUSIC AHU5 AHU4 I AHU3 AHU2 AHU1 1/2- SS 75 TO TELCO FOR CERTIFIED 40% I WHEELOCK PER ZONE CENTRAL STATION MONITORING (2) 7AH BATTERIES SEE NOTE /7 PANEL-8 CKT/12 C1 REVISIONS SECURITY SERVICES, INC. 7747 NW 48 ST SUITE #160 MIAMI FLORIDA 33166 112AWG (786) 331 -3940 FAX (786) 331 -3952 RISER'DIAGRAM NO.: DATES: BY: ISRAEL GARCIA EF 0001194 N.T.S. 2 OUTBACK STEAKHOUSE ... 1 s. . r . 1 �(, 3 5829 SW 73 STREET SUITE 101 SOUTH MIAMI. FLORIDA 33143 d` JAVECHP.E. owc BY. ,pT DESIGNED BY: FIRE ALARM PLAN IR.0 7) : �r iF1.ORDA38T76 5 ADT Q ,� f TH! 55t 0724 6 ATE SCALE: SHEET NO.: DWG. NO.: J <`;, Ii @�` �� • • •'' , 7 6/20/07 1/8" = 1' -0" 1 OF 2 00343 8. ALL INITIATING AND INDICATING CIRCUITS SHALL BE STYLE Y (CLASS B) UNLESS OTHERWISE SPECIFIED. 75 JEOL PSJC3 CKT/3 0.936A VOLTAGE DROP 0.4SV TOTAL 9. DUCT DETECTOR SEQUENCE OF OPERATION UPON ALARM DUCT DETECTOR SHALL ACTIVATE I 114 3A PER CKT 8A MAX ANY TROUBLE CONDITION WILL BE ANNUNCIATEIAT THE MAIN PANEL, AND ANNUNCIATOR, ALSO SHUTDOWN A/C UNIT 10. ANY DUCT DETECTOR ALARM SHALL CAUSE THE AIR HANDLERS TO SHUT DOWN, P%3 CKT�2 0.828A VOLTAGE DROP 0.41V 3A PER CKT 11. THIS SYSTEM WILL BE CERTIFICATED AS A CENTRAL STATION SERVICE FIRE ALARM SYSTEM. 12. ALLOWABLE AMPACITY ACCORDING TO CONDUCTOR SIZE. Ea PsilC3 CKT1 o.8 8 28A SIZE(AWG) ALLOWABLE AMPACITY VOLTAGE DROP 8 18 6 3A PER CKT 16 8 14 17 12 23 10 28 13. MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METAL TUBING. TYPE CONDUCTOR TRADE SIZES IN INCHES LETTER SIZE (AWG) 1/2' 3/4' V 1 -1/4' 1 -1/2' 2' 2-1/2' TEN, TFFN 18AWG 22 38 63 108 148 244 TFN, TFFN 16AWG 17 29 48 83 113 186 THHN 14AWG 12 22 35 61 84 138 241 THWN 12AWG 09 16 26 45 61 101 176 THWN -2 IOAWG 05 10 16 28 38 63 111 WIRE LEGEND CHART TYPE. CONDUCTORS/ DESCRIPT ION _ MARKINGS A 2 COND 18 AWG SOLID ADT493490 2C /18AWG TYPE FPLP /CMP(UL) B 4 COND 18 AWG SOLID ADT494449 4C /18AWG TYPE FPLP /CMP(UL) C 2 COND 14 AWG SOLID ADT493491 2C /14AWG TYPE FPLP /CMP(UL) D 2 COND 18 AWG SOLID SHLD 860830A 2C /18AWG TYPE FPLP /CMP(UL) E 4 COND 18 AWG SOLID SHLD 860836 4C /18AWG TYPE FPLP /CMP(UL) F 4 COND 22 AWG SOLID ADT494468 4C /22AWG TYPE FPLP /CMP(UL) G 12 COND 22 AWG SOLID ADT494469 12C /22AWG TYPE FPLP /CMP(UL) H 2 COND 18 AWG SOLID BLACK BURIAL 180010 2C /18AWG TYPE FPLP /IRR(UL) 14. ALL EQUIPMENT COMPATIBLE AND UL LISTED FOR FIRE SERVICE. 1/2' MIN EMC FOR STUBS r 40% FILL FOR ALL CONDUIT. 15. THE DESIGN INSTALLATION COMPLIES WITH FBC 11- 4.28.3 SEQUENCE OF OPERATION ANY INITIATING DEVICE ACTIVATED SHALL CAUSE THE FIRE ALARM PANEL TO GO INTO ALARM CONDITION, ON INITIATING DEVICE SUPERVISORY SIGNAL SHALL CAUSE THE FIRE ALARM PANEL TO SHOW A SUPERVISORY CONDITION, ALSO ON ANY TROUBLE CONDITION, BOTH THESE SIGNALS WILL DISPLAY THE BEVICE OR ZONE ON THE FRONT PANEAS WELL AS ANY REMOTE ANNUNCIATORS CONNECTED TO SYSTEM. ACTIVATE INDICATING DEVICES, TRANSMIT SIGNAL TO OFFSITE LISTED CENTRAL STATION AND ACTIVATE OR OPERATE OPERATE ANY AUX. RELAYS OR FUNCTONSAS NOTED ON FLOOR PLAN, SEE SEQUENCE OF OPERATION MATRIX AS SHOWN ON PLANS. FIRE ALARM LEGEND CONTRACTOR SHALL COORDINATE ALL MOUNTING HEIGHTS AND FINAL LOCATIONS OF DEVICES WITH A REPRESENTATIVE (PRIOR TO ROUGH -IN). SYMBOL DESCRIPTION PART # CATALOG # MANUFACTURER FIRE ALARM CABINET - INSTALLED 5' -O" AFF UNIMODE 10 ADT REMOTE POWER SUPPLY - CIRCUIT EXPANDER FCPS -24FS8 ADT VEP REMOTE POWER SUPPLY - CIRCUIT EXPANDER SP40S WHEELOCK Fm —1c I REMOTE MICROPHONE SPRM WHEELOCK �• FIRE ALARM MANUAL PULL STATION ADT- BG -12L ADT EONE/7 MAX 20 DEVICES SS 75 FIRE ALARM HORN - STROBE- "RED" CANDELLA 21- E70- 24MCW -FR WHEELOCK PER ZONE SS 95 CEILING SPEAKER - STROBE- "RED" CANDELLA -2-5- E90- 24MCC -FR WHEELOCK mwP WEATHERPROOF SPEAKER - STROBE- "RED" 75CD ET70WP- 2475W -FR WHEELOCK 7s FIRE ALARM STROBE- "RED" CANDELLA _75 -_ RSS- 24MCW -FR WHEELOCK 75 wp WEATHERPROOF STROBE- "RED" CANDELLA _ 75 _ RSSWP- 2475W -FR WHEELOCK 75 C CEILING STROBE- "RED" CANDELLA 75_ RSS - 24MCC -FR WHEELOCK FLOW SWITCH - PROVIDE 4' SQ. BOX P.O.C. BY OTHERS TAMPER PROOF STITCH P.O.C. BY OTHERS @D DUCT SMOKE DETECTOR P.O.C. BY OTHERS r;1%P PHOTO ELECTRIC SMOKE DETECTOR 2151 ADT NO HEAT DETECTOR 5451 ADT .NT COMPATIBLE CR CONTROL RELAY MR -101/C ADT ED FOR FIRE SERVICE IC FOR STUBS FSA LED ANNUNCIATOR LED -10 ADT 2 ALL ® REMOTE TEST BUTTON RTS- 451KEY SYSTEM SENSOR ANSUL SYSTEM P.O.C. BY OTHERS C1 REVISIONS SECURITY SERVICES, INC. 7747 NW 48 ST SUITE #160 MIAMI FLORIDA 33166 112AWG (786) 331 -3940 FAX (786) 331 -3952 RISER'DIAGRAM NO.: DATES: BY: ISRAEL GARCIA EF 0001194 N.T.S. 2 OUTBACK STEAKHOUSE ... 1 s. . r . 1 �(, 3 5829 SW 73 STREET SUITE 101 SOUTH MIAMI. FLORIDA 33143 d` JAVECHP.E. owc BY. ,pT DESIGNED BY: FIRE ALARM PLAN IR.0 7) : �r iF1.ORDA38T76 5 ADT Q ,� f TH! 55t 0724 6 ATE SCALE: SHEET NO.: DWG. NO.: J <`;, Ii @�` �� • • •'' , 7 6/20/07 1/8" = 1' -0" 1 OF 2 00343