05-875-018ELECTRICAL NOTES 1. THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), AND THE LATEST EDITION OF THE FLORIDA BUILDING CODE AND ANY OTHER APPLICABLE FEDERAL, STATE AND LOCAL CODES. 2. A LICENSED ELECTRICAL CONTRACTOR SHALL PERFORM ALL WORK IN A WORKMANLIKE MANNER. SAID CONTRACTOR SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES. 3. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 4. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN (1) ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE. 5. IT SHALL NOT BE THE INTENT OF THESE PLANS AND /OR SPECIFICATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. CONTRACTOR SHALL FURNISH AND INSTALL ANY ADDITIONAL CONDUITS, BOXES AND WIRING NECESSARY FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING CONDITION. 6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO ORIGINAL CONDITIONS, ANY AND ALL DAMAGES TO THE BUILDING SURFACES, EQUIPMENT, ETC. CAUSED DURING THE PERFORMANCE OF WORK. 7. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE OR DELAYS AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION, WHICH MAY HAVE BEEN DAMAGED. 8. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL EXISTING CONDITIONS, AND SHALL THOROUGHLY REVIEW ALL DRAWINGS, SPECIFICATIONS AND POSSIBLE ADDENDA PRIOR TO BIDDING ON HIS WORK. NO EXTRAS TO HIS CONTRACT WILL BE ALLOWED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT. 9. THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE. 10. CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES SO THAT INTERFERENCE WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL AND STRUCTURAL MEMBERS BE AVOIDED, BEFORE THE COMMENCEMENT OF THE WORK. 11. CONTRACTOR SHALL TAKE PERMITS, PROCURE CERTIFICATES AND PAY ALL FEES CONNECTED THEREWITH. 12. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCED ORDERING OF LONG LEAD ITEMS, AS TO NOT INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT ORDER ANY ITEMS UNTIL APPROVED SHOP DRAWINGS ARE RETURNED TO HIM.13. CONTRACTOR SHALL COORDINATE SERVICES WITH THE RESPECTIVE UTILITY COMPANIES. 14. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF CEILING CONSTRUCTION BEFORE ORDERING OR INSTALLING LIGHT FIXTURES. 15. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY BALANCING ALL BRANCH CIRCUITS BETWEEN THE PHASES OF THE SYSTEM REGARDLESS OF CIRCUITING INDICATED. 16. ALL CONDUCTORS SHALL BE COPPER, TYPE THHN /THWNNN EXCEPT WHERE OTHERWISE REQUIRED BY U.L. OR CODES. 17. APPLY TWO COATS OF BITUMASTIC (KOOPERS 60) TO ALL METALLIC CONDUITS IN SLABS OR UNDERGROUND. EMT IS NOT PERMITTED IN SLABS. ALUMINUM CONDUITS ARE NOT PERMITTED ANYWHERE. 18. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BOXES SUCH THAT NO SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360 DEGREES, OR 180 DEGREES FOR TELEPHONE. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE AND WITH IRON COVERS. WARNING TAPES, WHICH READ, "WARNING- BURIED ELECTRIC" SHALL BE PLACED IN TRENCHES ABOVE ALL ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDER PAVED AREAS, THEY SHALL BE GRC. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC. ELBOWS AND RISERS SHALL BE GRC. 19. ALL CONDUITS RUNS ARE SHOWN DIAGRAMMATICALLY. THE EXACT ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS NOTED OTHERWISE. LIGHTING CEILING MOUNTED LIGHTING FIXTURE OUTLET PROVIDE CEILING MTD. J -BOX WALL MOUNTED LIGHTING FIXTURE OUTLET PROVIDE WALL MTD. J -BOX ( l EXTERIOR WALL MOUNTED LIGHTING FIXTURE OUTLET PROVIDE WEATHER WALL MTD. J BOX NOTE: ALL LIGHTING FIXTURES SHALL BE SELECTED AND PROVIDED BY OWNER AND INSTALLED BY THE CONTRACTOR. RECEPTACLES 20A, 125V, 2P, 3W, GNDING TYPE DUPLEX RECEPTACLE MTD 18" AFF 20A, 125V, 2P, 3W, GNDING TYPE QUAD RECEPTACLE MTD 18" AFF CONDUITS -' - CONCEALED CONDUIT (SWITCHED) CONCEALED CONDUIT BATH LIGHT ELECTRICAL SYMBOLS LEGEND MISCELLANEOUS SYMBOLS GROUND v PHONE LINE JACK MOUNTED 18" A.F.F. UNLESS OTHERWISE NOTED. EXTEND 1/2" CONDUIT W /BUSHED END UP TO CEILING SPACE. TV CABLE TV JACK MOUNTED 18" A.F.F. UNLESS OTHERWISE NOTED. EXTEND 1/2" CONDUIT W /BUSHED END UP TO CEILING SPACE. POWER DISTRIBUTION 0 120/24OV, 10, 3W PANELBOARD 2P— DISCONNECT SWITCH. 2P = # OF POLES, 30 30 = FRAME SIZE, * = FUSE PER MANUFACTURERS RECOMMENDATIONS. FIRE ALARM SYSTEM PROVIDE NEW MASTEREEDROOM AND BEDROOM WITH AFCI BRANCH CIRCUIT PROTECTION PER NEC 210.12 (THIS PERTAINS TO ALL OUTLETS, INCLUDING RECEPTACLES LIGHTS AND SMOKE DETECTORS) SWITCHED LEG CONTROL WIRING TO OTHER SMOKE DETECTOR INSIDE THE SAME UNIT. SEE PLANS SMOKE DETECTOR LIGHT SWITCH NEUTRAL SMOKE DETECTOR W/ BATTERY BACK -UP LINE SIDE OF SWITCH 120 V. LINE SMOKE DETECTOR CONNECTION DETAIL NOT TO SCALE ABBREVIATIONS E.F. EXHAUST FAN M.C.B. MAIN CIRCUIT BREAKER V VOLT 0 PHASE W.P. WEATHER PROOF A.F.F. ABOVE FINISHED FLOOR G.F.I. RECEPTACLE W /INTEGRAL Li GROUND FAULT CIRCUIT U INTERRUPTER A. F. C. 1. RECEPTACLE W /INTEGRAL ARC FAULT CIRCUIT U� INTERRUPTER SD SMOKE DETECTOR WITH VISUAL SIGNALING APPLIANCE 120 VOLT WITH INTEGRAL BATTERY BACKUP. CEILING MTD "GENTEX" MODEL 7109CS SYNCHRONIZED W/ FORM C CONTACTS HARD WIRE TO THE BATHROOM LIGHTING CIRCUIT. TOGGLE SWITCHES SINGLE POLE SWITCH, 20A, 125 VOLT RATED MTD 48" AFF $3 20A, 120V THREE WAY SWITCH MTD. 48" AFF _I • n FA_ f0 ON i r\ r 1 � • Q o C DRAWN BY OLIO C SILVA cl-IECKm BY Ya H JOB No. 2004-0005 PAGE IWEI E. n Li O U I U� N o Q CEO — O LL U U) LL_ I N - r ) V ! 0 Q Lc) FA_ f0 ON i r\ r 1 � • Q o C DRAWN BY OLIO C SILVA cl-IECKm BY Ya H JOB No. 2004-0005 PAGE IWEI E.