05-213-010
GENERAL ELECTRICAL NOTES: 1.0 -GENERAL 1.1 - WORK INCLUDED UNDER THIS DIVISION CONSIST OF PROVIDING LABOR MATERIALS, APPLIANCES, EQUIPMENT, TOOLS, TRANSPORTATION, SUPERINTENDENCE AND SERVICES REQUIRED TO CONSTRUCT AND INSTALL COMPLETE AND PROPER OPERATING ELECTRICAL SYSTEMS AS SPECIFIED, INDICATED AND ELSEWHERE REQUIRED. 2.0 - EXAMINATION OF SITE 2.1 - BIDDER IS ADVICED TO VISIT THE SITE AND ACQUAINT HIMSELF WITH WORKING CONDITIONS. CONTRACTOR SHALL ACCEPT CONDITIONS AS THEY EXIST ON BID DATE. 3.0 - MATERIALS 3.1 - MATERIALS, EQUIPMENT AND APPLIANCES SHALL BE NEW AND OF BEST QUALITY UNLESS OTHERWISE INDICATED. 3.2 - DETERMINE THAT PROPOSED EQUIPMENT CAN BE INSTALLED IN SPACE AVAILABLE. INSTALL EQUIPMENT SO PARTS ARE READILY ACCESSIBLE FOR INSPECTION AND MAINTENANCE EXTRA COMPENSATION WILL NOT BE ALLOWED FOR DISMANTLING EQUIPMENT TO OBTAIN ENTRANCE INTO BLDG. 3.3 - MATERIALS SHALL BEAR UNDERWRITER'S LABEL WHERE SUCH STANDARDS HAVE BEEN STABLISHED AND LISTED BY UNDERWRITER'S LABORATORIES INC. 3.4 - MATERIALS, EQUIPMENT AND APPLIANCES SHALL CONFORM TO LATEST STANDARDS OF: AMCA, SMACNA, ANSI, ASHRAE, ASME, ASTM, NEMA, ARI AND NFI•A. 3.5 - USE EXTREME CARE IN SELECTION AND INSTALATION OF EQUIPMENT TO INSURE THAT NOISE AND VIBRATION ARE HELD TO ABSOLUTE MINIMUM. CORRECT OBJECTIONABLE NOISE AND VIBRATION. PROVIDE ELIMINATORS REQUIRED FOR PROVER RESULTS. 4.0 - PERMITS, FEES AND CODES 4.1 - COST FOR FEES, PERMITS, TESTS NAD INSPECTIONS SHALL BE PAID FOR BY THE CONTRACTOR. 4.2 - INSTALLATION SHALL BE IN ACCORDANCE WITH APPLICABLE CODES AND REGULATIONS INCLUDING: F.B.C., N.E.C., N.F.P.A., O.S.H.A. AND STATE, COUNTY AND CITY DEPARTMENTS OF HEALTH. 5.0 - COOPERATE WITH OTHER TRADES 5.1 - MAKE KNOWN ARRANGEMENT OF WORK AND CHECK ARRANGEMENT AND LOCATION OF OTHER TRADES TO AVOID CONFLICTS. EXAMINE DRAWINGS OF OTHER TRADES TO DETERMINE EXACT EQUIPMENT LOCATION. 6.0 - OPERATING INSTRUCTIONS 6.1 - CONTRACTOR SHALL PROVIDE TO OWNER OPERATION AND MAINTENANCE MANUALS. CONTRACTOR SHALL INSTRUCT OWNER OR OWNER'S REPRESENTATIVE IN OPERATION OF ALL EQUIPMENT. TYPE WRITTEN LABELS SHALL BE PLACED IN PANEL BOXES DESIGNATING CIRCUITS LAYOUTS. 7.0 - INSPECTION 7.1 - NOTIFY OWNER TWENTY -FOUR HOURS IN ADVANCE WHEN PIPING OR EQUIPMENT IS TO BE TASTED, BEFORE PIPING IS INSULATED OR CONCEALED, AND BEFORE TRENCHES ARE BACKFILLED. 7.2 - FAILING TO COMPLY WITH THE ABOVE, CONTRACTOR SHALL UNCOVER AND RETEST LINES, REPAIRIG DAMAGE TO OTHER CONTRACTOR'S WORK, AS WELLAS HIS OWN. 7.3 - BEFORE REQUESTING FINAL PAYMENT, INSPECT INSTALLATION TO ASSURE THAT WORK IS COMPLETE AND REQUIREMENTS OF CONTRACT HAVE BEEN FULFILLED. • 9.0 - CUTTING AND PATCHING 9.1 - UNLESS OTHERWISE INDICATED, DO NO MORE CUTTING AND PATCHING THAN REQUIRED FOR INSTALLATION OF WORK. 8.2 - CUTTING OF STRUCTURAL MEMBERS OR EXPOSED SURFACE OF CONCRETE BLOCK WILL NOT BE PERMITED. 9.0 - MATERIALS AND EQUIPMENT 9.1 - CONDUCTORS SHALL BE THWN COPPERAS NOTED ON DRAWINGS. 9.2 - RECEPTACLES, SWITCHES AND TELEPHONE OUTLETS SHALL BE AS MANUFACTURED BY LEVITON, HUBBEL OR APPROVED EQUAL. COLOR AND STYLE AS SPECIFIED BY ARCHITECT AND /OR OWNER. 6.3 -COMPUTER OUTLETS: (IF APPLICABLE) SHALL BE AS SPECIFIED BY OWNER. 9.4 - PANELBOARDS: A. GENERAL: INTERRUPTING CAPACITY RATINGS SHALL BE VERIFIED AND BASED ON THE AVAILABLE SYMMETRICAL FAULT CURRENT GIVEN BY THE POWER COMPANY UPON LOCATION AND INSTALLATION OF TRANSFORMER. B- DIRECTORY: COMPLETE AT END OF JOE, TYPEWRITTEN. C- FINISH: ANSI #61 ENAMEL OVER A RUST INHIBITING TREATMENT AFTER FABRICATION AND BEFORE ASSEMBLY. AFTER INSTALLATION , AND BEFORE ACCEPTANCE BY OWNER, ASSEMBLY SHALL BE PAINTED WITH A RUST INHIBITING PAINT ( COLOR SELECTED BY ARCHITECT) D- NAMEPLATES: PROVIDE A LAMACOID NAMEPLATE WITH 5/16" LETTERS ENGRAVED ON FRONT FACE SHOWING PANEL NAME, VOLTAGE AND PANEL RATING. COORDINATE TO GIVE SAME NAME AS SHOWN ON PANELBOARD SCHEDULE. 9.5 - FIXTURES: A. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL LIGHTING FIXTURES AS SPECIFIED ON DRAWING WITH OWNER AND /OR ARCHITECT APPROVAL_ VERIFY BEFORE PURCHASE AND INSTALLATION. 9.6- LAMPS: ALL LAMPS USED ON THIS PROJECT SHALL BE NEW, DELIVERED TO THE JOB SITE IN THE ORIGINAL PACKING CASES AND SLEEVES AND SHALL BE OF THE SAME MANUFACTURER UNLESS OTHERWISE SPECIFIED. 9.7 - BALLAST: ALL BALLAST SHALL BE RATED TO OPERATE AT THE SERVICE VOLTAGE AS SHOWN AND AS SPECIFIED, PLUS OR MINUS THE DEVIATIONS WITH THE ELECTRIC SERVICE COMPANY IS ALLOWED BY FRANCHISE. 10.0 -FUSES A - SUPPLY AND INSTALL ALL FUSES IN EACH FUSED DEVICE. B - ALL AIR CONDITIONING AND KITCHEN EQUIPMENT SHALL BE FUSED AS PER MANUFACTURER'S RECOMENDATIONS AND SPECIFICATIONS. C - INSTALL LABELS IN ALL FUSED DEVICES INDICATING PROPER SIZE FUSE TO USE. 11.0 - MISCELLANEOUS 11.1 - ALL EMPTY CONDUIT TO BE SUPPLIED WITH NYLON PULL WIRE. 11.2 - ALL FLEX CONDUIT SHALL HAVE "TITE- BITE" CONNECTORS. 11.3 - ELECTRICAL CONTRACTOR TO INSTALL AND WIRE OUTLETS IN FIXTURES WHERE SHOWN ON DRAWINGS - OUTLETS TO BE INSTALLED IN FIXTURES AFTER FIXTURES INSTALLATION. 11.4 - ALL DEDICATED CIRCUITS SHALL BE LABELED AS SUCH AT OUTLET. 11.5 - THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND VERIFYING THE TELEPHONE COMPANY REQUIREMENTS FOR INSTALLATION OF SERVICE AND ADVISE THE OWNER AND /OR THE ENGINEER OF ANY ADDITIONAL REQUIREMENTS THAT MAY BE NECESSARY. 11.6 - THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND VERIFYING THE ELECTRICAL COMPANY'S REQUIREMENTS AND SERVICE ENTRANCE FOR THE BUILDING TO MAIN ELECTRICAL ROOM. 11.7 - ALL OUTLETS PLATES SWITCHES ETC. TO BE WHITE. ELECT. METER ELECT. SERVICE ma 2 I) 200 f �3/0 THW -CU 2 "O #2 IN 1" COND. TO STRUCTURAL STEEL IN FOOTING CONNECT TO A CONCRETE ENCASED ELECTRODE BOND TO A 5/9 "x10' GND. RODS ( SEE DETAIL) PANEL "A" 200 A 5AFETY A/C COMP. UNIT 4'X5' J ' CC7NC. SLAB (I / II II I I sAm=TY CxLAr, I I I I I I I ELEGTi2ICAL fRI5Ef' �) 1AGf At'*1 1/4" = 1'- 0" I CONCRETE FOUNDATION ' 20 FT. MIN.+ AA z 4 A " -III -I -_El I I -I I I i-- -1 I ICI I ICI I I�I I I -I I GROUNDING ELECTRODE CONDUCTOR BOLTED -TYPE CONNECTIONDEVICE OR EXOTHERMIC WELD GROUNDING ELECTRODE CONDUCTOR NONMETALLIC PROTECTIVE SLEEVE • , N•.4 AVG. OR LARGER BARE COPPER CONDUCTOR OR STEEL REINFORCING BAR OR ROD NOT • LESS THAN 1/2 INCH DIAMETER. i i CONNECT TO A CONCRETE - ENCASED ELECTRODE CONSISTING OF AT LEAST 20 FT. OF ONE OR MORE BARE OR ZINC GALVANIZED STEEL REINFORCING BARS OF NOT LESS THAN 112 INCH OR CONSISTING OF AT LEAST 20 FT. OF BARE COPPER CONDUCTOR NOT SMALLER THAN No. 4 AND LOCATED WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH EARTH. ENCASE GROUNDING ELECTRODE DETAIL SCALE: 3/4 " =1' -O" ELECTRICAL SYMBOL LIST: DQE 3 W. GROUNDED DUPLEX RECEPTACLE 20 A. 120 V. M.H.+12 " A.F.F. 4 3 W. GROUNDED SINGLE RECEPTACLE 30 A. 240 V. M.H. +12" A.F.F. rV 3 W. GROUNDED SINGLE RECEPTACLE 60 A. 240 V. M.H. +12" A.F.F. KD PUSH BOTTON OJ JUNCTION BOX CIELING OR FLOOR MOUNTED JUNCTION BOX WALL MOUNTED M.H. AS DIRECTED VOICE DATA OUTLET M.H. + 12" A.F.F. OR AS INDICATED TELEVISION OUTLET M.H. +12" A.F.F. INTERCOM THERMOSTAT M.H. +50" A.F.F. ( REFER TO A/C DWGS. FOR LOCATION) MOTOR OUTLET ELECTRICAL PANEL ® SWITCH BOARD FUSED DISCONNECTED SWITCH W/ DUAL ELEMENT FUSES C.B CIRCUIT BREAKER (HACR TYPE IF FOR A/C UNIT) INCANDESCENT FIXTURE OUTLET CIELING MOUNTED FO INCANDESCENT FIXTURE OUTLET WALL MOUNTED Q RECESSED HI -HAT LIGHT CEILING MOUNTED -0- CEILING FLUORESCENT STRIP son FLOODLIGHT P t r I n n r EMERGENCY LIGHT WITH BATTERY BACK UP SERVICE EXIT LIGHT WALL MOUNTED ® EXIT LIGHT CIELING MOUNTED _ _ W • SINGLE POLE TOGGLE SWITCH M.H. 50" All _ F Y WY rV V '� THREE WAY SWITCH M.H.50 "A.F.F 3 GENERAL LIGHTING 5331* SINGLE POLE SWITCH W/ DIMMER M.H. 50" A.F.F s.D ELECTRICAL SMOKE DETECTOR DEVICE F.D ELECTRICAL FIRE DETECTOR DEVICE 1 EXHAUST FAN C.4 CEILING FAN G.F.I. GROUND FAULT INTERRUPTER W.P. WATER PROOF. V.P. VAPOR PROOF. 240 V. OUTLET �Q METER sP SPEAKER ELEGTFRfCAL FLAN 1/4 = V -0" • 10 •• son PANEL A P t r I n n r PANEL C SERVICE SQ. FT, 1777 _ _ W • F.. ti.. _ F Y WY rV V '� 0 w (q "- GENERAL LIGHTING 5331* . i G V Y V . • Y 6000 1 2 GENERAL LIGHTING WASHER «•« ,D« • W F r• «• W , . REFRIGERATOR 1500 1/2" 12 DISHWASHER 1500 4 RECEPTACLE 12 WATER HEATER 4000 C7 20 20 1 * 1/2" 12 RECEPTACLE 5 CV RECEPTACLE 12 1/2" SUB -TOTAL V.A. 19931 20 20 1 * LO r 0 0 • • a • 10000 12 di 0 REST 40% r« • • W• i W o v v 1/2" 12 G.F.I. BATH RECEPT. 9 10 W V • • v • W v W • O 20 20 r 1500 . RANGE .. .. L) KITCH. RECEPT. SMALLAPL. a 5400 1500 1 « « « T • « V • . , 1500 1/2" 12 TOTAL V.A. DEMAND 45662 14 REFRIGERATOR 12 1/2" 1500 1 20 50 AMPS DEMAND (V.A./240V) 190 314" 3#6 RANGE /OVEN 15 o WASHERIDRYER 2*9 i 3/4" BREAKER 200 30 ir• • «•i•• «•f. •««• C � �L • • • RECEPTACLE 19 LU DISHWASHER 12 v ! Y• Y • • V i W W 50 2 U 3/4" 0 A/C #1 21 22 A.H.U. #1 2#6 3/4" 10930 ('1 2 so r••• • •r••• c •r, • •«C• r 23 24 30 2 4000 1/2" PANEL A ITEM PANEL A PANEL B PANEL C SERVICE SQ. FT, 1777 Z U REMARKS w o 0 '� 0 w (q "- GENERAL LIGHTING 5331* 1/2" 12 SMALL APPLIANCES 6000 1 2 GENERAL LIGHTING WASHER 1500 * 1 15 REFRIGERATOR 1500 1/2" 12 DISHWASHER 1500 4 RECEPTACLE 12 WATER HEATER 4000 1 20 20 1 * 1/2" 12 RECEPTACLE 5 1 RECEPTACLE 12 1/2" SUB -TOTAL V.A. 19931 20 20 1 * 1/2" 12 RECEPTACLE 7 1st. 10KW 10000 12 1/2" * REST 40% 3932 20 1 1/2" 12 G.F.I. BATH RECEPT. 9 10 AIR HANDLER UNIT #1 10930 1/2" 0 1 20 20 1 1500 1/2" RANGE 15500 11 12 KITCH. RECEPT. SMALLAPL. DRYER 5400 1500 1 20 20 1 1500 1/2" 12 TOTAL V.A. DEMAND 45662 14 REFRIGERATOR 12 1/2" 1500 1 20 50 AMPS DEMAND (V.A./240V) 190 314" 3#6 RANGE /OVEN 15 16 WASHERIDRYER 2*9 i 3/4" BREAKER 200 30 17 19 1 #10 20 1 1/2" 12 RECEPTACLE 19 20 DISHWASHER 12 1/2" 1500 1 20 50 2 5060 ( **j 3/4" 2#9 A/C #1 21 22 A.H.U. #1 2#6 TYPE: SQUARE "D" QD (OR EQUAL,I P AN E L A ( TYPICAL) MAIN: 200 A VOLTAGE: 120/240 V. 10 3W. FEEDER: 3)#3/0 THW -CU MOUNTING: FLUSH (ALL 20 AMPS, 1 POLE CKTS. EXCEPT AS NOTED) CONDUIT: 2" (0 U. w 0 1 0 > F- Z O0 �_ REMARKS Z Z U REMARKS w o 0 '� 0 w (q "- 15 1 1/2" 12 GENERAL LIGHTING 1 1 2 GENERAL LIGHTING 12 1/2" * 1 15 20 1 1/2" 12 RECEPTACLE 3 4 RECEPTACLE 12 1/2" * 1 20 20 1 * 1/2" 12 RECEPTACLE 5 1 RECEPTACLE 12 1/2" * 1 20 20 1 * 1/2" 12 RECEPTACLE 7 9 RECEPTACLE 12 1/2" * 1 20 20 1 1/2" 12 G.F.I. BATH RECEPT. 9 10 SMOKE DETECTOR 12 1/2" 0 1 20 20 1 1500 1/2" 12 KITCH. RECEPT. SMALLAPL. 11 12 KITCH. RECEPT. SMALLAPL. 12 1/2" 1500 1 20 20 1 1500 1/2" 12 KITCH. RECEPT. SMALLAPL 13 14 REFRIGERATOR 12 1/2" 1500 1 20 50 2 15500 314" 3#6 RANGE /OVEN 15 16 WASHERIDRYER 2*9 i 3/4" 5400 2 30 17 19 1 #10 20 1 1/2" 12 RECEPTACLE 19 20 DISHWASHER 12 1/2" 1500 1 20 50 2 5060 ( **j 3/4" 2#9 A/C #1 21 22 A.H.U. #1 2#6 3/4" 10930 ('1 2 so 23 24 30 2 4000 1/2" 10 WATER HEATER 25 26 RECEPTACLE 12 1/2" * 1 20 27 29 KITCH, RECEPT. SMALLAPL. 12 1/2" 1500 1 20 29 30 31 32 33 34 35 36 37 39 39 40 41 42 y(� ••�e•••z FEEDER:SEE RISER ••� ,' CONNECTED LOAD :SEE LOAD CALCULATION ' !.r (A/C RATING 22,000 AMPS) FED FROM:SERVICE ('I AC COMPRESSOR @ AIR HANDLER UNIT LOADS ARE NOT CONCURRENT. NOTE: ALL BEDROOM AND SMOKE DETECTOR CIRCUITS TO BE ARC FAULT PROTECTED P.4", so SHEET: E -1 OF: 1 In., w mo �w f M c" 7 L ❑ M C cf) 1 w ❑ w �C z C) J Z LL . 0 0 w m LL J IV U) w w C © > _ �0 U) O r-- U) � ? CL (� Lu ADC W w j O _ LO 0 00 J < C.0 Z OD 0 0 0 P.4", so SHEET: E -1 OF: 1 In., w mo �w f L C 1 w �C C) J Z LL . w- 0 w J IV w w C Z mow/ W U) O r-- U) � ? �[ ADC W vJ O _ LO 0 00 J < m P.4", so SHEET: E -1 OF: 1 In., w mo �w f